MULTI SYSTEM AIR CONDITIONER

INSTALLATION MANUAL

G B

ENGLISH

INSTALLATION MANUAL

I T

ITALIANO

MANUALE DI INSTALLAZIONE

F R

MANUEL D'INSTALLATION

D E

INSTALLATIONSHANDBUCH

DEUTSCH

E S

MANUAL DE INSTALACIÓN

N L

INSTALLATIEHANDLEIDING
NEDERLANDS

FRANÇAIS

ESPAÑOL

P L

POLSKI

INSTRUKCJA MONTA

Ż

U

Summary of Contents for 38QUS018DS2 Series

Page 1: ...NUAL G B ENGLISH INSTALLATION MANUAL I T ITALIANO MANUALE DI INSTALLAZIONE F R MANUEL D INSTALLATION D E INSTALLATIONSHANDBUCH DEUTSCH E S MANUAL DE INSTALACIÓN N L INSTALLATIEHANDLEIDING NEDERLANDS FRANÇAIS ESPAÑOL P L POLSKI INSTRUKCJA MONTAŻU ...

Page 2: ...en buying a new product the retailer will take back the old product at least free of charge 3 The manufacture will take back the old appliance for disposal at least free of charge to the user 4 As old products contain valuable resources they can be sold to scrap metal dealers Wild disposal of waste in forests and landscapes endangers your health when hazardous substances leak into the ground water...

Page 3: ...UTDOOR UNIT INSTALLATION 3 1 Select The Installation Site 3 2 Outdoor Unit Mounting Dimensions 3 3 Space Requirements For Outdoor Unit 3 4 Install The Outdoor Unit 3 5 Install The Drain Pipe For Outdoor Unit 4 REFRIGERANT PIPING WORK 4 1 Flaring 4 2 Piping Work 4 3 Refrigerant Pipe 4 4 Air Evacuation 4 5 Leakage Test 5 WIRING 5 1 Wiring For Outdoor Unit 5 2 Wiring For Indoor Unit 6 FINAL CHECK AND...

Page 4: ...oking device Exposure to this gas could cause severe injury or death Disconnect from power source before attempting any electrical work Connect the connective cable correctly Wrongly connecting may result damaged electric parts Use the specified cables for electrical connections and attach the wires firmly to the terminal block connecting sections so that the external force is not exerted to the t...

Page 5: ...ge Do not instal the air conditioner in the following places The place where there is mineral oil or arsenic acid The place where corrosive gas such as sulfurous acid gas or combustible gas such as thinner can accumulate or collect or where volatile combustible substances are handled The place there is equipment that generates electromagnetic fields or high frequencey harmonics This productcontain...

Page 6: ... 09 09 02 09 12 12 09 09 08 09 12 18 Four Indoors 09 18 18 12 12 12 12 18 18 12 12 18 09 09 09 09 09 09 09 12 09 09 09 18 09 09 12 12 09 09 12 18 09 12 12 12 09 12 12 18 12 12 12 12 Total capacity of indoors should be less than 130 of capacity of outdoor When capacity of indoor combination is higher than capacity of outdoor performance may reduce if all indoors are working simultaneously CAUTION 1...

Page 7: ...accessories please refer to attached manual of wired controller The following accessories are related to remote controller 2 1 2 Installation site choosing Where it is out of direct sunlight Where the airflow is not blocked Where an optimum air distribution is ensured Where the condensate can drain correctly and safely Install the indoor unit on a wall ceiling that prevents vibration and is strong...

Page 8: ...htly tilted towards the outsides 2 1 4 Drill hole in the wall Indoor Outdoor The drain line must not have a trap anywhere in its length must pitch downwards and must be insulated up to the outside wall 2 1 5 Drainage Bend S shape Drain end into water O X X X The position of drain pipe interface can be selected according to installation position During the adjustment of drain hose the unused interf...

Page 9: ...controller manual The following accessories are related to remote controller Inspection Opening 600mmX600mm 300mm or more 200mm or more Seal sponge For changing of air intake direction 2 INDOOR UNIT INSTALLATION 2 2 DUCT TYPE INDOOR 2 2 1 Accessories 2 2 2 Installation site choosing Where it is out of direct sunlight Where the airflow is not blocked Where an optimum air distribution is ensured Whe...

Page 10: ...ing The size of descensional ventilation opening The size of mounted lug Unit mm T M P N O Air outlet opening size Air return opening size Size of mounted hook New air inlet Outline dimension 920 210 635 570 65 713 35 119 815 200 80 960 350 A B C D E F G H I J K L M 18 N O 26 20 26 20 700 210 635 570 65 493 35 119 595 200 80 740 350 09 12 1010 790 P Φ90 Φ90 T Model 2 INDOOR UNIT INSTALLATION ...

Page 11: ...ur sides It is recommended to install the Y joint before installing the indoor unit When moving the unit during or after unpacking make sure to lift by holding its hooks Do not exert any pressure on other parts especially the refrigerant piping drain piping and flange parts CAUTION 2 2 4 Hanging the indoor unit 2 2 4 1 Screw double nuts to each suspension bolts making space for hanging the indoor ...

Page 12: ... or more and fix it by hanger space of 1 0 1 5m The flexible hose should not be installed upward position it may cause water flow back to the indoor unit Lean over 1 100 200mm 1 0 1 5m Max 550mm 2 2 5 2 Drainage test Unit without Pump Conduct the drainage test before making the duct connection Gradually insert about 2 liters of water into the drain pan indoor unit with stow tube Check and confirm ...

Page 13: ...ngineer to increase the fan speed to increase the static pressure corresponding to external resistance Unit with Pump Open the cover of water supply intake by turning and pulling the cover Gradually insert about 2 liters of water into the indoor unit with stow tube Operate the unit under COOLING mode and check a drain pump pumping a time lag of 1 minute is allowed before water flowing out dependin...

Page 14: ...ttach the air filter to the flange in the manner shown in the diagram Flange Ventilation panel Seal sponge 2 2 7 Change the air ventilation direction Alternative Rear or Bottom NOTE For standard unit air intakes from rear side Air intake direction can be modify at site from rear side to bottom side following the process in below 2 2 8 Install fresh air duct All the indoor units reserve the hole to...

Page 15: ...ired controller The following accessories are related to remote controller Separate packed parts Name of Accessories Q ty pc 1 Shape Use Panel 2 3 2 Installation site choosing Where it is out of direct sunlight Where the airflow is not blocked Where an optimum air distribution is ensured Where the condensate can drain correctly and safely Install the indoor unit on a wall ceiling that prevents vib...

Page 16: ...arance from the wall or other obstacles Connecting port of refrigerant pipe Connecting port of drain pipe Connecting port of drain pipe Connecting port of refrigerant pipe 523 Hook location 570 Body 647 Panel 545 Hook location 570 Body 647 Panel 600mm Ceiling hole 290mm 260mm Fresh air intake Ø 65 106 106 75 65 ...

Page 17: ... 2 3 4 4 Adjust level of the unit by using level vial to make sure horizontal level of the main body within 1 It is recommended to install the Y joint before installing the indoor unit When moving the unit during or after unpacking make sure to lift by holding its hooks Do not exert any pressure on other parts especially the refrigerant piping and drain piping CAUTION 2 3 4 Hanging the indoor unit...

Page 18: ... 750mm 200mm 2 3 5 2 Drainage test Connect the drainage test during trial operation Operate the unit under COOLING mode and check a drain pump pumping a time lag of 1 minute is allowed before water flowing out depending on the length of the drain pipe Check and confirm the water flows out through the drain hose Check the drain water drops at the end of the drain pipe Make sure there is no water le...

Page 19: ...switches simultaneously then lift the grille up and remove the air inlet grille 2 3 6 2 Install the panel Align the mark on the panel with the same mark on the main body Fix the panel to the main body with the 4 screws Tighten the screw evenly to make sure there is no gap between the main body and panel and the edge of panel should contact the ceiling well Connect the wire of swing motor to the co...

Page 20: ...essories please refer to attached manual of wired controller The following accessories are related to remote controller 2 4 2 Installation site choosing Where it is out of direct sunlight Where the airflow is not blocked Where an optimum air distribution is ensured Where the condensate can drain correctly and safely Install the indoor unit on a wall ceiling that prevents vibration and is strong en...

Page 21: ... 100mm 100mm 1000mm SPACE REQUIREMENT FOR INDOOR UNIT The size of Outline dimension Unit mm 2 INDOOR UNIT INSTALLATION 195mm Hook 700mm 210mm 600mm Confirm that there is enough room for installation and maintenance ...

Page 22: ...the pipes and wires 2 4 4 1 Push the two switches simultaneously then open the panel 2 4 4 2 Remove the string and take off the panel The unit must be installed vertically CAUTION 195mm Hook Tapping screw Washer 6mm 2 4 3 2 Hang the indoor unit on the hook There should be no gap between unit and the ground No gap between unit and the ground ...

Page 23: ...ke off the frame Drain hose connection port Piping connection port 2 4 4 4 Remove the installation bearer and take off control box cover Wiring terminator can be observed Installation bearer Control box cover 2 4 5 Install the drain pipe Bend S shape The drain line must not have a trap anywhere in its length must pitch downwards and must be insulated up to the outside wall O X X ...

Page 24: ...tdoor unit in areas where it can be covered by snow If heavy snow is expected a field supplied ice or stand and field supplied installed wind baffle should be installed to protect the unit from snow accumulation and blocked air intake When installing the outdoor unit in a place that is constantly exposed to a strong wind it is recommended that a wind baffle be used X O Strong wind 3 3 OUTDOOR UNIT...

Page 25: ...the fixing leg that is in contact with the bottom plate of the outdoor unit 3 5 INSTALL THE OUTDOOR UNIT 100mm 100 300mm Outdoor unit Vibration proof rubber Anchor bolt M10 Drainage Wide 100mm x Depth 150mm Mortar Hole Φ100mm x Depth 150mm 200 50 300 300 30 60 200 30 Parallel connect the two units or above Parallel connect the front with rear sides Connect the drain outlet with an extension drain ...

Page 26: ...torque will cause flare damage or gas leaks CAUTION Torque Tubing size 18 20 N m 25 26 N m 35 36 N m 6 35mm Ø 9 52mm Ø 12 7mm Use separate thermal insulation pipes for gas liquid pipes The thickness above is a standard of the indoor temperature of 27 C and humidity of 80 If installing in an unfavorable conditions such as near bathrooms kitchens and other similar locations reinforce the insulation ...

Page 27: ... charge hose from the manifold gauge to the service port of the gas side packed valve Connect the charge hose to the port of the vacuum pump Fully open the handle Lo of manifold gauge Operate the vacuum pump to evacuate air from the system until 76cmHg Close the handle Lo of manifold gauge Repeat above steps for each system indoors Fully open the valve stem of the packed valves Remove the charging...

Page 28: ... be installed the capacity should be above 1 5 times of maximum current in circuit An individual branch circuit and single socket used only for this appliance must be available Wire cross section is depending on the rated current and national state and local electrical wiring code Consult local building codes and National electrical code for special requirement If the supply cord is damaged it mus...

Page 29: ...r C POWER SUPPLY To Indoor A To Indoor B Clamp Filter Clamp to indoor outdoor connecting wire Field supply 60mm 40mm 10mm Power input cord GND Connective Cable 60mm 40mm 10mm GND L L A N N A N B S A L B S B L C N C S C L N S Indoor D To Indoor D N D L D S D L N S Indoor A L N S Indoor B To Indoor C Make sure that the indoor unit A B connects to the valves and signal wire terminal A B of outdoor un...

Page 30: ...18 To outdoor Duct QSM012 18 Cassette QTD009 Console 09 18 S 1 L 2 N To outdoor W To Outdoor 1 L 2 N S W Cassette QTD012 18 To Outdoor L N S L N S To Outdoor L 1 1 2 N S To outdoor Wall mounted HVF 09 18 Duct QSM009 SVM 09 18 S N To outdoor L L N S To outdoor Cassette CVS 09 18 ...

Page 31: ...ature is adjusted well Whether the indicator lights on the display panel are normal Whether the manual button works well Whether the drainage is normal Whether there is a vibration or abnormal noise during the operation Whether the indoor unit works well in COOLING or HEATING mode Outdoor unit Whether there is a vibration or abnormal noise during the operation Whether the wind noise or condensed g...

Page 32: ...BEIJER RET AB Stortorget 8 Malmö Sweden ...