Electrical connection :
All electrical connections must be performed by qualified, ATEX-approved personnel.
Under no circumstances may the manufacturer be held liable for the performance of these connections, which are outside the scope
of its services.
THE UNIT MUST BE CONNECTED TO EARTH.
Product liability can not be held liable for accidents as a connection to incorrect or nonexistent land.
Before connecting the unit to the network, ensure that the voltage matches that indicated on
the motor's data plate
A bag containing an ATEX-certified cable gland is supplied with the unit. Please install this
cable gland in accordance with the manual contained in this bag.
The use of any other cable gland will render the 42AM ATEX certification null and void, as will
its incorrect installation.
Y-connexion
Δ-connexion
THREE-PHASE voltage
230/400V – 50Hz
GAS ONLY ENVIRONMENT Z1 & Z2
IIB T4
IIB T5
IIC T4
IIC T6
Use
HEATING
Motor designation
F71-2GBST/C6
F71-2GBTV/C6
F71-2GCTV/C6
F80-2GCTV/A6
Rated speed (rpm)
925
925
925
890
Rated current (A) (400V))
0,9
0,9
0,9
0,9
Id/In
2,7
2,3
2,3
2,5
Abs. P (W) (400V)
180
180
180
250
Use
COOLING
or REVERSIBLE
Size 350 and 400
Motor designation
F71-2GBST/C6
F71-2GBTV/C6
F71-2GCTV/C6
F80-2GCTV/A6
Rated speed (rpm)
925
925
925
890
Rated current (A) (400V)
0,9
0,9
0,9
0,9
Id/In
2,7
2,3
2,3
2,5
Abs. P (W) (400V)
180
180
180
250
Size 450 and 500
Motor designation
F71-2GBTV/C8
F80-2GBTV/A8
F80-2GCTV/A8
F80-2GCTV/A8
Rated speed (rpm)
660
705
705
705
Rated current (A) (400V)
1,05
0,95
0,95
0,95
Id/In
2,2
3
3
3
Abs. P (W) (400V)
180
180
180
180
Shared
IP
55
Operating T°C
-20°C / +40°C
Class
F
Heat Protection Sensor
No Heat Protection Sensor (neither PTC nor PTO (thermal overload protection) – See Note)
Note :
No heat protection sensor originally fitted to the motor as not variator-driven.
It is recommended to connect the motor to a thermal-magnetic circuit breaker. Device to be supplied by the installer.
The customer is informed of this via a message on the ATEX sheet which they complete and sign ahead of the offer. The
message reads as follows:
"For this equipment, the motor must not be fitted with heat protection and MUST be connected to a correctly sized thermal-
magnetic circuit breaker (not supplied by the manufacturer)."
4 - INSTALLATION & CONNECTION
22