background image

40KQV

GB - 12

                                                               

 

120

105

49

Ø A

216

B

Ø A

Ø

 C

 

Fresh air renewal and conditioned air supply to an adjacent room

Model

050

080 - 110 - 130

Ø A

 mm

150

150

B

 mm

120

120

Ø C

mm

70

100

Duct connection flange

Clip

6 mm neoprene gasket

Insulated flexible duct

 

Fresh air intake

Conditioned air supply to an
adjacent room

Polystyrene partition

Baffle

Frame

 

Wall

 

Undercut door

 

Wall-fitted grille

 

Door-fitted grille

Air intake grille

• Side knockouts allow connection of fresh air inlet ducts and

ducts to deliver conditioned air to an adjacent room.

• Remove the external prepunched anti-condensate insulation and

take away the knockout panels using a punch.

Air distribution to adjacent room

With a pencil, trace a line on the polystyrene around the inside
edges of the panel that was previously removed.
Cut away the polystyrene with a knife, taking care not to damage
the heat exchange coil.

Fresh air intake

Remove the polystyrene partition.
Introduce baffle supplied after frame has been hooked as per
above figure.

Following that screw the frame/grille assembly using the 4 screws.

• Use locally purchased material, suitable for operating

temperatures of 60 

°

C (continuous).

Conduits can be of flexible polyester (with spiral core) or
corrugated aluminium, externally covered with anti-condensate
material (fibre glass from 12 to 25 mm thickness).

• To complete the installation, all non-insulated ducts must be

covered with anti-condensate insulation (ex. expanded neoprene,
6 mm thickness).

Not observing of these instructions may cause condensate
dripping; the manufacturer will not be held responsible for
any damage caused.

• The two prepunched side knockouts must not be used at the

same time to deliver conditioned air to an adjacent room.

• The return and supply duct lengths can be calculated in

accordance with the “air distribution to an adjacent room” and
“fresh air renewal” diagrams (also taking into account the
pressure drop through air diffusers, grilles and fresh air filters),
as well as the increase in noise caused by these ducts.

Summary of Contents for 40KQV

Page 1: ...40KQV INSTALLATION MANUAL L L O Y D S R E G I S TER QUALIT Y A S S U R A N C E IS O 900 1...

Page 2: ...he manuals for each unit These are supplied with the unit Contents Page Dimensions and weight 2 Technical data 3 Material supplied 3 Operating limits 3 Components required for a complete installation...

Page 3: ...40KQV 050 080 110 130 Unit 19 36 38 38 Frame Grille assembly 3 5 5 5 kg 575 298 120 225 280 56 52 91 575 158 720 550 515 1 5 0 7 0 5 0 3 0 25 813 595 825 120 298 168 237 960 825 1 5 0 6 6 4 8 2 5 100...

Page 4: ...it according to EN 60335 2 40 standards Technical data TableII Material supplied Description Quantity Use Installation instructions 1 Indoor unit installation Owner s Manual 1 Correct use Fresh air in...

Page 5: ...to any other manufacturer s outdoor unit The manufacturer declines any liability for system malfunction resulting from unauthorised system combinations General information The manufacturer declines a...

Page 6: ...nit flattening or kinking the refrigerant pipes or condensate pipes installation in areas with high frequency waves only partial insulation of the piping Non level installation which will cause conden...

Page 7: ...possible in the room the air flow direction can be controlled by means of the remote control where used or automatically according to the operating mode cooling or heating this will ensure optimum dis...

Page 8: ...unit may need to be tilted this operation may only be carried out with false ceilings with a minimum height of 300 mm First position the refrigerant lines as described in the chapter Refrigerant conne...

Page 9: ...10 mm slope toward the outside Insert the plastic conduit provided Pass the power connection cables through the conduit see electrical connections Condensate drain pipe To ensure correct condensate wa...

Page 10: ...o the pipes Make the flare to the pipe end with the proper flaring tool Flare end must not have any burrs or imperfections The length of the flared walls must be uniform Lubricate the end of pipe and...

Page 11: ...Emergency push button Fan connector LED RECEIVER connector Float connector Pump connector Louverconnector CP CG CA CV CLR B Outdoor unit connection SYSTEM CONFIGURATION Make the electrical connection...

Page 12: ...Earth 1 Live connection indoor outdoor unit 2 Neutral connection indoor outdoor unit 3 Communication high voltage Cable passage Interconnection cable 4x1 mm2 H07 RN F Room Controller CZM connecting c...

Page 13: ...yrene partition Introduce baffle supplied after frame has been hooked as per above figure Following that screw the frame grille assembly using the 4 screws Use locally purchased material suitable for...

Page 14: ...gths can be calculated in accordance with the air distribution to an adjacent room diagram also taking into account the pressure drop through air diffusers and fresh air filters DO NOT use active carb...

Page 15: ...either the or button to change the default value of minimum cooling set point temperature admitted in Degrees Celsius 17 or Degrees Fahrenheit 63 to the new value Degrees Celsius 17 32 or Degrees Fah...

Page 16: ...perations or for any other needs Unit warning lights and guide for the owner Button T EMERGENCY Can be used when the remote control is lost or inoperative Use a screwdriver to press the push button th...

Page 17: ...125H95 0605 Via R Sanzio 9 20058 Villasanta MI Italy Tel 039 3636 1 The manufacturer reserves the right to change any product specifications without notice June 2005 Supersedes April 2005 Printed in I...

Reviews: