7
—
UNIT
ESP
RPM
DIP2-6
DIP2-5
DIP2-4
DIP2-3
DIP2-2
DIP2-1
42CN008
12Pa
960
N/A
ON
OFF
OFF
OFF
ON
30Pa
1090
N/A
ON
OFF
OFF
ON
OFF
50Pa
1240
N/A
ON
OFF
OFF
ON
ON
42CN010
12Pa
1060
N/A
ON
OFF
ON
OFF
OFF
30Pa
1160
N/A
ON
OFF
ON
OFF
ON
50Pa
1320
N/A
ON
OFF
ON
ON
OFF
42CN012
12Pa
1060
N/A
ON
OFF
ON
ON
ON
30Pa
1180
N/A
ON
ON
OFF
OFF
OFF
50Pa
1280
N/A
ON
ON
OFF
OFF
ON
(Table 4)
Room Controller
User should operate room controller following specification.
User main power supply: 220~230VAC, 50/60Hz
User should comply with below demand,
Triple valve contact rating:
≤
1A/250VAC , interlock point contact rating:
≤
3A/250VAC
Error codes see table 5
Error Code
Reset
type
Motor start error
E1
Auto
Motor overload
E2
Auto
Control and driver communicate error
E3
Auto
Sensor on controller error
E4
Auto
Sensor on driver error
E5
Auto
(Table 5)
Operation
Driver board and room controller connection specification:
1. Connect the driver board and room controller with standard RS-485 twisted-pair
shielded wire.
2. Communication cable: 1 (Black)
→
contact B, 2 (Red)
→
contact A, 3 (Blue)
→
contact GND,
4 (Yellow)
→
c12V.
3. Make sure all the wires well insulated, without improper connection or short circuit.