background image

R-410A—QUICK REFERENCE GUIDE

R-410A refrigerant operates at 50-70 percent higher pressures than R-22. Be sure that servicing equipment and replacement
components are designed to operate with R-410A.

R-410A refrigerant cylinders are rose colored.

R-410A refrigerant cylinders have a dip tube which allows liquid to flow out of cylinder in upright position.

Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400.

R-410A systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose.

Manifold sets should be 800 psig high side and 250 psig low side with 550 psig low-side retard.

Use hoses with 800 psig service pressure rating.

Leak detectors should be designed to detect HFC refrigerant.

R-410A, as with other HFCs, is only compatible with POE oils.

Vacuum pumps will not remove moisture from oil.

Do not use liquid-line filter driers with rated working pressures less than 600 psig.

Do not install a suction-line filter drier in liquid line.

POE oils absorb moisture rapidly. Do not expose oil to atmosphere.

POE oils may cause damage to certain plastics and roofing materials.

Wrap all filter driers and service valves with wet cloth when brazing.

A liquid-line filter drier is required on every unit.

Do not use an R-22 TXV.

If indoor unit is equipped with an R-22 TXV, it must be changed to an R-410A TXV.

Never open system to atmosphere while it is under a vacuum.

When system must be opened for service, break vacuum with dry nitrogen prior to opening to atmosphere.

Always replace filter drier after opening system for service.

Do not vent R-410A into the atmosphere.

Do not use capillary tube coils.

Observe all warningscautions, and bold text.

6

Summary of Contents for 38YXA

Page 1: ...mpressor discharge gas an energy efficient fan and fan motor to move air more efficiently and the InViroFlow design for an improved airflow pattern which requires less energy All units contain scroll compressors specially designed for use with R 410A FEATURES SEER up to 14 5 and HSPF up to 8 5 with specified Carrier equipment Silencer System Environmentally safe refrigerant R 410A High pressure sw...

Page 2: ... 20 20 Rows 1 1 2 2 2 2 Circuits 2 3 3 3 4 5 VALVE CONNECTION In ID Sweat Vapor 5 8 3 4 3 4 7 8 7 8 7 8 Liquid 3 8 REFRIGERANT TUBES In OD Vapor 0 50 Ft Tube Length 5 8 3 4 3 4 7 8 7 8 1 1 8 Vapor Alternate 3 4 ACR 7 8 7 8 7 8 7 8 7 8 Vapor RST Not Permitted 3 4 1 1 8 1 1 8 3 4 and 1 1 8 3 4 and 1 1 8 3 4 Liquid All Applications 3 8 Tube diameters are for lengths up to 50 ft For tubing lengths gre...

Page 3: ...Changeover Non Programmable F C 2 Stage Heat 1 Stage Cool TSTATCCPHP01 A Thermostat Auto Changeover 7 Day Programmable F C 2 Stage Heat 1 Stage Cool TSTATCCPDF01 A Thermostat Auto Changeover 7 Day Programmable F C Dual Fuel Must be used with Outdoor Air Temperature Sensor TSTATXXSEN01 TSTATCCPRH01 A Thermidistat Control Programmable Thermostat with Humidity Control HH 07AT 215 Thermostat Manual Ch...

Page 4: ...ance ment Standard Rating Carrier Gas Furnace or Accessory TDR Accessory TXV TC COP TC COP 024 30 FX4ANF030 25 000 TDR TXV 13 00 11 50 25 000 3 30 16 600 2 30 8 00 030 30 FX4ANF030 29 000 TDR TXV 13 00 11 40 30 000 3 50 18 500 2 34 8 00 036 30 FX4ANF042 35 000 TDR TXV 13 00 11 30 35 000 3 35 21 600 2 34 7 70 042 30 FV4ANF003 40 500 TDR TXV 13 10 11 30 40 500 3 35 25 400 2 45 7 70 048 30 FV4ANF005 ...

Page 5: ...or operating ambient in heating mode is 66 F 3 Series designation is the 13th position of the unit model number 4 Center of gravity 5 NOTES A96517 Dimensions In UNIT SIZE SERIES UNIT DIMENSIONS MINIMUM MOUNTING PAD DIMENSIONS A B C D E F G H J K L M Support Feet Snow Stand 024 30 39 13 16 30 34 15 16 4 9 3 4 27 1 2 33 7 8 5 8 8 3 16 15 7 8 14 3 8 14 1 4 26 X 32 31 X 35 030 30 33 13 16 30 34 15 16 ...

Page 6: ...rant R 410A as with other HFCs is only compatible with POE oils Vacuum pumps will not remove moisture from oil Do not use liquid line filter driers with rated working pressures less than 600 psig Do not install a suction line filter drier in liquid line POE oils absorb moisture rapidly Do not expose oil to atmosphere POE oils may cause damage to certain plastics and roofing materials Wrap all filt...

Page 7: ...door unit is indoor coil above 30 ft indoor coil below 30 ft See items 8 and 9 following 8 For interconnecting tubing lengths greater than 50 ft consult the Residential Split System Application Guideline and Service Manual for Air Conditioners and Heat Pumps using R 410A Refrigerant 9 If ANY refrigerant tubing is buried provide a minimum 6 in vertical rise to the valve connections at the unit Refr...

Page 8: ...rvice Training plus hands on the products in our labs can mean increased confidence that really pays dividends in faster troubleshooting fewer callbacks Course descriptions and schedules are in our catalog CALL FOR FREE CATALOG 1 800 962 9212 Packaged Service Training Classroom Service Training Copyright 1997 CARRIER Corp 7310 W Morris St Indianapolis IN 46231 38yxa1pf Manufacturer reserves the ri...

Reviews: