background image

7

INSTALLING MOUNTING BRACKET AND MOUNT-ING

UNIT (FLOOR STANDING) — The mounting bracket (see

Fig.  10)  can  be  anchored  to  the  wall  with  screws.  For  unit

weight and mounting dimensions, see Table 4.

Fig. 10 —Mounting Bracket Locations

Table 4 —Unit Weight and Mounting Dimensions 

(Floor Standing)

The unit can now  be lifted  and mounted onto the mounting

brackets.

1. Anchor the brackets at the specified location on the wall

using the mounting screws. See Fig. 11.

2. Once the brackets are secured, lift the unit and mount it

on the brackets. Be sure the brackets are engaged in the

correct mounting locations on the back of the unit.

Fig. 11 —Mounting Brackets to Wall

For models 036 and 048 there is an outside air opening on the

back of the unit. See Fig. 12 below.

Fig. 12 —Outside Air Opening Cutout Location

Step 4 — Connect Piping

CONDENSATE PIPING  — The unit is supplied with a 5/8-

in.  OD  drain  connection  to  connect  copper  or  plastic  drain

piping.  When  installing  condensate  piping,  follow  these

recommendations:.
• Condensate  piping  should  slope  downward  in  the

direction of condensate flow, with a minimum gradient

of 1 in. per 100 inches.

• When  multiple  units  are  connected  to  a  common

condensate drain, ensure that the drain is large enough to

accommodate the volume of condensate from all units. It

is  also  recommended  to  have  an  air  vent  in  the

condensate piping to prevent any air locks.

• Condensate piping must not be installed where it may be

exposed to freezing temperatures.

REFRIGERANT PIPING

When connecting refrigerant piping from an indoor unit to an

outdoor unit, follow these guidelines:
• Check  maximum  height  drop  and  length  of  refrigerant

piping  between  the  indoor  and  outdoor  units.  If  the

difference  between  them  is  more  than  33  ft,  consider

mounting the outdoor unit above indoor unit.

• Refrigerant  piping  connection  between  indoor  and

outdoor  units  should  be  performed  once  the  units  are

secured at their respective installation locations.

• The refrigeration piping starts at the indoor unit and ends

at the outdoor unit.

• The number of bends in the refrigeration piping must be

fewer than 15.

• The refrigerant piping should be dry and free of dust and

other impurities.

• The  bending  angle  of  the  refrigerant  pipe  should  not

exceed 90

°

 and the bending radius should be as large as

possible to prevent any breakage in piping.

• Use proper cutting and flaring tools to avoid leakage.
• Before  insulating  the  suction  and  liquid  refrigeration

pipes,  perform  pressure  and  leak  tests.  For  details,  see

the  outdoor  unit  installation  manual.  Insulating  both

suction and liquid refrigerant pipes is required.

• Vacuuming and charging of the system should be carried

out as described in the outdoor unit installation manual.

40VMU UNIT

WEIGHT (lb)

DIMENSION (in.)

A

B

012

57

17-

7

/

8

19-

7

/

8

015-024

62

17-

7

/

8

19-

7

/

8

030

76

31-

1

/

4

19-

7

/

8

036,048

106

42-

1

/

8

17-

3

/

4

CAUTION

To avoid site damage, be sure there are no water, plumbing,

or electrical lines running through the wall at the mounting

location.

IMPORTANT: Be sure to anchor the brackets on wall

studs.

A

B

BRACKET

A40 1861

WASHER

 

BRA

 

CKET

TAPPING
SCREW

< 0.25 IN.

CAUTION

Cut along the marked dotted line only. Failure to do so may

result in damage to the equipment.

CAUTION

When connecting from an indoor unit to an outdoor unit,

the  isolation  valve  at  the  outdoor  unit  should  be  in  the

closed position throughout the refrigerant piping process.

Failure to follow this procedure may result in equipment

damage.

please cut along the marked 

For outside air opening, 

dotted line.

Summary of Contents for 40VMU

Page 1: ...ll result in severe personal injury or death WARNING signifies hazards that could result in personal injury or death CAUTION is used to identify unsafe practices which would result in minor personal i...

Page 2: ...ures may result in damage to equipment For information about replacement oil type and viscosity see the Installation Start Up and Service Instructions for the 38VMAH and 38VMAR outdoor units UNIT 40VM...

Page 3: ...Connect the drain hose to condensate connec tion Flexible conduit and connectors 1 Routing power lines Hanging bracket 4 Used for hanging the unit Installation guide for metallic flexible pipe 1 Mount...

Page 4: ...ns shown in inches Fig 2 40VMU012 030 Dimensions NOTE All dimensions shown in inches Fig 3 40VMU036 048 Dimensions 40VMU UNIT SIZE DIMENSION in A B C D 012 024 39 26 8 19 7 8 30 50 1 2 26 8 31 1 4 A B...

Page 5: ...SITE FOR UNIT INSTALLATION To save time and to reduce the possibility of costly errors set up a complete sample installation in a typical room at the job site Check all critical dimensions such as pip...

Page 6: ...h locknuts and washers on both sides Ensure the threaded rod does not protrude more than 1 in below the mounting hole on the hanging bracket as shown in Fig 7 Fig 7 Mounting the Hanging Bracket 3 Remo...

Page 7: ...the indoor and outdoor units If the difference between them is more than 33 ft consider mounting the outdoor unit above indoor unit Refrigerant piping connection between indoor and outdoor units shou...

Page 8: ...d cables to the unit s power terminal Be sure the power wiring and control wiring do not cross This might cause disturbance on the controls side See Fig 15 for wiring diagrams OUTSIDE DIAMETER IN RECO...

Page 9: ...iliary Heat CS Condensate Switch Optional CTON Output for Cooling Operation EEV Electronic Expansion Valve FAN Output for Fan Operation FM Indoor Fan Motor HTON Output for Heating Operation PUMP Pump...

Page 10: ...r to fix the communication wire on the outdoor unit communication terminal as shown in Fig 19 Fig 19 Connecting Communication Wire to Outdoor Unit Communication Terminal If communication wires are use...

Page 11: ...or To No 1 indoor To No 2 indoor To Sub MDC Main MDC unit To outdoor To outdoor L1 L2 L3 L3 L3 L3 L4 L4 L5 L6 L7 L8 L9 L10 L11 Indoor unit 1 HA HB Indoor unit 2 Indoor unit 3 Indoor unit 4 Indoor unit...

Page 12: ...L5 L6 L7 L8 L9 L10 L11 L3 L3 L3 L3 Indoor unit 1 Indoor unit 2 Indoor unit 4 Indoor unit 5 Indoor unit 6 Indoor unit 3 P Q HA HB HA HB HA HB HA HB HA HB HA HB P Q Network Resistor wired controller To...

Page 13: ...hedule In addition Clean condensate tray with suitable cleaning agent Clean the grille and panel if applicable EVERY 12 MONTHS Follow the 6 month maintenance schedule In addition Be sure all electrica...

Page 14: ...confirm and exit the setting interface Fig 27 Non Programmable Controller Setting IDU Address Programmable Controller When setting an address connect only one wired controller to an indoor unit 1 Pre...

Page 15: ...mmunication Error Between Indoor and Outdoor Unit E2 Check Indoor Ambient Temperature Sensor T1 T0 E4 Check Evaporator Temperature Sensor T2B E5 Check Evaporator Outlet Temperature Sensor T2A E6 Check...

Page 16: ...E9 Communication Error Between Indoor Unit and Controller Signal wires are short circuited or disconnected Check or reconnect signal wires Signal wires close to electromagnetic source Distance signal...

Page 17: ...o Addressing Mode Default ON Factory Test Mode POSITION 2 MODE OFF Normal Mode default ON Factory Self Checking Mode POSITION 3 NOT USED POSITION 4 INDOOR UNIT IDENTIFICATION OFF Standard Indoor Unit...

Page 18: ...ht to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 20 40VMU001 02 Printed in U S A Form 40VMU 2SI Pg 18 02 20 Replaces 40VMU...

Reviews: