GB - 8

42PHQ ...P 

Connection to the unit

Insufficient tightening torque will cause gas leaks.
Overtightening the fittings will damage the tube flaring and
cause gas leaks.

Tubing diameter

Torque

mm

(inches)

Nm

6.35

(1/4")

18

9.52

(3/8")

42

12.70

(1/2")

55

Once all connections have been completed, check for leaks by
applying soapy water to them.
Finally wrap connections with anti-condensate insulation and
tighten with tape, without exerting great pressure on the
insulation.
Repair and cover any possible cracks in the insulation.
Connection pipes and electric cables between indoor and
outdoor units must be fixed to the wall with appropriate
conduits.

Refer to the outdoor unit installation manual for tube sizing,
and limitations (slope, length, number of bends allowed,
refrigerant charge, etc.).

For refrigerant tubes use seamless, insulated refrigeration grade
tube, (Cu DHP type according to ISO1337), degreased and
deoxidized, suitable for operating pressures of at least 4200 kPa
and for burst pressure of at least 20700 kPa.
Under no circumstances must sanitary type copper pipe be used.

Flaring the end of the tubing

Remove protective caps from the copper tube ends.
Position tube end downward, cut the tube to the required length
and remove the burrs with a reamer.

Remove flare nuts from the unit connections and place them on
the tube end.
Flare the tube with the flaring tool.

Flare end must not have any burrs or imperfections.
The length of the flared walls must be uniform.

           Tubing diameter

Gas

Liquid

Model

(Suction)

(Discharge)

mm

(inches)

mm

(inches)

 007, 009

9.52

(3/8")

6.35

(1/4")

 012, 014, 018, 024

12.70

(1/2")

6.35

(1/4")

Refrigerant connections

Tube

Tube insulation

Fastening tape

  Adjustable wrench or torque wrench

  Outdoor end

  Indoor end

Lubricate the tube end and thread of the flare fitting with anti-
freeze oil.
Finger-tighten the fitting several turns, then tighten it fully with
two wrenches by applying the tightening torque indicated in the
table.

L

L

3

1

2

4

5

6

Summary of Contents for 42PHQ Series

Page 1: ...42PHQ P INSTALLATION MANUAL L L O Y D S R E G I S TER QUALIT Y A S S U R A N C E IS O 900 1...

Page 2: ...ions and weight 2 Nominal data 2 Operating limits 2 Minimum clearances 3 Material supplied 3 General information 4 Warnings avoid 5 Installation 6 7 Refrigerant connections 8 Check 9 Electrical connec...

Page 3: ...nal data Unit is not suitable for operation in laundry premises For sizing of power supply wires and delay type fuses refer to the outdoor unit installation instructions Mod 007 009 012 014 018 024 A...

Page 4: ...ld supplied items are required to complete the installation Name Specification 007 009 Connection pipe 3 8 9 52 mm Gas 1 4 6 35 mm Liquid 012 014 018 024 1 2 12 70 mm Gas 1 4 6 35 mm Liquid Wall sleev...

Page 5: ...onsisting of two units manufactured by Carrier Consult the factory or a qualified system engineer prior to connecting this unit to any other manufacturer s outdoor unit Coupling units which have diffe...

Page 6: ...ondensate dripping Flattening or kinking the refrigerant pipes or condensate pipes Excessive height difference between outdoor and indoor units see installation manual of outdoor unit Unnecessary turn...

Page 7: ...he bracket and the wall Check that the wall hanging bracket does not move This can cause noise during operation If the unit is removed from the wall hanging bracket after installing it onto the wall r...

Page 8: ...e the unit using a tool such as a screwdriver set between the middle area of the body and bottom right of the wall hanging bracket Connecting the pipe can be done more easily if the unit is inclined F...

Page 9: ...to ISO1337 degreased and deoxidized suitable for operating pressures of at least 4200 kPa and for burst pressure of at least 20700 kPa Under no circumstances must sanitary type copper pipe be used Fla...

Page 10: ...screws After installation if there is a significant gap between the unit and wall it can be adjusted by securing the body to the wall hanging bracket using 2 screws Screw holes can be only seen after...

Page 11: ...009 012 014 to the indoor unit sizes 018 024 to the outdoor unit Make electrical connections between units prior to proceeding to mains supply unit connection Before proceeding with the connection to...

Page 12: ...l Cooling only 42PHQ007P 009P 012P 014P 2 Minimum connection wire size Minimum connection wire size between for power supply mm2 indoor and outdoor unit mm2 Models GND L N N Y O W2 42PHQ007P 009P 1 5...

Page 13: ...2P 014P 2 3 Minimum connection wire size Minimum connection wire size between for power supply mm2 indoor and outdoor unit mm2 Models GND L N N Y O W2 42PHQ007P 009P 1 5 1 5 1 5 1 5 1 5 42PHQ012P 014P...

Page 14: ...default value of temperatures in Degrees Celsius C to the new value Degrees Fahrenheit o F Press button repeatedly until rc is displayed Press either the or button to change the default value of Heat...

Page 15: ...ress button to leave the configuration menu Fault code Once a failure occurs with the indoor unit in operation the green LED flashes at intervals of 0 5 seconds The fault code is deduced from the numb...

Page 16: ...Via R Sanzio 9 20058 Villasanta MI Italy Tel 039 3636 1 The manufacturer reserves the right to change any product specifications without notice December 2003 Printed in Korea 42KU5A54040...

Reviews: