SYSTEM REQUIREMENTS

Allow sufficient space for airflow and servicing unit.

Piping
IMPORTANT

Both refrigerant lines must be insulated separately.

S

  Minimum refrigerant line length between the indoor and outdoor units is 10 ft. (3 m).

S

  Table 2 lists the pipe sizes for the indoor unit. Refer to the outdoor unit installation instructions for other allowed piping lengths and

refrigerant information.

Table 1—Indoor Unit Pipe Sizes

9K

12K

Gas Pipe

in(mm)

3/8 (9.52)

1/2 (12.7)

Liquid Pipe

in(mm)

1/4 (6.35)

1/4 (6.35)

All wires must be sized per NEC (National Electrical Code) or

CEC (Canadian Electrical Code) and local codes. Use the

Electrical Data table MCA (minimum circuit amps) and MOCP

(maximum over current protection) to correctly size the wires and

the disconnect fuse or breakers respectively.
Per the caution note, only stranded copper conductors with a 600

volt rating and a double insulated copper wire must be used.

IMPORTANT

: The use of BX cable is not recommended.

Recommended Connection Method for Power and

Communication Wiring 

 Power and Communication Wiring:

The main power is supplied to the outdoor unit. The field

supplied 14/3 power/communication wiring from the outdoor unit

to the indoor unit consists of four (4) wires and provides the

power for the indoor unit. Two wires are high voltage AC power.

One wire is for communication wiring and the other is a ground

wire.

Recommended Connection Method for Power and

Communication Wiring (To minimize communication wiring

interference)
Power Wiring:

The main power is supplied to the outdoor unit. The field

supplied connecting cable from the outdoor unit to the indoor unit

consists of three (3) wires and provides the power for the indoor

unit. Two wires are high voltage AC power and one is a ground

wire.

Communication Wiring:

A separate stranded copper conductor only, with a 600 volt rating

and a double insulated copper wire must be used as the

communication wire from the outdoor unit to the indoor unit.

Please use a separate shielded 16GA stranded control wire.

CAUTION

!

EQUIPMENT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.

S

Wires should be sized based on NEC and local codes.

S

Use copper conductors only with a 600 volt rating and 

double insulated copper wire.

Summary of Contents for 40MBF Series

Page 1: ...he installation TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS 2 PARTS LIST 3 SYSTEM REQUIREMENTS 4 DIMENSIONS 5 CLEARANCES 5 INSTALLATION LOCATION REQUIREMENTS 6 INDOOR UNIT INSTALLATION 6 ELECTRICAL D...

Page 2: ...ds which will result in severe personal injury or death WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor...

Page 3: ...5 A150654 Fig 1 Parts List Note If the outdoor unit is higher than the indoor unit prevent rain from flowing into the indoor unit along the connection pipe by creating a downward arc in the connectio...

Page 4: ...d Communication Wiring The main power is supplied to the outdoor unit The field supplied 14 3 power communication wiring from the outdoor unit to the indoor unit consists of four 4 wires and provides...

Page 5: ...IMENSIONS Fig 2 Indoor Unit Table 2 Dimensions Indoor UNIT SIZE 9 12 Height in mm 8 27 210 8 27 210 Width in mm 27 56 700 27 56 700 Depth in mm 23 62 600 23 62 600 Weight Net Lb kg 32 41 14 7 32 41 14...

Page 6: ...6 CLEARANCES Fig 3 Indoor Unit Clearance...

Page 7: ...hooks are secured lift the unit and mount it on the hooks Be sure the hooks are on the correct mounting locations on the back of the unit see Fig 5 Washer Tapping screw Hook 6mm A150705 Fig 5 Hang the...

Page 8: ...ar A150710 Fig 11 Clamp Handle 5 Apply a small amount of refrigerant oil to the flare connection on the tubing 6 Align the center of the pipes Indoor unit tubing Flare nut Pipings A150711 Fig 12 Align...

Page 9: ...than 1 100 Bend S shape VP30 Downward declivity lower than 1 100 Put as deep as possible about 10cm A150714 Fig 16 Condensate Flow ELECTRICAL DATA Table 5 Electrical Data INDOOR FAN MAX FUSE CB AMP UN...

Page 10: ...ection feature prevents air conditioner from being activated for approximately 3 to 4 minutes 2 Press MODE and select COOLING HEATING FAN mode to check if all functions work correctly 3 To run the tes...

Page 11: ...open circuit or short circuit 7 times X EC Refrigerant leakage detection 8 times X EE Water level alarm malfunction 1 time O F0 Current overload protection 2 times O F1 Open circuit or short circuit...

Page 12: ...ration S 7310 W Morris St S Indianapolis IN 46231 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 40MBF 02SI Replaces...

Reviews: