2. DIP2
Setting
Default setting by factory at minimum rpm:
Single motor: 790rpm
Dual motor: 960rpm
The rpm should be reset on job site follow the table below for different unit sizes, table 3
for single motor, table 4 for dual motor. The position of DIP2 shows below: Fig 6 for single
motor, Fig 7 for dual motor.
(Fig 6) Single Motor
(Fig 7) Dual Motor
UNIT
ESP
RPM
DIP2-6
DIP2-5
DIP2-4
DIP2-3
DIP2-2
DIP2-1
42CN002
12Pa
790
ON
OFF
OFF
OFF
OFF
ON
30Pa
930
ON
OFF
OFF
OFF
ON
OFF
50Pa
1070
ON
OFF
OFF
OFF
ON
ON
42CN003
12Pa
820
ON
OFF
OFF
ON
OFF
OFF
30Pa
980
ON
OFF
OFF
ON
OFF
ON
50Pa
1140
ON
OFF
OFF
ON
ON
OFF
42CN004
12Pa
850
ON
OFF
OFF
ON
ON
ON
30Pa
990
ON
OFF
ON
OFF
OFF
OFF
50Pa
1130
ON
OFF
ON
OFF
OFF
ON
42CN005
12Pa
960
ON
OFF
ON
OFF
ON
OFF
30Pa
1090
ON
OFF
ON
OFF
ON
ON
50Pa
1220
ON
OFF
ON
ON
OFF
OFF
42CN006
12Pa
990
ON
OFF
ON
ON
OFF
ON
30Pa
1110
ON
OFF
ON
ON
ON
OFF
50Pa
1250
ON
OFF
ON
ON
ON
ON
(Table 3)