41
19. TEST RUNNING
19.1 Note:
-
Operate test running after mounting air filters, return grill and cabinet.
-
Operate testing running after completion of connecting refrigerant piping lines,
drain line and electrical wiring
19.2 STEPS FOR COOLING TEST RUNNING
a. Move circuit breaker to ON position.
b. After system operation becomes stabilized:
-
Measure high and low pressures to check
correct refrigerant charge. (See figure & table)
-
Measure total Amps consumed by the system.
-
Measure System working voltage.
System Cooling Test Running
SYSTEM MODEL
53QG18-H
53QG24-H
AMBIENT TEMP ºC
35
40
46
35
40
46
52
HIGH PRESSURE PSI
280 315 350 260 305 345 390
LOW PRESSURE PSI
72 75 79 60 62 64 66
TOTAL AMPS
9.5
10.5 11.5 11.8 12.7 13.9 15.1
Notes:
1- Readings at 220 volt and 27 ºC return air to indoor unit
and high speed of indoor unit motor.
2- System with Standard mild ambient outdoor unit with rotary compressor.
SYSTEM MODEL
53QG18-H
53QG24-H
AMBIENT TEMP ºC
35
40
46
52
35
40
46
52
HIGH PRESSURE PSI
280 312 343 392 267 300 334 382
LOW PRESSURE PSI
73 75 77 79 65 67 69 71
TOTAL AMPS
8.6
9.3 10.1 11.1 12.2 13.1 14.0 15.3
Notes:
1- Readings at 220 volt and 27 ºC return air to indoor unit
and high speed of indoor unit motor.
2- System with High ambient outdoor unit with rotary compressor.
SYSTEM MODEL
53QG18-C
53QG24-C
AMBIENT TEMP ºC
35
40
46
52
35
40
46
52
HIGH PRESSURE PSI
260 295 330 370 260 297 335 375
LOW PRESSURE PSI
69 71 73 75 62 64 66 68
TOTAL AMPS
8.5
9.1 9.8 10.5 12.5 13.4 14.4 15.5
Notes:
1- Readings at 220 volt and 27 ºC return air to indoor unit
and high speed of indoor unit motor.
2- System with High ambient outdoor unit with rotary compressor.
(1)
1. High Pressure Measuring.
2.
Low Pressure Measuring.
(2)
Outdoor Unit
Details