background image

7

Step  5  —  Complete  Electrical  Connections

Installation of wiring must conform with local building codes,

or in the absence of local codes, with National Electric Code

ANSI/NFPA  70,  current  editions.  Units  must  be  electrically

grounded  in  conformance  with  the  code.  In  Canada,  wiring

must comply with CSA C22.1, Electrical Code.

This  equipment  in  its  standard  form  is  designed  for  an

electrical supply of 208/230-1-60. Any damage to or failure of

units caused by incorrect wiring or voltage is not covered by

warranty.

Electric wiring must be sized to carry the full load amp draw of

the motor, starter, and any other controls that are used with the

unit. See Table 4 for electrical data.

Table 4 — 40VMV Electrical Data

After the pipe work is complete, the electrical supply can be

connected by routing the cable through the appropriate casing

holes  or  knockouts  and  connecting  the  supply  and  ground

cables to the unit’s power terminal.

Be sure the power wiring and control wiring do not cross, as

this might cause disturbance on the controls side. See Fig. 5 for

wiring diagram.

NOTE

:

 

The indoor unit requires its own power supply. Indoor

units are not powered from outdoor units.

Step  6  —  Position  and  Connect  Controller

NOTE:

 Controllers are ordered separately.

Wired  controllers  should  be  installed  in  a  position  that

maintains good temperature control:

• Position  the thermostat approximately 48  inches above

floor level.

• Do  not  position  thermostat  where  it  can  be  directly

affected by the unit’s discharge airstream.

• Avoid external walls and drafts from window and doors.

• Avoid  positioning  near  shelves  and  curtains  as  these

restrict air movement.

• Avoid  heat  sources  such  as  direct  sunlight,  heaters,

dimmer switches, and other electrical devices.

See Fig. 6 and Fig. 7.

CONTROL WIRING

1. The  communication  wire  should  be  2-core  stranded

shielded cable.

2. For  indoor  and  outdoor  unit  communication,  use  P,  Q

terminals. Shielded core should be used for ground.

3. Wiring should be done according to wiring diagram.

4. Communication wire must not form a closed loop.

5. Use separate conduit for power and control wiring.

WARNING

Electrical  shock  can  cause  personal  injury  and  death.

Disconnect  power  supply  before  making  wiring

connections.  There  may  be  more  than  one  disconnect

switch. Tag all disconnect locations to alert others not to

restore power until work is completed. 

WARNING

All  units  must  be  wired  strictly  in  accordance  with  the

wiring  diagram  furnished  with  the  unit.  Any  wiring

different from the wiring diagram could result in personal

injury and property damage.

CAUTION

Any original factory wiring that requires replacement must

be  replaced  with  wiring  material  having  a  temperature

rating of at least 221°F.

Ensure supply voltage to the unit, as indicated on the serial

plate, is not more than 10% over the rated voltage or 10%

under the rated voltage.

Failure  to  follow  these  recommendations  may  result  in

equipment damage.

40VMV UNIT SIZE

POWER SUPPLY

MCA

MOPD

012A

1.5

15

018A

3.8

15

024A

3.8

15

030A

3.8

15

036A

5.3

15

048A

5.3

15

054A

7.2

15

LEGEND

MCA

Minimum Circuit Amps

MOPD

Maximum Overcurrent

Protective Device

Summary of Contents for 40VMV0012A

Page 1: ...ER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies hazards that could result in personal injury or death CAUTION is used to identify unsafe p...

Page 2: ...h Unit CAUTION DO NOT re use compressor oil or any oil that has been exposed to the atmosphere Dispose of oil per local codes and regulations DO NOT leave refrigerant system open to air any longer tha...

Page 3: ...700 840 1120 1260 EXTERNAL STATIC PRESSURE in wg 0 8 INDOOR UNIT NOISE LEVEL dBA High 37 6 41 6 46 2 52 2 46 9 53 0 57 1 Medium 34 5 37 1 42 3 48 4 44 1 48 5 52 6 Low 34 5 34 4 37 9 44 4 39 3 43 8 47...

Page 4: ...ig 2 40VMV012A 054A Dimensions 40VMV UNIT SIZE A B C D 012A 030A 46 1 2 19 5 8 18 21 5 8 036A 054A 54 1 2 22 19 1 2 24 RIGHT SIDE A FRONT B C D DRAIN PIPE LEFT SIDE AIR RETURN REFRIGERANT SIDE PIPE LI...

Page 5: ...es in their parts of the installation Units must be installed in compliance with all applicable local code requirements IDENTIFYING AND PREPARING UNITS Be sure power requirements match available power...

Page 6: ...een the bottom of the trap and outlet should also be three inches See Fig 4 Fig 4 Condensate Drain Trap Auxiliary drain should be connected and run to a location where it is easily visible when it bec...

Page 7: ...rectly affected by the unit s discharge airstream Avoid external walls and drafts from window and doors Avoid positioning near shelves and curtains as these restrict air movement Avoid heat sources su...

Page 8: ...CN3 CN18 CN31 CN54 CN4 CN15 CN19 CN8 CN21 CN12 CN26 CN14 CN25 CN52 CN17 CN9 To wired controller comm bus XP8 XP9 MDC unit comm bus To outdoor indoor P Q XT2 HA HB HA HB BLUE WHITE L1 L2 POWER IN P Q E...

Page 9: ...cting Communication Wire to Outdoor Unit Communication Terminal CAUTION Failure to follow these procedures may result in personal injury or damage to equipment NEVER CONNECT the main power source to t...

Page 10: ...o outdoor To Sub MDC To outdoor Indoor unit 1 L1 L2 L3 L3 L3 L3 L4 L5 L6 L7 L8 L9 L10 1 1 L Indoor unit 2 Indoor unit 3 Indoor unit 4 Indoor unit 5 Indoor unit 6 HA HB HA HB HA HB HA HB HA HB HA HB To...

Page 11: ...it 5 Indoor unit 6 P Q HA HB HA HB HA HB HA HB HA HB HA HB Network Resistor Maximum wiring length L1 L3 3937 ft 18 AWG 2 Core Stranded Shield L5 3937 ft 18 AWG 2 Core Stranded Shield L6 L7 L8 L9 820 f...

Page 12: ...ble cleaning agent Clean the grille and panel Every 12 Months Follow 6 month maintenance schedule In addition Be sure all electrical connections are secure Check condensate pump operation Check the he...

Page 13: ...setting interface Programmable Controller When setting an address connect only one wired controller to an indoor unit 1 Access parameter settings as shown in Fig 18 Fig 18 Programmable Controller IDU...

Page 14: ...DE STATUS NO ERROR Setting Temperature Starting Shutdown Standby Timing ON Timing OFF Setting Temperature System Defrost ON Setting Temperature System Defrost OFF ERROR dd Heating Cooling Mode Conflic...

Page 15: ...e PC board E7 EEPROM Error Data Storage Chip or PC board fault Replace PC board E9 Communication Error Between Indoor Unit Controller Signal wires are short circuited or disconnected Check or reconnec...

Page 16: ...de POSITION 2 OFF Normal Mode Default ON Factory Self Checking Mode POSITION 3 NOT USED POSITION 4 INDOOR UNIT IDENTIFICATION OFF STANDARD INDOOR UNIT Default MODE PRIORITY INDOOR UNIT HP ONLY ON IDU...

Page 17: ...ring replacement parts or contacting the factory about the unit This information can be found on the serial plates attached to the unit as shown in Figs 21 27 Fig 21 40VMV012 3 Unit Serial Plate Fig 2...

Page 18: ...18 Fig 25 40VMV036 3 Unit Serial Plate Fig 27 40VMV054 3 Unit Serial Plate Fig 26 40VMV048 3 Unit Serial Plate...

Page 19: ...s Fig D 40VMV030A Fan Curves 0 00 0 20 0 40 0 60 0 80 1 00 EXTERNAL STATIC PRESSURE in wg H speed 500 AIRFLOW cfm M speed L speed 700 300 600 400 Upper Limit of ESP 0 00 0 20 0 40 0 60 0 80 1 00 EXTER...

Page 20: ...VMV048A Fan Curves Fig G 40VMV054A Fan Curves 0 00 0 20 0 40 0 60 0 80 1 00 700 800 900 1000 1100 1200 1300 1400 EXTERNAL STATIC PRESSURE in wg H speed M speed L speed Upper Limit of ESP AIRFLOW cfm 0...

Reviews: