background image

2

SAFETY CONSIDERATIONS

Installing, starting up, and servicing air

conditioning equipment

can be hazardous due to system pressures, electrical components,

and equipment location (roofs, elevated structures, etc.).
Only trained, qualified installers and service mechanics should

install, start

up, and service this equipment.

Untrained personnel can perform basic maintenance functions such

as cleaning coils. All other operations should be performed by

trained service personnel.
When working on the equipment, observe precautions in the

literature and on tags, stickers, and labels attached to the

equipment.
Follow all safety codes. Wear safety glasses and work gloves. Keep

quenching cloth and fire extinguisher nearby when brazing. Use

care in handling, rigging, and setting bulky equipment.
Read these instructions thoroughly and follow all warnings or

cautions included in literature and attached to the unit. Consult

local building codes and National Electrical Code (NEC) for

special requirements.

Recognize safety information. This is the safety

alert symbol 

!

 !

.

When you see this symbol on the unit and in instructions or

manuals, be alert to the potential for personal injury. Understand

these signal words: DANGER, WARNING, and CAUTION.
These words are used with the safety

alert symbol. DANGER

identifies the most serious hazards which 

will 

result in severe

personal injury or death. WARNING signifies hazards which 

could

result in personal injury or death. CAUTION is used to identify

unsafe practices which 

may 

result in minor personal injury or

product and property damage. NOTE is used to highlight

suggestions which 

will

 result in enhanced installation, reliability, or

operation.

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal

injury or death.
Before installing, modifying, or servicing system, main

electrical disconnect switch must be in the OFF

position. There may be more than 1 disconnect switch.

Lock out and tag switch with a suitable warning label.

EXPLOSION HAZARD

Failure to follow this warning could

result in death, serious personal injury,

and/or property damage.
Never use air or gases containing

oxygen for leak testing or operating

refrigerant compressors. Pressurized

mixtures of air or gases containing

oxygen can lead to an explosion.

!

WARNING

CAUTION

!

EQUIPMENT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
Do not bury more than 36 in. (914 mm) of refrigerant pipe

in the ground. If any section of pipe is buried, there must

be a 6 in. (152 mm) vertical rise to the valve connections

on the outdoor units. If more than the recommended length

is buried, refrigerant may migrate to the cooler buried

section during extended periods of system shutdown. This

causes refrigerant slugging and could possibly damage the

compressor at start

up.

Summary of Contents for 40MBF Series

Page 1: ...he installation TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS 2 PARTS LIST 3 SYSTEM REQUIREMENTS 4 DIMENSIONS 5 CLEARANCES 5 INSTALLATION LOCATION REQUIREMENTS 6 INDOOR UNIT INSTALLATION 6 ELECTRICAL D...

Page 2: ...ds which will result in severe personal injury or death WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor...

Page 3: ...5 A150654 Fig 1 Parts List Note If the outdoor unit is higher than the indoor unit prevent rain from flowing into the indoor unit along the connection pipe by creating a downward arc in the connectio...

Page 4: ...d Communication Wiring The main power is supplied to the outdoor unit The field supplied 14 3 power communication wiring from the outdoor unit to the indoor unit consists of four 4 wires and provides...

Page 5: ...IMENSIONS Fig 2 Indoor Unit Table 2 Dimensions Indoor UNIT SIZE 9 12 Height in mm 8 27 210 8 27 210 Width in mm 27 56 700 27 56 700 Depth in mm 23 62 600 23 62 600 Weight Net Lb kg 32 41 14 7 32 41 14...

Page 6: ...6 CLEARANCES Fig 3 Indoor Unit Clearance...

Page 7: ...hooks are secured lift the unit and mount it on the hooks Be sure the hooks are on the correct mounting locations on the back of the unit see Fig 5 Washer Tapping screw Hook 6mm A150705 Fig 5 Hang the...

Page 8: ...ar A150710 Fig 11 Clamp Handle 5 Apply a small amount of refrigerant oil to the flare connection on the tubing 6 Align the center of the pipes Indoor unit tubing Flare nut Pipings A150711 Fig 12 Align...

Page 9: ...than 1 100 Bend S shape VP30 Downward declivity lower than 1 100 Put as deep as possible about 10cm A150714 Fig 16 Condensate Flow ELECTRICAL DATA Table 5 Electrical Data INDOOR FAN MAX FUSE CB AMP UN...

Page 10: ...ection feature prevents air conditioner from being activated for approximately 3 to 4 minutes 2 Press MODE and select COOLING HEATING FAN mode to check if all functions work correctly 3 To run the tes...

Page 11: ...open circuit or short circuit 7 times X EC Refrigerant leakage detection 8 times X EE Water level alarm malfunction 1 time O F0 Current overload protection 2 times O F1 Open circuit or short circuit...

Page 12: ...ration S 7310 W Morris St S Indianapolis IN 46231 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 40MBF 02SI Replaces...

Reviews: