CONDENSATE DRAIN CONNECTION

The unit is supplied with a drain connection to connect the drain

piping. When installing condensate piping, follow these

recommendations:

S

Condensate piping should slope downward in the direction
of the condensate flow, with a minimum gradient of 1 in.

per 100 inches.

S

When multiple units are connected to a common
condensate drain, ensure the drain is large enough to

accommodate the volume of condensate from all units. It

is also recommended to place an air vent in the condensate

piping to prevent any air locks.

S

Condensate piping must not be installed where it may be
exposed to freezing temperatures.

1.5

m~

2

m

Insulating

material

Downward declivity

lower than 

1/1

00 

Bend

S shape 

VP

3

0

Downward declivity 

lower than 

1/1

00

Put as deep as possible

(about 

1

0cm)

A150714

Fig. 16

 - 

Condensate Flow

ELECTRICAL DATA

Table 5—Electrical Data

INDOOR FAN

MAX FUSE CB AMP

UNIT SIZE

V-Ph-Hz

FLA

HP

9K

2

0

8/23

0

-1-6

0

0

.

0

9

0

.

0

73

Refer

 

to

 

outdoor

 

unit

 

installation

 

instructions

 –

Indoor

 

unit

 

powered

 

by

 

the

 

outdoor

 

unit

12K

1

0

.

0

73

LEGEND

FLA - Full Load Amps

CONNECTION DIAGRAMS

Fig. 17

 - 

Connection Diagram

Notes

:

1. Do not use thermostat wire for any connection between indoor and outdoor units.
2. All connections between indoor and outdoor units must be as shown. 

The connections are sensitive to polarity and will result in a fault code.

A150635

Fig. 18

 - 

Control and Power Wiring on Indoor Unit

NOTE

:  

For applications where gravity cannot be used for drainage, a condensate pump accessory is available. Consult the

condensate pump installation instructions for more information.

Summary of Contents for 40MBF Series

Page 1: ...he installation TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS 2 PARTS LIST 3 SYSTEM REQUIREMENTS 4 DIMENSIONS 5 CLEARANCES 5 INSTALLATION LOCATION REQUIREMENTS 6 INDOOR UNIT INSTALLATION 6 ELECTRICAL D...

Page 2: ...ds which will result in severe personal injury or death WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor...

Page 3: ...5 A150654 Fig 1 Parts List Note If the outdoor unit is higher than the indoor unit prevent rain from flowing into the indoor unit along the connection pipe by creating a downward arc in the connectio...

Page 4: ...d Communication Wiring The main power is supplied to the outdoor unit The field supplied 14 3 power communication wiring from the outdoor unit to the indoor unit consists of four 4 wires and provides...

Page 5: ...IMENSIONS Fig 2 Indoor Unit Table 2 Dimensions Indoor UNIT SIZE 9 12 Height in mm 8 27 210 8 27 210 Width in mm 27 56 700 27 56 700 Depth in mm 23 62 600 23 62 600 Weight Net Lb kg 32 41 14 7 32 41 14...

Page 6: ...6 CLEARANCES Fig 3 Indoor Unit Clearance...

Page 7: ...hooks are secured lift the unit and mount it on the hooks Be sure the hooks are on the correct mounting locations on the back of the unit see Fig 5 Washer Tapping screw Hook 6mm A150705 Fig 5 Hang the...

Page 8: ...ar A150710 Fig 11 Clamp Handle 5 Apply a small amount of refrigerant oil to the flare connection on the tubing 6 Align the center of the pipes Indoor unit tubing Flare nut Pipings A150711 Fig 12 Align...

Page 9: ...than 1 100 Bend S shape VP30 Downward declivity lower than 1 100 Put as deep as possible about 10cm A150714 Fig 16 Condensate Flow ELECTRICAL DATA Table 5 Electrical Data INDOOR FAN MAX FUSE CB AMP UN...

Page 10: ...ection feature prevents air conditioner from being activated for approximately 3 to 4 minutes 2 Press MODE and select COOLING HEATING FAN mode to check if all functions work correctly 3 To run the tes...

Page 11: ...open circuit or short circuit 7 times X EC Refrigerant leakage detection 8 times X EE Water level alarm malfunction 1 time O F0 Current overload protection 2 times O F1 Open circuit or short circuit...

Page 12: ...ration S 7310 W Morris St S Indianapolis IN 46231 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 40MBF 02SI Replaces...

Reviews: