background image

CHECK ACCURATER® METERING DEVICE — The cor-
rect AccuRater (bypass type) refrigerant control is required
for system capacity optimization. An AccuRater device with
field-replaceable piston (see Fig. 4) is supplied on indoor coil
and at service valve of outdoor unit. Refer to the AccuRater
metering device table in separate indoor unit installation in-
structions to determine the correct AccuRater piston size re-
quired for the heat pump/indoor unit system being installed.

Note that one of 2 types of AccuRater controls can be found

on the indoor unit, and that Type B AccuRater devices are
used on 38QR018C-060C heat pumps. Do not interchange
components between the AccuRater device types. Matching
of heat pump with indoor unit may require field replacement
of piston. Replace pistons, if required, before connecting re-
frigerant lines. Piston replacement instructions are included
in separate indoor unit installation instructions. After system
installation is complete, see Refrigerant Charging section on
page 10 to check and/or adjust refrigerant charge.

Step 2 — Rig and Mount Unit

MOUNTING ON GROUND — Mount unit on a solid, level
concrete pad. Position unit so water or ice from roof does
not fall directly onto unit. Use accessory snow rack (part no.
38QR900001 or -011) or ice stand (part no. 38QR900021 or
-031) (see Fig. 2, 3) where prolonged subfreezing tempera-
tures or heavy snow occurs. Refer to separate installation
instructions packaged with the accessories. If conditions or
local codes require unit be fastened to pad, 6 field-supplied
tiedown bolts should be used and fastened through slots pro-
vided in unit mounting feet.

MOUNTING ON ROOF — Mount unit on a level platform
or frame at least 6 in. above roof surface. Isolate unit and
tubing from structure.

RIGGING

Be sure unit panels are securely in place prior to
rigging.

Keep unit upright. Lift unit using sling. Use cardboard or

padding under sling, and spreader bars to prevent sling dam-
age to unit. See Fig. 5. See Fig. 2 and 3 for center of gravity
reference. Install unit so that coil does not face into prevail-
ing winds. If this is not possible and constant winds above
25 mph are expected, use Accessory Wind Baffle (part no.
38QR900041 or -051). See installation instructions pro-
vided with accessory kit.

Step 3 — Complete Refrigerant Piping Connec-
tions —

Outdoor units may be connected to indoor units

using field-supplied tubing of refrigerant grade and condi-
tion. See Table 1 for correct line sizes. Do not use less than
10 ft of interconnecting tubing.

DO NOT BURY MORE THAN 36 IN. OF REFRIG-
ERANT PIPE IN THE GROUND. If any section of pipe
is buried, there must be a 6-in. vertical rise to the valve
connections on the outdoor unit. If more than the rec-
ommended length is buried, refrigerant may migrate to
cooler, buried section during extended periods of sys-
tem shutdown. This causes refrigerant slugging and could
possibly damage compressor at start-up.

When more than 50 ft of interconnecting tubing and more

than 30 ft of vertical lift is used, refer to Part 3 of Carrier
System Design Manual for design details, or contact your
local distributor.

TYPE A

NOTE: Arrow on AccuRater body points in

free flow

direction, away

from the indoor coil.

TYPE B

Fig. 4 — AccuRater® (Bypass Type) Metering De-

vice Components

Fig. 5 — Lifting Unit With Sling

4

Summary of Contents for 38QR018C-060C

Page 1: ...gloves Use quenching cloth for brazing operations Have fire ex tinguisher available Read these instructions thoroughly Con sult local building codes and National Electrical Code NEC for special insta...

Page 2: ...6C 3 7 sq ft 34 m2 5 Do not use screws longer than 1 2 in 13 mm near return air opening UNIT WEIGHT LB KG DIMENSIONS in mm A B C 38QR018C 154 70 13 329 5 8 15 88 3 8 9 53 38QR024C 167 76 38QR030C 180...

Page 3: ...longer than 1 2 in 13 mm near return air opening UNIT WEIGHT LB KG DIMENSIONS in mm A B C 38QR036C 249 113 13 11 16 28 97 7 8 22 22 3 8 9 53 38QR048C 252 114 1311 16 28 97 7 8 22 22 3 8 9 53 38QR060C...

Page 4: ...s should be used and fastened through slots pro vided in unit mounting feet MOUNTING ON ROOF Mount unit on a level platform or frame at least 6 in above roof surface Isolate unit and tubing from struc...

Page 5: ...through piping while brazing to prevent formation of copper oxide To avoid damage while brazing service valves should be wrapped with a heat sinking material such as a wet cloth When brazing tubing s...

Page 6: ...unit in system where voltage may fluctuate above or below permissible limits See Table 2 for recommended fuse sizes When making electrical connections provide clearance at unit for refrig erant pipin...

Page 7: ...meter or continuity tester If necessary refer to Carrier Stand ard System Techniques Manual Chapter 2 for complete information Pumpdown Procedure The system may be pumped down in order to make repairs...

Page 8: ...opens DO NOT attempt to simulate the system abnormalities high pressures pose a serious safety hazard High pressure switch is also checked with an ohmmeter similar to checking low pressure switch If...

Page 9: ...pts the nor mal system heating operation to defrost the outdoor coil if the coil saturated suction temperature indicates freezing temperatures Defrost control board can be field set to check need for...

Page 10: ...wet bulb temperature with a sling psychrometer 6 Refer to Table 3 Find air temperature entering outdoor coil and wet bulb temperature entering indoor coil At this intersection note the superheat temp...

Page 11: ...of Table 5 Heating Operation Pressure Table Fixed Restrictor High Pressure at Suction Valve Low Pressure at Liquid Valve Suction Pressure at Compressor UNIT 38QR INDOOR DRY BULB TEMP F OUTDOOR TEMPERA...

Page 12: ...HOOTING CHART HEATING CYCLE LEGEND NC Normally Closed ODT Outdoor Thermostat NOTE For systems with indoor units equipped with microprocessor control see separate controls service and troubleshooting m...

Page 13: ...TROUBLESHOOTING CHART COOLING CYCLE LEGEND NC Normally Closed NOTE For systems with indoor units equipped with microprocessor control see separate controls service and troubleshooting manual 13...

Page 14: ......

Page 15: ......

Page 16: ...acturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab 5a 5a PC 111 Catalog No 563 882 Printed in U S A...

Reviews: