Installation and Operating Instructions

Part Number 40WA900024

CONTENTS

Page

SAFETY CONSIDERATIONS

. . . . . . . . . . . . . . . . . . . . . . 1

GENERAL

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

INSTALLATION

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  1-3

Controller Installation

. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

System Wiring

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

OPERATION

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  4-7

Red Status Indicator

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Backlight

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Power On or Reset Signal

 . . . . . . . . . . . . . . . . . . . . . . . . 5

Indoor Unit Address Display

 . . . . . . . . . . . . . . . . . . . . . 5

Individual Unit Operation

. . . . . . . . . . . . . . . . . . . . . . . . . 6

Global Operation

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Control Summary

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Filter Cleaning

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

TROUBLESHOOTING

 . . . . . . . . . . . . . . . . . . . . . . . . . . .7,8

SAFETY CONSIDERATIONS

Read and follow manufacturer instructions carefully. Fol-

low all local electrical codes during installation. All wiring
must conform to local and national electrical codes. Improper
wiring or installation may damage thermostat.

Understand the signal words — DANGER, WARNING,

and CAUTION. DANGER identifies the most serious hazards
which will result in severe personal injury or death.
WARNING signifies hazards that could result in personal inju-
ry or death. CAUTION is used to identify unsafe practices,
which would result in minor personal injury or product and
property damage.

Recognize safety information. This is the safety-alert

symbol (

). When this symbol is displayed on the unit and in

instructions or manuals, be alert to the potential for personal
injury. Installing, starting up, and servicing equipment can be
hazardous due to system pressure, electrical components, and
equipment location.

GENERAL

The single-phase VRF (variable refrigerant flow) central

controller is a wall-mounted, low-voltage supply (24 vac) ther-
mostat that can control 64 indoor units. The controller does not
require batteries.

The central controller accessory is available for use with the

single-phase VRF (variable refrigerant flow) indoor units listed
in Table 1.

Table 1 —  Central Controller Accessory Usage 

INSTALLATION

Controller Installation — 

The controller should be

mounted:

• approximately 48 in. from the floor

• on a section of wall without water or drainage pipes

• typically in a mechanical room, facility manager’s office,

or central control room

To install the controller, perform the following procedures:

1.

Turn off all power to the system (outdoor and all indoor
units.

2.

Confirm that 24 vac power supply is available to power
the controller at this location.

3.

Be sure that total signal wire length from the central con-
trol does not exceed 3,937 feet.

4.

Shielded 3-core control cable is required with no interme-
diate joints. If a joint is necessary, make the connection
using a terminal block in an acceptable enclosure. All
three conductors and the shield must be connected at the
terminal block.

UNIT

SIZES

40WAC Compact Cassette

007,009,012,015

40WAF 4-Way Cassette

009,012,015,018,024,030,048

40WAW High Wall

007,009,012,015,018

40WAD Ducted

007,009,012,015,018,024

40WAH High Static

024,030,036,048

40WAU Under Ceiling

012,015,018,024,030,036,048

40WAV Vertical

018,024,030,036,048

WARNING

Electrical shock can cause personal injury and death.
Before installing thermostat, shut off all power to this
equipment during installation. There may be more than one
power disconnect. Tag all disconnect locations to alert oth-
ers not to restore power until work is completed.

CAUTION

Failure to follow this caution may result in equipment dam-
age or improper operation.
Improper wiring or installation may damage the thermo-
stat. Check to make sure wiring is correct at the controller
and unit ends before proceeding with installation or turning
on unit.

40WAC,WAF,WAW,WAD,

WAH,WAU,WAV

Single-Phase VRF (Variable Refrigerant Flow) System

Central Controller Accessory

Summary of Contents for 40WA900024

Page 1: ...entral controller accessory is available for use with the single phase VRF variable refrigerant flow indoor units listed in Table 1 Table 1 Central Controller Accessory Usage INSTALLATION Controller I...

Page 2: ...e slots provided on the top of the controller to open the back mounting plate See Fig 2 8 Attach the back mounting plate directly over the opening in the wall using 4 screws and route the control cabl...

Page 3: ...connections See Fig 6 for complete system central controller wiring diagram X X Y Y E E CENTRAL CONTROLLER OUTDOOR UNIT a40 1875 Fig 5 Controller Connections P Q E X Y E 3 4 3 4 3 4 3 4 3 4 5 MATCH R...

Page 4: ...1 6 INDOOR UNIT ADDRESS DISPLAY GRID NOT USED SWING ON NOT USED ERROR PROTECTION CODE CENTRAL CONTROLLER OPERATION STATUS NOT USED OPERATION MODE SETTING COOLING MODE LOCK HEATING MODE LOCK REMOTE CO...

Page 5: ...ontal coordinates are 00 to 15 The sum of the vertical and horizontal coordinates is the address of the indoor unit The unit s location on the grid has no relation to the unit s physical location For...

Page 6: ...e delayed operation start time for the selected indoor units Press the INC button to se lect the start hour from 0 to 24 hours Each button press incre ments the setting by 1 2 hour for the first 10 ho...

Page 7: ...the same time The controller displays 88 the display flashes 5 Use the INC and DEC buttons to set the appropriate func tion as shown below 6 Press OK 7 Use the INC and DEC buttons to select the code...

Page 8: ...tion at port on PC board Tighten the connection at port on PC board Sensor is short circuited Using multi meter measure resistance of the sensor If the resistance is 100 ohms change the sensor PC boar...

Reviews: