Prior to installation

It is advisable to place the unit as close as possible to the
installation site before removing it from the packaging. The grille
panel and the remote control are separately packed for maximum
protection.

IMPORTANT:
Do not lift the unit by the condensate drain discharge pipe or
by the refrigerant connections; hold it by its four corners
only.

Unit installation will be facilitated using a stacker.

If plaster board ceiling panels are installed the maximum
dimensions of the unit housing must not exceed 660 x 660 mm (for
model 050) and 900 x 900 mm (for models  080,110, 130).

In rooms with high humidity, brackets should be insulated using
the  self adhesive insulation supplied.

Installation

Installation




   

                               

 

 

 

mm

Threaded hangers

"T" bar
(to be removed)

 False ceiling

 Spirit level

Suspension brackets

Carefully lift the unit (without the frame) using the four
suspension brackets (or the four corners), inserting it into the
false ceiling.
If the “T” bar cannot be removed the unit may need to be tilted
(this operation may only be carried out with false ceilings with a
minimum height of 300 mm).

First position the refrigerant lines, as described in the chapter
“Refrigerant connections”.
Remove the “T” bar in order to facilitate installation operations.

Mark the position of the hangers, refrigerant lines and condensate
drain pipe, power supply cables and remote control cable (see
dimensions); the cardboard template (supplied with the kit) may be
of assistance for this operation.
Depending on the type of ceiling the hangers can be fixed as
shown in the drawing.

Once the threaded hangers have been positioned, do not tighten
the nuts, and insert the washers as shown in the drawing.

Washer

Threaded hangers

Washer

Nut

Nut

Nut

Wooden frame

Threaded hangers

Washers

 

Nut

Align and level the unit by adjusting the nuts and locknuts on the
threaded hangers, maintaining a distance of 25 - 30 mm
between the sheet metal body and the underside of the false
ceiling.
Reposition the “T” bar and align the unit in relation to the bar by
tightening the nuts and locknuts.
After connection of the condensate drain line and the refrigerant
lines, carry out a final check to make sure that the unit is level.

Summary of Contents for 40KQV

Page 1: ...40KQV INSTALLATION MANUAL L L O Y D S R E G I S TER QUALIT Y A S S U R A N C E IS O 900 1...

Page 2: ...he manuals for each unit These are supplied with the unit Contents Page Dimensions and weight 2 Technical data 3 Material supplied 3 Operating limits 3 Components required for a complete installation...

Page 3: ...40KQV 050 080 110 130 Unit 19 36 38 38 Frame Grille assembly 3 5 5 5 kg 575 298 120 225 280 56 52 91 575 158 720 550 515 1 5 0 7 0 5 0 3 0 25 813 595 825 120 298 168 237 960 825 1 5 0 6 6 4 8 2 5 100...

Page 4: ...it according to EN 60335 2 40 standards Technical data TableII Material supplied Description Quantity Use Installation instructions 1 Indoor unit installation Owner s Manual 1 Correct use Fresh air in...

Page 5: ...to any other manufacturer s outdoor unit The manufacturer declines any liability for system malfunction resulting from unauthorised system combinations General information The manufacturer declines a...

Page 6: ...nit flattening or kinking the refrigerant pipes or condensate pipes installation in areas with high frequency waves only partial insulation of the piping Non level installation which will cause conden...

Page 7: ...possible in the room the air flow direction can be controlled by means of the remote control where used or automatically according to the operating mode cooling or heating this will ensure optimum dis...

Page 8: ...unit may need to be tilted this operation may only be carried out with false ceilings with a minimum height of 300 mm First position the refrigerant lines as described in the chapter Refrigerant conne...

Page 9: ...10 mm slope toward the outside Insert the plastic conduit provided Pass the power connection cables through the conduit see electrical connections Condensate drain pipe To ensure correct condensate wa...

Page 10: ...o the pipes Make the flare to the pipe end with the proper flaring tool Flare end must not have any burrs or imperfections The length of the flared walls must be uniform Lubricate the end of pipe and...

Page 11: ...Emergency push button Fan connector LED RECEIVER connector Float connector Pump connector Louverconnector CP CG CA CV CLR B Outdoor unit connection SYSTEM CONFIGURATION Make the electrical connection...

Page 12: ...Earth 1 Live connection indoor outdoor unit 2 Neutral connection indoor outdoor unit 3 Communication high voltage Cable passage Interconnection cable 4x1 mm2 H07 RN F Room Controller CZM connecting c...

Page 13: ...yrene partition Introduce baffle supplied after frame has been hooked as per above figure Following that screw the frame grille assembly using the 4 screws Use locally purchased material suitable for...

Page 14: ...gths can be calculated in accordance with the air distribution to an adjacent room diagram also taking into account the pressure drop through air diffusers and fresh air filters DO NOT use active carb...

Page 15: ...either the or button to change the default value of minimum cooling set point temperature admitted in Degrees Celsius 17 or Degrees Fahrenheit 63 to the new value Degrees Celsius 17 32 or Degrees Fah...

Page 16: ...perations or for any other needs Unit warning lights and guide for the owner Button T EMERGENCY Can be used when the remote control is lost or inoperative Use a screwdriver to press the push button th...

Page 17: ...125H95 0605 Via R Sanzio 9 20058 Villasanta MI Italy Tel 039 3636 1 The manufacturer reserves the right to change any product specifications without notice June 2005 Supersedes April 2005 Printed in I...

Reviews: