background image

38VYM 

R-410A

GB - 12

Incorrect wiring and piping procedure check

This procedure only applies to models 38VYM-28 and 38VYM-32.

The incorrect wiring/piping procedure check can be performed at an
ambient temperature of 5

°

C or more.

Sequence with electrical and refrigerant connections correctly
carried out:

• Position the red connector 

 

outside of terminal block zone.

• Switch the main power supply ON and start all indoor units in

cooling mode.

• Disconnect the red connector 

 

(incorrect wiring/piping test),

 with compressor OFF.

• Start the test sequence for incorrect wiring/piping.

• The yellow LED 

 flashes (D800).

• During the test for incorrect wiring/piping, the

compressor starts operating at a fixed frequency, the outdoor unit
fan operates normally, the indoor unit fans remain OFF.

• The yellow LED 

 

and red LED 

 

flash

(D800 and D801).

• The yellow LED 

 

and red LED 

 flash

(D800 and D802).

• The yellow LED 

 

and red LED 

 flash

(D800 and D803).

• The yellow LED 

 

and red LED 

 flash

(D800 and D804).

• Normally the test procedure for incorrect

wiring/piping lasts from 3 to 15 minutes.

• When the test procedure is completed, the compressor and

outdoor unit fan stop operation, the red LED 

(D801) flashes, while the yellow one 

 

(D800) is

OFF.

• If no incorrect wiring/piping has been found, system automatically

restarts and the red LED 

 

(D801) that was

flashing, turns OFF.

• Reconnect the red connector 

.

At the end of the test, if there is a fault code, the yellow LED 

(D800) flashes and the red LEDs that indicate the defect remain ON
(see table).
The compressor does not start and the indoor unit fans operate in
fan only mode.

After the defect has been corrected, repeat the procedure and carry
out another check.

CHECK LED

LED

  

LED

D800

D801

D802

D803

D804

Description

Normal operation (no fault)

Checking unit A1

Check

Checking unit A2

Checking unit A3

*

Checking unit A4

Kinking/clogging of pipe unit A1

Kinking/clogging of pipe unit A2

Kinking/clogging of pipe unit A3

*

Kinking/clogging of pipe unit A4

Incorrect wiring/piping or kinking/clogging of pipe unit A1, A2

Incorrect wiring/piping or kinking/clogging of pipe unit A1, A3

*

Incorrect wiring/piping or kinking/clogging of pipe unit A1, A4

Fault

Incorrect wiring/piping or kinking/clogging of pipe unit A2, A3

*

Incorrect wiring/piping or kinking/clogging of pipe unit A2, A4

*

Incorrect wiring/piping or kinking/clogging of pipe unit A3, A4

Incorrect wiring/piping of pipe unit A1, A2, A3

Incorrect wiring/piping of pipe unit A1, A2, A4

Incorrect wiring/piping of pipe unit A1, A3, A4

Incorrect wiring/piping of pipe unit A2, A3, A4

Incorrect wiring/piping of packed valve,
that keeps the circuit closed, unit A1, A2, A3, A4

Table IV: Check for incorrect wiring/piping

Legend:

LED ON
LED OFF
LED flashing

*

Only for 38VYM-32 model

Red LED (D803)

Red LED (D804)

Red connector

Yellow LED (D800)

Red LED (D801)

Red LED (D802)

Summary of Contents for 38VYM Series

Page 1: ...38VYM L L O Y D S R E G I S TER QUALIT Y A S S U R A N C E IS O 900 1 R 410A INSTALLATION MANUAL...

Page 2: ...70 higher than R 22 Be sure that servicing equipment and replacement components are designed to operate with R 410A R 410A refrigerant cylinders are pink R 410A refrigerant cylinders have a dip tube...

Page 3: ...A mm 800 800 800 B mm 590 800 800 C mm 300 300 300 D mm 508 508 508 E mm 146 146 146 F mm 330 330 330 kg kg 50 64 65 38VYM 28 38VYM 32 Model 38VYM 18 28 32 A mm 100 100 100 B mm 250 250 250 C mm 500...

Page 4: ...s designed with chargeless specification For 38VYM 28 and 38VYM 32 models connection of only one indoor unit is not allowed Two or more units must be connected A4 A3 A2 A1 H Table I Connections 38VYM...

Page 5: ...owed for the mains supply circuit The mains supply must be connected to the outdoor unit Connect indoor and outdoor units with field supplied copper pipes by means of flare connections Use insulated s...

Page 6: ...wet before connection Disconnecting the refrigerant connections after installation as this will cause refrigerant leaks Connecting the condensate drain pipe to the outdoor unit Predominant head winds...

Page 7: ...otect copper tubes during storage Use tools designed for R 410A higher pressure Keep inside clean 2 stage vacuum pump Replace oil regularly No moisture No dust No leak No mineral oil Neat Dry nitrogen...

Page 8: ...the wall using the bracket kit Connect tubing in accordance with the limits shown on Table II Connections Finger tighten the fitting several turns then tighten it with a wrench by applying the tighten...

Page 9: ...vacuum with a vacuum pump connected to the service connection of the suction shut off valve as shown keeping the shut off valves completely shut until a 50 Pa 0 5 mbar vacuum has been reached Now ope...

Page 10: ...1 2 3 A1 A2 1 2 3 1 2 3 A3 A4 A3 1 2 3 Terminal box legend Earth L Live power supply N Neutral power supply 1 Connection indoor outdoor unit 2 Connection indoor outdoor unit 3 Connection indoor outdo...

Page 11: ...th L Live power supply N Neutral power supply 1 Connection indoor outdoor unit 2 Connection indoor outdoor unit 3 Connection indoor outdoor unit Indoor unit Outdoor unit Main switch Time delay fuse or...

Page 12: ...rs to indoor unit A4 This only refers to model 38VYM 32 Make certain the refrigerant pipes and the electrical connection lines between the indoor unit and the outdoor unit have the same colours and re...

Page 13: ...as flashing turns OFF Reconnect the red connector At the end of the test if there is a fault code the yellow LED D800 flashes and the red LEDs that indicate the defect remain ON see table The compress...

Page 14: ...posal in this case after removal the unit must be delivered to an appropriate disposal centre or the original dealer Shut off the liquid valves with the Allen wrench Turn the indoor units ON in coolin...

Page 15: ...io 9 20058 Villasanta MI Italy Tel 039 3636 1 The manufacturer reserves the right to change any product specifications without notice Order No 13812 74M10 January 2003 Supersedes Order No 13812 74M10...

Reviews: