background image

8

• Use a torque wrench for flare nuts. Refer to Table 5 for

flare nut torque recommendations.

Table 5 — Flare Nut Torque Recommendations

For unit size 012 to 048 the refrigerant pipe can be routed

thorough bottom/rear of the unit as shown in Fig. 13. Table 6
shows the length of pipe that should be coming out of the unit.

For unit size 012 to 024 the refrigerant pipe can be routed

through the right side of the unit as shown in Fig. 14. Pipe
lengths are shown in Table 6.

Table 6 — Pipe Lengths (Refer to Fig. 13 and 14)

Step 5 — Complete Electrical Connections —

Installation of wiring must conform with local building codes
and with National Electric Code ANSI/NFPA 70, current edi-
tions. Units must be electrically grounded in conformance with

the code. In Canada, wiring must comply with CSA C22.1,
Electrical Code.

This equipment in its standard form is designed for an elec-

trical supply of 208/230-1-60. Any damage to or failure of
units caused by incorrect wiring or voltage is not covered by
warranty.

Electric wiring must be sized to carry the full load amp

draw of the motor, starter, and any other controls that are used
with the unit. See Table 7 for electrical data.

Table 7 — 40VMU Electrical Data

                   LEGEND

After the pipe work is complete, the electrical supply can be

connected by routing the cable through the appropriate casing
holes or knockouts and connecting the supply and ground ca-
bles to the unit’s power terminal.

Be sure the power wiring and control wiring do not cross, as

this might cause disturbance on the controls side. See Fig. 15
for wiring diagram.

OUTSIDE DIAMETER (in.)

RECOMMENDED TORQUE 

(ft-lb)

1

/

4

15

3

/

8

26

1

/

2

41

5

/

8

48

40VMU 

SIZE

DIMENSIONS (in.)

a

b

c

d

012

1

/

4

 2 

1

/

4

 

4

4

015

1

/

4

2

4

4

018,024

3

/

4

4

4

4

030

5

1

/

4

 

036,048

3

/

4

3

/

4

Gas side adapting pipe
(installation on-site)

Liquid side adapting pipe

(installation on-site)

a

b

Fig. 13 — Routing the Refrigerant Pipe through 

the Bottom

Gas side adapting pipe 

(only 012-024)

(installation on-site)

Liquid side adapting pipe

(only 012-024)

(installation on-site)

protect the plastic side

enclosure when brazing

d

c

Fig. 14 — Routing the Refrigerant Pipe through 

the Side

WARNING

Electrical shock can cause personal injury and death. Dis-
connect power supply before making wiring connections.
There may be more than one disconnect switch. Tag all dis-
connect locations to alert others not to restore power until
work is completed. 

WARNING

All units must be wired strictly in accordance with the wir-
ing diagram furnished with the unit. Any wiring different
from the wiring diagram could result in personal injury and
property damage.

CAUTION

Any original factory wiring that requires replacement must
be replaced with wiring material having a temperature rat-
ing of at least 105 C.
Ensure supply voltage to the unit, as indicated on the serial
plate, is not more than 10% over the rated voltage or 10%
under the rated voltage.
Failure to follow these recommendations may result in
equipment damage.

UNIT

POWER SUPPLY

MCA

MOPD

40VMU012

0.44

15

40VMU015

0.73

15

40VMU018

0.87

15

40VMU024

1.20

15

40VMU030

1.40

15

40VMU036

1.80

15

40VMU048

2.80

15

MCA

Minimum Circuit Amps

MOPD —

Maximum Overcurrent
Protective Device

Summary of Contents for 40VMU012 Series

Page 1: ...he Canadian Electrical Code CSA Ca nadian Standards Association C22 1 Understand the signal words DANGER WARNING and CAUTION DANGER identifies the most serious hazards which will result in severe pers...

Page 2: ...es may result in damage to equipment For information about replacement oil type and viscosity see the Installa tion Start Up and Service Instructions for the 38VMAH and 38VMAR outdoor units UNIT 40VMU...

Page 3: ...d sub MDC Connecting wire 1 Occupancy sensor connecting wire Gas side copper pipe For 012 024 only 1 For routing refrigerant pipes to the side of the unit Liquid side copper pipe For 012 024 only 1 Ga...

Page 4: ...A B C D Fig 2 40VMU012 030 Dimensions 40VMU UNIT SIZE DIMENSION in A B C D 012 024 39 26 8 19 7 8 030 50 1 2 26 8 31 1 4 66 27 10 42 a40 1857 1 8 Fig 3 40VMU036 048 Dimensions NOTE All dimensions show...

Page 5: ...INSTALLATION To save time and to reduce the possibility of costly errors set up a complete sample installation in a typical room at jobsite Check all critical dimensions such as pipe wire and duct co...

Page 6: ...otrude more than 1 in below the mounting hole on the hanging bracket as shown in Fig 7 3 Remove the side board and grille from the unit as shown in Fig 8 does not apply to unit size 048 4 Slide the un...

Page 7: ...indoor unit Refrigerant piping connection between indoor and out door units should be performed once the units are secured at their respective installation locations The refrigeration piping starts a...

Page 8: ...might cause disturbance on the controls side See Fig 15 for wiring diagram OUTSIDE DIAMETER in RECOMMENDED TORQUE ft lb 1 4 15 3 8 26 1 2 41 5 8 48 40VMU SIZE DIMENSIONS in a b c d 012 2 1 4 2 1 4 4 4...

Page 9: ...Board 1 CN1 CN3 CN18 CN27 CN24 CN11 CN5 CN52 CN54 CN12 CN15 CN9 CN8 CN22 vertical CN2 3 Level CN2 1 vertical EARTH POWER IN U E L B R E D L1 L2 G Y GM GM GM T2B UE L B T2A WHITE T1 T0 D E R Display b...

Page 10: ...ion wiring of the heat pump and heat recovery sys tems Fig 16 Communication Wire Connection To outdoor indoor MDC units comm bus To wired controller comm bus XT2 3 4 3 4 3 4 LEGEND ACB Auxiliary Contr...

Page 11: ...HB Touch screen wired controller NOTE Power from IDU Maximum wiring length L1 L3 3937 ft 16 AWG 2 Core Stranded Shield L5 3937 ft 16 AWG 2 Core Stranded Shield L6 L7 L8 L9 820 ft 16 20 AWG 2 Core Stra...

Page 12: ...1 L Indoor unit 1 Indoor unit 2 HA HB HA HB HA HB HA HB HA HB HA HB Indoor unit 3 Indoor unit 4 Indoor unit 5 Indoor unit 6 Maximum wire length L1 L2 3937 ft 16 AWG 2 Core Stranded Shield L3 3937 ft 1...

Page 13: ...y with suitable cleaning agent Clean the grille and panel if applicable EVERY 12 MONTHS Follow 6 month maintenance schedule In addition Be sure all electrical connections are secure Check condensate p...

Page 14: ...indoor unit the display shows FE 00 see Fig 26 Otherwise the display shows the current address of the indoor unit Click TEMP UP or TEMP DOWN to change 00 to the desired address as shown in Fig 27 The...

Page 15: ...3 Press TEMP UP or TEMP DOWN to choose the ad dress see Fig 29 Press MENU OK to send this address to the IDU 4 Press BACK twice or wait 30 sec to automatically exit the parameter settings menu Fig 28...

Page 16: ...ror Between Indoor and Outdoor Unit E2 Check Indoor Ambient Temperature Sensor T1 T0 E4 Check Evaporator Temperature Sensor T2B E5 Check Evaporator Outlet Temperature Sensor T2A E6 Check DC Fan Motor...

Page 17: ...r Data Storage Chip or PC board fault Replace PC board E9 Communication Error Between Indoor Unit and Controller Signal wires are short circuited or discon nected Check or reconnect signal wires Signa...

Page 18: ...display board The de fault display is Fahrenheit To change from Fahrenheit to Cel sius press the button and hold for 5 seconds ON OFF 1 2 3 4 a40 1923 POSITION 1 START UP OFF Auto Addressing Mode Def...

Page 19: ......

Page 20: ...right to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53400035 01 Printed in U S A Form 40VMU 1SI Pg 20 8 16 Replaces New...

Reviews: