10 Over voltage or too low voltage protection diagnosis and solution (P1)
Error Code
P1
Malfunction decision
conditions
An abnormal voltage rise or drop is detected by checking the
specified voltage detection circuit.
Supposed causes
●
Power supply problems.
●
System leakage or block
●
PCB faulty
Check the power supply
Check the connections and
wires
Stop the unit
No
Yes
No
Correct the connections or
replace the wires.
Yes
Replace the reactor
Yes
No
Replace the IPM board
Check the voltage between P
and N
Check the reactor
Yes
No
Replace outdoor main PCB
Remark:
Measure the DC voltage
between P and N port. The
normal value should be
around 310V.
Summary of Contents for 38QUS012DS
Page 1: ...SERVICE MANUAL 12 18 24K LIGHT COMMERCIAL ...
Page 5: ...2 PRODUCT LINEUP ...
Page 6: ...3 UNIT MODEL INDENTIFICATION ...
Page 7: ...PART 1 GENERAL INFORMATION 1 1 DUCT ...
Page 9: ...2 INSTALLTION SPACE ...
Page 10: ...3 STATIC PRESSURE ...
Page 11: ...4 STATIC PRESSURE 42QSM012DS ...
Page 12: ...5 STATIC PRESSURE 42QSM018DS ...
Page 13: ...6 STATIC PRESSURE 42QSM024DS ...
Page 18: ...11 5 Screw off the fixing screws to remove the evaporator 1 screw ...
Page 19: ...PART 1 GENERAL INFORMATION 1 2 CASEETTE ...
Page 22: ...3 INSTALLTION SPACE ...
Page 29: ...PART 1 GENERAL INFORMATION 1 3 UNDER CEILING ...
Page 31: ...3 INSTALLTION SPACE ...
Page 37: ...PART 1 GENERAL INFORMATION 1 4 OUTDOOR UNIT ...
Page 44: ...8 compressor on bottom plate 4 Lift the compressor from the base pan assembly ...
Page 45: ...PART 2 ELECTRICAL DIAGRAM ...
Page 46: ...1 WIRING DIAGRAM 42QSM012 18 24DS ...
Page 47: ...2 WIRING DIAGRAM 42QTD012 18DS ...
Page 48: ...3 WIRING DIAGRAM 42QTD024DS ...
Page 49: ...4 WIRING DIAGRAM 42QZL018 24DS ...
Page 50: ...5 WIRING DIAGRAM 38QUS012DS ...
Page 51: ...6 WIRING DIAGRAM 38QUS018DS ...
Page 52: ...7 WIRING DIAGRAM 38QUS024DS ...
Page 53: ...PART 3 TROUBLE SHOOTING ...