11 High temperature protection of compressor top diagnosis and solution (P2)
Error Code
P2
Malfunction decision
conditions
If the sampling voltage is not 5V, the LED will display the failure.
Supposed causes
●
Power supply problems.
●
System leakage or block
●
PCB faulty
Check the air flow system
of indoor and outdoor units
Clear up the air inlet and outlet or the heat
exchanger of indoor and outdoor units.
Yes
No
Yes
Yes
Power off, then restart the unit 10
minutes later
Check if the temperature
of compressor
No
Check refrigerant system
Yes
Check the overload
protector
Correct the connection.
No
Measure the resistance
between the two ports of
the OLP. Is it zero?
Yes
Replace the OLP.
No
Replace the outdoor control PCB.
Yes
Summary of Contents for 38QUS012DS
Page 1: ...SERVICE MANUAL 12 18 24K LIGHT COMMERCIAL ...
Page 5: ...2 PRODUCT LINEUP ...
Page 6: ...3 UNIT MODEL INDENTIFICATION ...
Page 7: ...PART 1 GENERAL INFORMATION 1 1 DUCT ...
Page 9: ...2 INSTALLTION SPACE ...
Page 10: ...3 STATIC PRESSURE ...
Page 11: ...4 STATIC PRESSURE 42QSM012DS ...
Page 12: ...5 STATIC PRESSURE 42QSM018DS ...
Page 13: ...6 STATIC PRESSURE 42QSM024DS ...
Page 18: ...11 5 Screw off the fixing screws to remove the evaporator 1 screw ...
Page 19: ...PART 1 GENERAL INFORMATION 1 2 CASEETTE ...
Page 22: ...3 INSTALLTION SPACE ...
Page 29: ...PART 1 GENERAL INFORMATION 1 3 UNDER CEILING ...
Page 31: ...3 INSTALLTION SPACE ...
Page 37: ...PART 1 GENERAL INFORMATION 1 4 OUTDOOR UNIT ...
Page 44: ...8 compressor on bottom plate 4 Lift the compressor from the base pan assembly ...
Page 45: ...PART 2 ELECTRICAL DIAGRAM ...
Page 46: ...1 WIRING DIAGRAM 42QSM012 18 24DS ...
Page 47: ...2 WIRING DIAGRAM 42QTD012 18DS ...
Page 48: ...3 WIRING DIAGRAM 42QTD024DS ...
Page 49: ...4 WIRING DIAGRAM 42QZL018 24DS ...
Page 50: ...5 WIRING DIAGRAM 38QUS012DS ...
Page 51: ...6 WIRING DIAGRAM 38QUS018DS ...
Page 52: ...7 WIRING DIAGRAM 38QUS024DS ...
Page 53: ...PART 3 TROUBLE SHOOTING ...