![Carrier 38QPCT18C-708 Installation Manual Download Page 44](http://html1.mh-extra.com/html/carrier/38qpct18c-708/38qpct18c-708_installation-manual_2560775044.webp)
42
CONNECTING ELECTRICAL WIRING (Cont.)
18-3 ELECTRICAL DATA
Split
System
Model
Starting
Current
(Note 1)
Nominal
System
Power
Supply
Electrical Consumption
Circuit
Breaker
Cooling
Heating
****
35 °C
*
46 °C
**
52 °C
***
Heat Pump
Amp V/1Ph/50Hz Amp
Watt
Amp
Watt
Amp
Watt
Amp
Watt
Amp
53QPCT18H
58 220-240 8.5
1842 9.9 2205 10.7 2407 8.1 1735 20
53QPCT24H
65 220-240
11.7
2435 14.2 2975 15.4 3321 11.8 2494 25
Cool Only
Amp V/1Ph/50Hz Amp
Watt
Amp
Watt
Amp
Watt
Amp
Watt
Amp
53QPCT18C
52 220-240 8.7
1820 10.8 2323 11.6 2546
20
53QPCT24C
65 220-240
11.7
2436 14.3 2998 15.5 3308
25
NOTES
1. Starting Current duration is usually less than 1 Second.
2. Operating Conditions.
* @ 35ºC db outdoor temperature :
27/19ºC db/wb Indoor Temperature. High air flow of indoor unit
** @ 46ºC db outdoor temperature :
29/19ºC db/wb Indoor Temperature. High air flow of indoor unit
*** @ 52ºC db outdoor temperature :
32/23ºC db/wb Indoor Temperature. High air flow of indoor unit
**** Standard operating conditions for heating
Indoor 20 °C DBT Outdoor 7/6 °C DBT/WBT High speed of indoor unit
Summary of Contents for 38QPCT18C-708