background image

13

START−UP

Test Operation

Perform a test operation after completing a gas leak and electrical
safety check. See the indoor unit installation instructions and
owner’s manual for additional start up information.

SYSTEM CHECKS

1. Conceal the tubing where possible.

2. Make sure that the drain tube slopes downward along its

entire length.

3. Ensure all tubing and connections are properly insulated.

4. Fasten the tubes to the outside wall, when possible.

5. Seal the hole through which the cables and tubing pass.

OUTDOOR UNIT

1. Are there unusual noises or vibrations during operation?

Explain the Following Items to the Customer (with the aid of
the Owner’s Manual):

1. Explain care and maintenance.

2. Present the installation instructions to the customer.

OUTDOOR UNIT DIAGNOSTIC GUIDES

For ease of service, the systems are equipped with a diagnostic code display LEDs on both the indoor and outdoor units. The outdoor
diagnostic is displayed on the outdoor unit microprocessor board.

There may be a few error codes displayed in the indoor unit that might relate to the outdoor unit’s problems. If possible, always check the
diagnostic codes displayed on the indoor unit first.

The diagnostic codes displayed on the outdoor units are listed on Table 10.

Table 10—Unit Diagnostic Guides

DISPLAY

LED STATUS

E1

Communication malfunction between indoor and outdoor units.

F0

Protection of over-current

F1

Open circuit or short circuit of outdoor ambient temperature sensor T4

F2

Open circuit or short circuit of condenser coil temperature sensor T3

F3

Open circuit or short circuit of Compressor discharge temperature sensor T5

F4

Outdoor unit EEPROM error

F5

Outdoor fan speed has been out of control

P0

IPM malfunction

P1

Over voltage or over low voltage protection

P2

High temperature protection of compressor top

P3

Outdoor low temperature protection

P4

Inverter compressor drive error

P7

Outdoor IGBT temperature sensor error

J0

High temperature protection of indoor coil in heating

J1

Outdoor temperature protection of outdoor coil in cooling

J2

Discharge temperature protection

J3

Protection of active PFC module

J4

Communication error between control board and IPM board

J5

High-pressure switch protection

J6

Low-pressure switch protection

J8

AC voltage protection

For additional diagnostic information, refer to the Service Manual.

Summary of Contents for 38MHR series

Page 1: ...ual before starting the installation TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS 2 PARTS LIST 3 SYSTEM REQUIREMENTS 4 DIMENSIONS OUTDOOR 5 CLEARANCES OUTDOOR 8 INSTALLATION TIPS 9 OUTDOOR UNIT INSTAL...

Page 2: ...hazards which will result in severe personal injury or death WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in...

Page 3: ...rips from the connection pipe before it enters the wall Piping and the interconnecting wiring are field supplied The illustration above is only a sketch Different models may be slightly different The...

Page 4: ...il connected Wiring All wires must be sized per NEC National Electrical Code or CEC Canadian Electrical Code and local codes Use the Electrical Data table MCA minimum circuit amps and MOCP maximum ove...

Page 5: ...88 6 40 2 Heat Pump System Size Height H in mm Width W in mm Depth D in mm Weight Net lbs kg 9K 115 21 85 555 30 31 770 11 81 300 61 5 27 9 12K 115V 21 85 555 30 31 770 11 81 300 65 0 29 5 9K 208 230V...

Page 6: ...800 20 24 514 21 81 554 2 36 6 0 3 37 8 5 5 13 39 340 0 47 1 2 12 24 311 12 80 325 13 11 333 2 76 7 0 H H1 H2 D1 D2 D3 2 43 6 1 8 4 17 1 06 0 87 2 2 R 0 79 R 20 R 0 24 R 6 2 43 6 1 6 D W W1 W2 B1 B2 A...

Page 7: ...7 DIMENSIONS OUTDOOR CONT Unit inch mm Fig 4 Size 24K...

Page 8: ...C E A07894 Fig 5 Outdoor Unit Clearance Table 5 Outdoor Unit Clearance Dimensions UNIT MINIMUM VALUE in mm A 24 610 B 24 610 C 24 610 D 4 101 E 4 101 NOTE The outdoor unit must be mounted at least 2i...

Page 9: ...ntaminants to avoid damaging the refrigerant system Avoid sags in the suction line to prevent the formation of oil traps Insulate each tube with a minimum 3 8 in 10 mm wall thermal pipe insulation Ins...

Page 10: ...malfunction A fire hazard may also exist Therefore ensure all wiring is tightly connected S No wire should be allowed to touch the refrigerant tubing compressor or any moving parts S Disconnecting mea...

Page 11: ...ble limits of the voltage range at which the unit will operate satisfactorily LEGEND FLA Full Load Amps MCA Minimum Circuit Amps MOCP Maximum Over Current Protection RLA Rated Load Amps CONNECTION DIA...

Page 12: ...acuum Method The deep vacuum method requires a vacuum pump capable of pulling a vacuum of 500 microns and a vacuum gage capable of accurately measuring this vacuum depth The deep vacuum method is the...

Page 13: ...r unit s problems If possible always check the diagnostic codes displayed on the indoor unit first The diagnostic codes displayed on the outdoor units are listed on Table 10 Table 10 Unit Diagnostic G...

Page 14: ...BDP S 7310 W Morris St S Indianapolis IN 46231 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No IM 38MHR 01 Replaces N...

Reviews: