Installation
Static Pressure Range
unit: Pa
4. Drainpipes
40VD007-030H-7S-QEE
40VD038-054H-7S-QEE
Static Pressure Range
0-200
• Proper Piping
• Improper Piping
hanging bolt
Heat insultor
gradient of 1/100 or over
air outlet port
avoid lobing
avoid curving
Do not put pipe
into water
1.5m ~ 2m
280mm
280mm
250mm
250mm
176mm
184.5mm
134.5mm
105mm
77mm
drain pipe
gas pipe
liquid pipe
512mm
473mm
414mm
468mm
468mm
405mm
467mm
738mm
30mm
30mm
(a) Keep a gradient (1/50-1/100)of the drain pipes and avoid lobing or curving.
(b) When connecting the drainpipe to the equipment, don’t apply too much force on one side of the
equipment. Meanwhile, the piping should be positioned as close to the equipment as possible.
(c) For the drainpipe, a general purpose hard PVC tube can be purchased at local shops. During
the connection, insert the end of PVC tube into the wash port and fasten it with drainage hose
and thread clip. Binding agents or glues shouldn’t be used to connect the wash port and
drainage hose.