8
CLEARANCES − OUTDOOR
A
D
B
Air-outlet
Air-inlet
C
E
A07894
Fig. 5
-
Outdoor Unit Clearance
Table 5—Outdoor Unit Clearance Dimensions
UNIT
MINIMUM VALUE in. (mm)
A
24 (610)
B
24 (610)
C
24 (610)
D
4 (101)
E
4 (101)
NOTE: The outdoor unit must be mounted at least 2in. (50mm) above the maximum anticipated snow depth.