background image

Step 4 — Make Electrical Connections

Unit cabinet must have an uninterrupted, unbroken elec-
trical ground to minimize the possibility of personal in-
jury if an electrical fault should occur. This ground may
consist of electrical wire connected to unit ground lug
in control compartment, or conduit approved for elec-
trical ground when installed in accordance with NEC,
ANSI/NFPA (American National Standards Institute/
National Fire Protection Association) 70-1987 and lo-
cal electrical codes. Failure to follow this warning could
result in the installer being liable for personal injury of
others.

Unit failure as a result of operation on improper line
voltage or excessive phase imbalance constitutes abuse
and may cause damage to electrical components. Such
operation would invalidate any applicable Carrier
warranty.

POWER WIRING — Unit is factory wired for voltage shown
on nameplate. Provide adequate fused disconnect switch within
sight from unit, readily accessible, but out of reach of chil-
dren. Provision for locking switch open (off) is advisable to
prevent power from being turned on while unit is being ser-
viced. Disconnect switch, fuses, and field wiring must com-
ply with NEC and local code requirements. Use copper wire
only between disconnect switch and unit. Use minimum
60 C wire for field power connection.

Route power wires through opening in unit side panel and

connect in unit control box as shown on unit label diagram
and Fig. 6 and 7. Unit must be grounded.

CONTROL CIRCUIT WIRING — Control voltage is 24 v
(40 va minimum). See Fig. 7 and unit label diagram for field-
supplied wiring details. Route control wires through open-
ing in unit side panel to connection in unit control box.

NOTE: For wire runs up to 50 ft, use no. 18 AWG (Ameri-
can Wire Gage) insulated wire (35 C minimum) For 50 to
75 ft, use no. 16 AWG insulated wire (35 C minimum). For
over 75 ft, use 14 AWG insulated wire (35 C minimum).

NOTE: Operation of unit on improper line voltage consti-
tutes abuse and could affect Carrier warranty. See Table 2.
Do not install unit in system where voltage may fluctuate
above or below permissible limits.

See Table 2 for recommended fuse sizes. When making

electrical connections, provide clearance at unit for refrig-
erant piping connections.

Use indoor unit transformer as 24-v (40-va minimum) sup-

ply for system or use accessory transformer.

Before performing service or maintenance, be sure in-
door unit main power switch is turned OFF and indoor
blower has stopped. Failure to do so may result in elec-
trical shock, or injury from rotating fan blades.

START-UP

Preliminary Checks

1. Check that all internal wiring connections are tight and

that all barriers, covers, and panels are in place.

2. Field electrical power source must agree with unit name-

plate rating.

3. All service valves must be open.
4. Belly-band crankcase heater must be tight on compressor

crankcase for those units with belly-band heaters.

Leak Test —

Field piping and fan coil must be leak tested

by pressure method described in Carrier Standard Service
Techniques Manual, Chapter 1, Section 1-6. Use R-22 at ap-
proximately 25 psig backed up with an inert gas to a total
pressure not to exceed 245 psig.

Before starting unit, crankcase heater must be on for

12 hours to be sure all refrigerant is out of the oil.

To energize crankcase heater, set space thermostat above

ambient temperature so there will be no demand for cooling.
Close field disconnect. The crankcase heater is now
energized.

Evacuate and Dehydrate —

Field piping and fan coil

must be evacuated and dehydrated by either of the methods
described in Carrier Standard Service Techniques Manual,
Chapter 1, Section 1-7.

Service valves must be fully backseated to close service
port. There is no Schrader valve at the service port, and
failure to backseat the valve could result in loss of sys-
tem charge or personal injury.

Charge System —

Release holding charge into system

by opening (backseating) liquid and suction line service valves.
Add charge amount as required for the total system. Refer to
indoor unit installation instructions for the required total sys-
tem charge, when connected by 25 ft of tubing.

LEGEND

NEC — National Electrical Code
TB

— Terminal Board

TB Connections
Field Wiring
Factory Wiring

Fig. 6 — Line Power Connections

6

Summary of Contents for 38QR018C-060C

Page 1: ...gloves Use quenching cloth for brazing operations Have fire ex tinguisher available Read these instructions thoroughly Con sult local building codes and National Electrical Code NEC for special insta...

Page 2: ...6C 3 7 sq ft 34 m2 5 Do not use screws longer than 1 2 in 13 mm near return air opening UNIT WEIGHT LB KG DIMENSIONS in mm A B C 38QR018C 154 70 13 329 5 8 15 88 3 8 9 53 38QR024C 167 76 38QR030C 180...

Page 3: ...longer than 1 2 in 13 mm near return air opening UNIT WEIGHT LB KG DIMENSIONS in mm A B C 38QR036C 249 113 13 11 16 28 97 7 8 22 22 3 8 9 53 38QR048C 252 114 1311 16 28 97 7 8 22 22 3 8 9 53 38QR060C...

Page 4: ...s should be used and fastened through slots pro vided in unit mounting feet MOUNTING ON ROOF Mount unit on a level platform or frame at least 6 in above roof surface Isolate unit and tubing from struc...

Page 5: ...through piping while brazing to prevent formation of copper oxide To avoid damage while brazing service valves should be wrapped with a heat sinking material such as a wet cloth When brazing tubing s...

Page 6: ...unit in system where voltage may fluctuate above or below permissible limits See Table 2 for recommended fuse sizes When making electrical connections provide clearance at unit for refrig erant pipin...

Page 7: ...meter or continuity tester If necessary refer to Carrier Stand ard System Techniques Manual Chapter 2 for complete information Pumpdown Procedure The system may be pumped down in order to make repairs...

Page 8: ...opens DO NOT attempt to simulate the system abnormalities high pressures pose a serious safety hazard High pressure switch is also checked with an ohmmeter similar to checking low pressure switch If...

Page 9: ...pts the nor mal system heating operation to defrost the outdoor coil if the coil saturated suction temperature indicates freezing temperatures Defrost control board can be field set to check need for...

Page 10: ...wet bulb temperature with a sling psychrometer 6 Refer to Table 3 Find air temperature entering outdoor coil and wet bulb temperature entering indoor coil At this intersection note the superheat temp...

Page 11: ...of Table 5 Heating Operation Pressure Table Fixed Restrictor High Pressure at Suction Valve Low Pressure at Liquid Valve Suction Pressure at Compressor UNIT 38QR INDOOR DRY BULB TEMP F OUTDOOR TEMPERA...

Page 12: ...HOOTING CHART HEATING CYCLE LEGEND NC Normally Closed ODT Outdoor Thermostat NOTE For systems with indoor units equipped with microprocessor control see separate controls service and troubleshooting m...

Page 13: ...TROUBLESHOOTING CHART COOLING CYCLE LEGEND NC Normally Closed NOTE For systems with indoor units equipped with microprocessor control see separate controls service and troubleshooting manual 13...

Page 14: ......

Page 15: ......

Page 16: ...acturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab 5a 5a PC 111 Catalog No 563 882 Printed in U S A...

Reviews: