POWER SUPPLY
Table 27 —Electrical Characteristics of Outdoor Units
Table 28 —Electrical Characteristics of MDC Units
OUTDOOR UNITS (208/230-3-60)
COMPRESSOR
MODEL
VOLTS
VOLTAGE RANGE
Hz
MCA(A)
RECOMMENDED FUSE SIZE (A)
SC(A)
38VMA072RDS5-1
208/230V
187 to 253V
60
43
50
12
38VMA096RDS5-1
45
50
12
38VMA120RDS5-1
46
50
12
38VMA144RDL5-1
70
80
12
38VMA168RDS5-1
70
80
12
38VMA192RDS5-1
71
80
12
38VMA216RDS5-1
81
100
12
38VMA240RDS5-1
81
100
12
38VMA240RDL5-1
101
110
12
38VMA264RDS5-1
104
110
12
38VMA288RDS5-1
104
110
12
38VMA312RDS5-1
106
110
12
38VMA336RDS5-1
106
110
12
OUTDOOR UNITS (460-3-60)
38VMA072RDS6-1
460V
414 to 506V
60
20
30
7
38VMA096RDS6-1
22
30
7
38VMA120RDS6-1
22
30
7
38VMA144RDL6-1
35
40
7
38VMA168RDS6-1
35
40
7
38VMA192RDS6-1
35
40
7
38VMA216RDS6-1
38
40
7
38VMA240RDS6-1
38
40
7
38VMA240RDL6-1
52
60
7
38VMA264RDS6-1
54
60
7
38VMA288RDS6-1
54
60
7
38VMA312RDS6-1
55
60
7
38VMA336RDS6-1
55
60
7
MCA : Min. Circuit Amps
SC : Starting Current
MAIN MDC UNITS (208/230-1-60)
MODEL
VOLTS
VOLTAGE RANGE
HZ
MCA(A)
40VMD006M--3
208/230V
187 to 253V
60
0.73
40VMD008M--3
0.89
40VMD010M--3
1.05
40VMD016M--3
1.54
40VMD016ML-3
1.54
SUB MDC UNITS (208/230-1-60)
40VMD006S--3
208/230V
187 to 253V
60
0.69
40VMD008S--3
0.85
40VMD010S--3
1.01
40VMD016S--3
1.49
Summary of Contents for 38VMA072RDS5-1
Page 24: ...24 Refrigerant Circuit Diagram Fig 7 38VMA072 096 120RDS Models...
Page 25: ...25 Refrigerant Circuit Diagram Cont Fig 8 38VMA144RDL 168 196 216 240RDS Models...
Page 26: ...26 Refrigerant Circuit Diagram Cont Fig 9 38VMA240RDL 264 288 312 336RDS Models...
Page 55: ...55 Equipment Selection SELECTION FLOW CHART Fig 53 Selection Flow Chart...