background image

A

90

Refrigerant Piping Connection

Tightening connection

Align the centers of the connecting pipes and tighten the fl are nut as far as 
possible with your fi ngers. Then tighten the nut with a spanner and torque 
wrench as shown in the fi gure.

(Unit : N·m)

Outer dia. of copper pipe 

Tightening torque

’

6.35 mm

16 to 18 (1.6 to 1.8 kgf·m)

’

12.70 mm

50 to 62 (5.0 to 6.2 kgf·m)

Tightening torque for connection of fl are pipe

  The pressure of R410A is higher than 

R22. (Approx. 1.6 times.) Therefore 
securely tighten the fl are pipes which 
connect the outdoor unit and the indoor 
unit with the specifi ed tightening torque 
using a torque wrench. If any fl are pipe 
is incorrectly connected, it may cause 
not only a gas leakage but also trouble 
in the refrigeration cycle.

Flaring

1. Cut the pipe with a pipe cutter.

Obliquity

Roughness

Warp

Half uniont

Flare nut

Pipe

Die

Use a wrench to secure.

Use a torque wrench to tighten.

2. Insert a fl are nut into the pipe and fl are the pipe.

Projection margin in fl aring : A (Unit : mm)

Outer dia.

of copper pipe

A

Rigid

Imperial

’

6.35

1.0 to 1.5

1.5 to 2.0

’

12.70

1.0 to 1.5

2.0 to 2.5

CAUTION

Do not apply excess torque. Otherwise, the nut may crack depending on 
the conditions.

Internally
threaded side

Externally
threaded side

CAUTION

KEEP IMPORTANT 5 POINTS FOR PIPING WORK.

(1) Take away dust and moisture (inside of the connecting pipes).
(2) Tighten the connections (between pipes and unit).
(3) Evacuate the air in the connecting pipes using a VACUUM PUMP.
(4) Check gas leak (connected points).
(5) Be sure to fully open the packed valves before operation.

After the piping has been connected to the indoor unit, you can perform the 
air purge together at once.

Using a vacuum pump

Be sure to use a vacuum pump with counter-fl ow prevention function so 
that inside oil of the pump does not fl ow backward into pipes of the air 
conditioner when the pump stops.

A

1. Connect the charge hose from the manifold valve to the service port of 

the packed valve at gas side.

2. Connect the charge hose to the port of the vacuum pump.
3. Open fully the low pressure side handle of the gauge manifold valve.
4. Operate the vacuum pump to start evacuating. Perform evacuating for 

about 15 minutes if the piping length is 20 meters. (15 minutes for 20 
meters) (assuming a pump capacity of 27 liters per minute) Then confi rm 
that the compound pressure gauge reading is –101 kPa (–76 cmHg).

5. Close the low pressure side valve handle of the gauge manifold valve.
6. Open fully the valve stem of the packed valves (both gas and liquid 

sides).

7. Remove the charging hose from the service port.
8. Securely tighten the caps on the packed valves.

Packed valve at liquid side

Vacuum

pump

Handle Lo

–101 kPa
(–76 cmHg)

Packed valve handling precautions

  Open the valve stem until it touches the stopper. Once it is in contact with 

the stopper, refrain from applying any more force than is necessary.

  Securely tighten the valve stem cap with torque in the following table:

Wiring Connection

1. Remove the valve cover, the electric parts cover and the cord clamp from 

the outdoor unit.

2. Connect the connecting cable to the terminal as identifi ed by the matching 

numbers on the terminal block of indoor and outdoor unit.

3. Insert the power cord and the connecting cable carefully into the terminal 

block and secure it tightly with screws.

4. Use vinyl tape, etc. to insulate the cords which are not to be used. 
    Locate them so that they do not touch any electrical or metal parts.
5. Secure the power cord and the connecting cable with the cord clamp.
6. Attach the electric parts cover and the valve cover on the outdoor unit.

Electrical Work

1. The supply voltage must be the same as the rated voltage of the air 

conditioner.

2. Prepare the power source for exclusive use with the air conditioner.

TO CHARGE REFRIGERANT

Refrigerant

18 Class

24 Class

Non refrigerant charging

Less than 15 m

Less than 15 m

Refrigerant charging

15 – 20 m (20g/m)

15 – 25 m (20g/m)

Hexagon wrench
is required.

Pipe side

Tightening torque

A

Gas side
(

’

12.70 mm)

50 to 62 N·m
(5.0 to 6.2 kgf·m)

4 mm

Liquide side
(

’

6.35 mm)

16 to 18 N·m
(1.6 to 1.8 kgf·m)

Same as

gas side

Service port

9 to 10 N·m
(0.9 to 1.0 kgf·m)

Vacuum pump adapter for
counter-fl ow prevention
(For  R410A only)

AIR PURGE

Evacuate the air in the connecting pipes and in the indoor unit using a 
vacuum pump. Do not use the refrigerant in the outdoor unit. For details, see 
the manual of the vacuum pump.

Service port (Valve core (Setting pin))

Charge hose
(For  R410A only)

Charge hose
(For  R410A only)

Manifold valve

Pressure gauge

Compound pressure gauge

Handle Hi
(Keep full closed)

Connecting pipe

Packed valve at gas side

Evacuating

Flare at
indoor unit side

Flare at
outdoor unit side

6

EN

ES

FR

IT

VT

PL

CZ

RU

CR

HU

TR

NL

GR

SV

FI

NO

DK

RO

BG

EE

LV

SK

SI

VT

1110651131 (01_EN).indd 7

1110651131 (01_EN).indd   7

2/2/09 11:15:11 AM

2/2/09   11:15:11 AM

Summary of Contents for 38NY018

Page 1: ...OMI NORSK DANSK ROM N EESTI LATVISKI SLOVEN INA SLOVEN INA ESPA OL FRAN AIS P C T RK E ENGLISH Indoor unit 42NQ018 024 Series Outdoor unit 38NY018 024 Series AIR CONDITIONER SPLIT TYPE INSTALLATION MA...

Page 2: ...s na Instala o em Regi es com Queda de Neve e Temperaturas Negativas 5 n Liga o das Condutas de Refrigera o 6 n Purga de Ar 6 n Liga es El ctricas 6 n Trabalhos de Electricidade 6 OUTROS 7 n Teste de...

Page 3: ...Instalare Op ionale 2 UNITATE INTERIOAR 3 n Locul de Instalare 3 n Executarea unei G uri i Montarea Pl cii de Instalare 3 n Racordarea Cablurilor 4 n Instalarea evilor i a Furtunului de Evacuare 4 n...

Page 4: ...HEAT SOURCES SUCH AS RADIATORS HEATERS FURNACE STOVES ETC WHEN MOVING THE AIR CONDITIONER FOR INSTALLING IT IN ANOTHER PLACE AGAIN BE VERY CAREFUL NOT TO GET THE SPECIFIED REFRIGERANT R410A WITH ANY O...

Page 5: ...get slack Make sure to run the drain hose sloped downward The auxiliary piping can be connected to the left rear left rear right right bottom right or bottom left Right Rear right Left Bottom right Re...

Page 6: ...the pipe hole is above the arrow Pipe hole In case of block brick concrete or similar type walls make 5 mm dia holes in the wall Insert clip anchors for appropriate mounting screws 7 Indoor unit Side...

Page 7: ...ipe is laid exceeding 43 mm above the wall surface the indoor unit may unstably be set on the wall When bending the connecting pipe make sure to use a spring bender so as not to crush the pipe Bend th...

Page 8: ...sion drain hose with shield pipe NOTE The hole should be made at a slight downward slant on the outdoor side CAUTION Arrange the drain pipe for proper drainage from the unit Improper drainage can resu...

Page 9: ...pressure gauge reading is 101 kPa 76 cmHg 5 Close the low pressure side valve handle of the gauge manifold valve 6 Open fully the valve stem of the packed valves both gas and liquid sides 7 Remove th...

Page 10: ...door units are installed in the separated rooms it is not necessary to change the selector switches Check the are nut connections valve stem cap connections and service port cap connection for gas lea...

Page 11: ...does not blink This product is designed so that after a power failure it can restart automatically in the same operating mode as before the power failure To switch the TEST RUN COOL mode press RESET b...

Reviews: