2 - INSTALLATION

2.6 - Horizontal or ceiling installation (42SIC or 42SIN)

Using the paper template, trace on the ceiling the position of the two fixing brackets and the two rear screws. Using a suitable drill, 

make the holes and insert the toggle bolts (2 for each bracket); fix the two brackets. Do not over-tighten the screws. Position the 

machine on the two brackets, keeping it in position and then fix the two screws into the rear toggle bolts, one on each side.
Make sure that there is sufficient inclination of the unit towards the drainage pipe to facilitate the water drainage.
Fully tighten all 6 fixing screws.

For installation of the 42NSIC versions, horizontal condensation collection basin accessory kits are available GB0520/GB0524.
The installation of 42SIR (low height with cabinet) units in horizontal position is prohibited.

 Carefully check the inclination of the exhaust pipe. Any counterslope of the discharge line can cause water leakage

B

B

C

C

D

E

B

toggle bolts

C

brackets

D

screws

E

drainage pipe

2.7 - Mounting front grill safety support (42SIC)

In the case in which the cooler-convector is installed in a horizontal position, to guarantee the safety of the cleaning/filter replacement 

operations it is obligatory that the two clamps, in the supplied bag together with the instruction manual and the accessories, are mounted 

by the installer.

 Install braces to prevent the fall of the grid.

 

-

Separate the two clamps;

 

-

open the front grill and completely unscrew the fixing screws on the springs;

 

-

fix the two clamps, blocking them by retightening the screws;

 

-

fix the other part of the clamp to the grill using the supplied screw;

 

-

close the grill.

B

B

C

D

B

Ties

C

Screws fixing springs

D

grid

Summary of Contents for 42SIC

Page 1: ...Original document INSTALLATION OPERATION AND M A I N T E N A N C E I N S T R U C T I O N S 42SIC 42SIR 42SIN 42SIl...

Page 2: ...CHNICAL CUSTOMER SERVICE Safety pictograms Generic danger Signals to the personnel that the operation described could cause physical injury if not performed according to the safety rules Danger of hig...

Page 3: ...n 42SIC or 42SIN 7 2 7 Mounting front grill safety support 42SIC 7 2 8 Horizontal or ceiling installation 42SIC or 42SIN 8 2 9 Hydraulic connections 8 2 10 Condensation discharge 9 2 11 Filling the sy...

Page 4: ...odically open the windows to ensure a correct change of air This instruction leaflet is an integral part of the unit and consequently must be kept carefully and must ALWAYS accompany the unit even whe...

Page 5: ...de in case of ceiling installation the airflow is not directed towards persons 2 2 Installation modes The following descriptions of the various mounting phase and the relative designs refer to a versi...

Page 6: ...efer to the individual instructions leaflets supplied and the relative manual for the mounting of the feet Using the paper template trace the position of the two fixing brackets on the wall Use a suit...

Page 7: ...lation of 42SIR low height with cabinet units in horizontal position is prohibited Carefully check the inclination of the exhaust pipe Any counterslope of the discharge line can cause water leakage B...

Page 8: ...zes 29 49 69 89 99 Pipeline diameter mm 14 14 16 18 20 The choice and sizing of the hydraulic lines must be made by an expert who must operate according to the rules of good technique and the laws in...

Page 9: ...ld interfere with the normal outflow If there is a height difference that could interfere with the outflow of the condensation a pump must be mounted in a vertical installation mount the pump under th...

Page 10: ...sition take a screwdriver and act on the highest breather of the battery for appliances installed in a horizontal position act on the highest positioned breather for the 4 pipe versions act on the hig...

Page 11: ...the risk of burns Do not use abrasive sponges or abrasive or corrosive detergents to avoid damaging the painted surfaces When necessary clean the outer surfaces of the Air Leaf cooler convector with...

Page 12: ...m cleaner wash the filter with running water without using detergents or solvents and leave to dry Remount the filter on the cooler convector fig 32 ref A taking care to insert the lower flap into its...

Page 13: ...rt B C B tabs C slots For the versions with a mobile panel rest it in its position parallel to the front panel and press until it is blocked 2 17 Energy saving tips Always keep the filters clean when...

Page 14: ...s of the motor and thefree rotation of the fan The micro switch that stops the ventilation when the filter grill is opened does not close correctly Check that by closing the grill the micro switch con...

Page 15: ...15...

Page 16: ...der No 10547 09 2019 Supersedes order No New Manufactured by Carrier SCS Montluel France Manufacturer reserves the right to change any product specifications without notice Printed in the European Uni...

Reviews: