22
NOTE: Two-pole motors operate at a nominal 3600 rpm for 60 Hz and
3000 rpm for 50 Hz; 4-pole motors operate at a nominal 1800 rpm for
60 Hz and 1500 rpm for 50 Hz.
Table 6 — VFD Data
39M
MOTOR HP
ABB PART
NO. ACH550-UH-
MAX. CONTINUOUS
OUTPUT AMPS
FUSE AMPS
MCCB
RATED AMPS
PROGRAMMED SETTINGS
OVERLOAD TRIP AMPS
4 POLE / 2 POLE
MAX. OUTPUT AMPS
4 POLE / 2 POLE
208-230 VOLT / 3 PHASE / 60 HZ (PROGRAMMED TO OPERATE AT 208 VOLTS)
1/2
04A6-2
4.6
10
15
1.8/ 1.7
3.0/ 2.2
3/4
04A6-2
4.6
10
15
2.6/ 2.5
3.2/ 3.0
1
04A6-2
4.6
10
15
3.5/ 3.2
3.8/ 3.8
1-1/2
06A6-2
6.6
10
15
5.2/ 4.2
5.8/ 5.8
2
07A5-2
7.5
10
15
6.7/ 5.9
7.2/ 7.0
3
012A-2
11.8
15
15
9.0/ 8.5
10.0/ 9.5
5
017A-2
16.7
25
25
14.5/ 13.6
16.7/ 16.0
7-1/2
024A-2
24.2
30
30
21.4/ 20.7
24.0/ 23.0
10
031A-2
30.8
40
40
27.4/ 27.4
30.8/ 30.0
15
046A-2
46.2
60
60
40.5/ 40.5
46.2/ 43.0
20
059A-2
59.4
80
80
53.0/ 52.2
59.4/ 57.0
25
075A-2
74.8
100
100
67.0/ 66.0
74.0/ 71.0
30
088A-2
88.0
110
110
82.0/ 78.0
85.0/ 82.0
40
114A-2
114.0
150
150
92.0/107.0
114.0/110.0
208-230 VOLT / 3 PHASE / 60 HZ (PROGRAMMED TO OPERATE AT 230 VOLTS)
50
143A-2
143.0
200
200
125.0/130.0
142.0/130.0
60
178A-2
178.0
250
250
154.0/135.0
172.0/145.0
75
221A-2
221.0
300
300
186.0/166.0
221.0/172.0
460 VOLT / 3 PHASE / 60 HZ (PROGRAMMED TO OPERATE AT 460 VOLTS)
1/2
03A3-4
3.3
10
15
0.9/ 1.0
1.5/ 1.2
3/4
03A3-4
3.3
10
15
1.3/ 1.2
1.7/ 1.5
1
03A3-4
3.3
10
15
1.6/ 1.5
1.9/ 1.7
1-1/2
03A3-4
3.3
10
15
2.2/ 2.0
2.8/ 2.3
2
03A3-4
3.3
10
15
2.7/ 2.7
3.0/ 3.0
3
06A9-4
5.4
10
15
4.0/ 3.8
4.5/ 4.2
5
06A9-4
6.9
10
15
6.2/ 6.0
6.9/ 6.5
7-1/2
012A-4
11.9
15
15
9.0/ 8.8
10.0/ 9.5
10
015A-4
15.4
20
20
12.0/ 11.6
13.6/ 12.8
15
023A-4
23.0
30
30
17.6/ 16.5
19.3/ 19.0
20
031A-4
31.0
40
40
23.0/ 23.0
25.0/ 25.0
25
031A-4
31.0
40
40
29.0/ 28.0
31.0/ 30.0
200-230 VOLT / 3 PHASE / 50 HZ (PROGRAMMED TO OPERATE AT 200 VOLTS)
1
04A6-2
4.6
10
15
3.3/ 3.3
3.9/ 3.9
1-1/2
06A6-2
6.6
10
15
4.9/ 4.9
5.8/ 5.8
2
07A5-2
7.5
10
15
6.3/ 6.3
7.1/ 7.1
3
012A-2
11.8
15
15
8.7/ 8.7
10.0/ 10.0
5
017A-2
16.7
25
25
14.0/ 14.0
16.7/ 16.7
7-1/2
024A-2
24.2
30
30
21.2/ 20.2
24.2/ 24.2
10
031A-2
30.8
40
40
27.2/ 27.4
30.8/ 30.8
15
046A-2
46.2
60
60
41.4/ 40.5
46.2/ 46.2
20
059A-2
59.4
80
80
53.4/ 49.0
59.4/ 56.0
25
075A-2
74.8
100
100
65.4/ 66.0
74.0/ 74.8
380 VOLTS / 3 PHASE / 50 HZ (PROGRAMMED TO OPERATE AT 400 VOLTS)
1
03A3-4
3.3
10
15
1.7/ 1.7
2.3/ 2.3
1-1/2
03A3-4
3.3
10
15
2.5/ 2.5
3.3/ 3.3
2
04A1-4
4.1
10
15
3.2/ 3.2
3.8/ 3.6
3
06A9-4
5.4
10
15
4.5/ 4.5
5.4/ 5.3
5
08A8-4
8.8
15
15
7.0/ 7.0
8.5/ 8.0
7-1/2
012A-4
11.9
15
15
10.6/ 8.9
11.9/ 11.0
10
015A-4
15.4
20
20
13.6/ 11.6
15.4/ 14.6
15
023A-4
23.0
30
30
20.7/ 17.0
22.6/ 21.0
20
031A-4
31.0
40
40
26.7/ 24.5
29.3/ 29.0
25
038A-4
38.0
50
50
32.7/ 29.5
37.0/ 36.0
LEGEND
MCCB