2 - INSTALLATION

2.1 - Positioning the unit

 Avoid installing the unit in proximity to:

 

-

positions subject to exposure to direct sunlight;

 

-

in proximity to sources of heat;

 

-

in damp areas or places with probable contact with water;

 

-

in places with oil fumes

 

-

places subject to high frequencies.

 Make sure that:

 

-

the wall on which the unit is to be installed is strong enough to support the weight;

 

-

the part of the wall interested does not have pipes or electric wires passing through;

 

-

the interested wall is perfectly flat;

 

-

there is an area free of obstacles which could interfere with the inlet and outlet air flow;

 

-

the installation wall is preferably an outside perimeter wall to allow the discharge of the condensation outside;

 

-

in case of ceiling installation the airflow is not directed towards persons. 

2.2 - Installation modes

The following descriptions of the various mounting phase and the relative designs refer to a version of the machine with fixtures on 

the left.

The operations for the mounting of machines with fixtures on the right are exactly the same.

Only the images are to be considered as a mirror image.
To ensure that the installation is performed correctly and that the unit will perform perfectly carefully follow the instructions indicated 

in this manual. Failure to respect the rules indicated not only can cause malfunctions of  the unit but will also invalidate the warranty 

and hence CARRIER shall not respond for any damage to persons, animals or property.

2.3 - Minimum installation distances

Figure indicates the minimum mounting distances between the wall-mounted cooler-convector and furniture present in the room.

Summary of Contents for 42SIC

Page 1: ...Original document INSTALLATION OPERATION AND M A I N T E N A N C E I N S T R U C T I O N S 42SIC 42SIR 42SIN 42SIl...

Page 2: ...CHNICAL CUSTOMER SERVICE Safety pictograms Generic danger Signals to the personnel that the operation described could cause physical injury if not performed according to the safety rules Danger of hig...

Page 3: ...n 42SIC or 42SIN 7 2 7 Mounting front grill safety support 42SIC 7 2 8 Horizontal or ceiling installation 42SIC or 42SIN 8 2 9 Hydraulic connections 8 2 10 Condensation discharge 9 2 11 Filling the sy...

Page 4: ...odically open the windows to ensure a correct change of air This instruction leaflet is an integral part of the unit and consequently must be kept carefully and must ALWAYS accompany the unit even whe...

Page 5: ...de in case of ceiling installation the airflow is not directed towards persons 2 2 Installation modes The following descriptions of the various mounting phase and the relative designs refer to a versi...

Page 6: ...efer to the individual instructions leaflets supplied and the relative manual for the mounting of the feet Using the paper template trace the position of the two fixing brackets on the wall Use a suit...

Page 7: ...lation of 42SIR low height with cabinet units in horizontal position is prohibited Carefully check the inclination of the exhaust pipe Any counterslope of the discharge line can cause water leakage B...

Page 8: ...zes 29 49 69 89 99 Pipeline diameter mm 14 14 16 18 20 The choice and sizing of the hydraulic lines must be made by an expert who must operate according to the rules of good technique and the laws in...

Page 9: ...ld interfere with the normal outflow If there is a height difference that could interfere with the outflow of the condensation a pump must be mounted in a vertical installation mount the pump under th...

Page 10: ...sition take a screwdriver and act on the highest breather of the battery for appliances installed in a horizontal position act on the highest positioned breather for the 4 pipe versions act on the hig...

Page 11: ...the risk of burns Do not use abrasive sponges or abrasive or corrosive detergents to avoid damaging the painted surfaces When necessary clean the outer surfaces of the Air Leaf cooler convector with...

Page 12: ...m cleaner wash the filter with running water without using detergents or solvents and leave to dry Remount the filter on the cooler convector fig 32 ref A taking care to insert the lower flap into its...

Page 13: ...rt B C B tabs C slots For the versions with a mobile panel rest it in its position parallel to the front panel and press until it is blocked 2 17 Energy saving tips Always keep the filters clean when...

Page 14: ...s of the motor and thefree rotation of the fan The micro switch that stops the ventilation when the filter grill is opened does not close correctly Check that by closing the grill the micro switch con...