
R-410A—QUICK REFERENCE GUIDE
•
R-410A refrigerant operates at 50-70 percent higher pressures than R-22. Be sure that servicing equipment and replacement
components are designed to operate with R-410A.
•
R-410A refrigerant cylinders are rose colored.
•
R-410A refrigerant cylinders have a dip tube which allows liquid to flow out of cylinder in upright position.
•
Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400.
•
R-410A systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose.
•
Manifold sets should be 800 psig high side and 250 psig low side with 550 psig low-side retard.
•
Use hoses with 800 psig service pressure rating.
•
Leak detectors should be designed to detect HFC refrigerant.
•
R-410A, as with other HFCs, is only compatible with POE oils.
•
Vacuum pumps will not remove moisture from oil.
•
Do not use liquid-line filter driers with rated working pressures less than 600 psig.
•
Do not install a suction-line filter drier in liquid line.
•
POE oils absorb moisture rapidly. Do not expose oil to atmosphere.
•
POE oils may cause damage to certain plastics and roofing materials.
•
Wrap all filter driers and service valves with wet cloth when brazing.
•
A liquid-line filter drier is required on every unit.
•
Do not use an R-22 TXV.
•
If indoor unit is equipped with an R-22 TXV, it must be changed to an R-410A TXV.
•
Never open system to atmosphere while it is under a vacuum.
•
When system must be opened for service, break vacuum with dry nitrogen prior to opening to atmosphere.
•
Always replace filter drier after opening system for service.
•
Do not vent R-410A into the atmosphere.
•
Do not use capillary tube coils.
•
Observe all warnings, cautions, and bold text.
6