background image

4

SYSTEM REQUIREMENTS

Allow sufficient space for airflow and service of the unit. See Fig. 5 for the required minimum distances between the unit, walls or ceilings.

Piping

IMPORTANTBoth refrigerant lines must be insulated separately.

S

  Table 3 contains piping information for the product covered within this document.

Table 3—Piping and Refrigerant Information

System Size

9K (115V)

12V (115V)

9K (208-230V)

12K (208-230V)

18 (208-230V)

24K (208-230V)

Piping

Min. Piping Length

ft. (m)

10(3)

10(3)

10(3)

10(3)

10(3)

10(3)

Standard Piping Length

ft. (m)

25(7.5)

25(7.5)

25(7.5)

25(7.5)

25(7.5)

25(7.5)

Max. outdoor-indoor
height difference (OU
higher than IU)

ft. (m)

33(10)

33(10)

33(10)

33(10)

33(10)

33(10)

Max. outdoor-indoor
height difference (IU higher
than OU)

ft. (m)

33(10)

33(10)

33(10)

33(10)

33(10)

33(10)

Max. Piping Length with
no additional refrigerant
charge per System
(Standard Piping length)

ft. (m)

25(7.5)

25(7.5)

25(7.5)

25(7.5)

25(7.5)

25(7.5)

Total Max. Piping
Length per system

ft. (m)

82(25)

82(25)

82(25)

82(25)

98(30)

164(50)

Additional refrigerant
charge (between Standard
– Max piping length)

Oz/ft

(g/m)

0.161(15)

0.161(15)

0.161(15)

0.161(15)

0.161(15)

0.322(30)

Suction Pipe
(size - connection type)

In (mm)

3/8(9.52)

1/2(12.7)

3/8(9.52)

1/2(12.7)

1/2(12.7)

5/8(15.9)

Liquid Pipe
(size - connection type)

In (mm)

1/4(6.35)

1/4(6.35)

1/4(6.35)

1/4(6.35)

1/4(6.35)

3/8(

9.52

)

Refrigerant Type

Type

R410A

R410A

R410A

R410A

R410A

R410A

Refrigerant

Cooling Only Models
Charge Amount

Lbs (kg)

1.06(0.48)

1.30(0.59)

1.06(0.48)

1.30(0.59)

2.09(0.95)

2.65(1.2)

Heat Pump Models
Charge Amount

Lbs (kg)

1.76(0.8)

2.12(0.96)

1.76(0.8)

2.12(0.96)

3.30(1.5)

3.968(1.8)

All outdoor units have an electronic expansion valve to manage the refrigerant flow of the fan coil connected.

Wiring

All wires must be sized per NEC (National Electrical Code) or
CEC (Canadian Electrical Code) and local codes. Use the Electrical
Data table MCA (minimum circuit amps) and MOCP (maximum
over current protection) to correctly size the wires and the
disconnect fuse or breakers respectively.

Per the caution note, only stranded copper conductors with a 600
volt rating and double insulated copper wire must be used. The use
of BX cable is not recommended.

Recommended Connection Method for Power and
Communication Wiring − Power and Communication Wiring:

The main power is supplied to the outdoor unit. The field supplied
14/3 power/communication wiring from the outdoor unit to the
indoor unit consists of four (4) wires and provides the power for
the indoor unit. Two wires are high voltage AC power, one is
communication wiring and the other is a ground wire.

Recommended Connection Method for Power and
Communication Wiring (To minimize communication wiring
interference) Power Wiring:

The main power is supplied to the outdoor unit. The field supplied
power wiring from the outdoor unit to the indoor unit consists of
three (3) wires and provides the power for the indoor unit. Two
wires are high voltage AC power and one is a ground wire. To
minimize voltage drop, the factory recommended wire size is 14/2
stranded with a ground.

Communication Wiring:

A separate shielded stranded copper conductor only, with a 600
volt rating and double insulated copper wire, must be used as the
communication wire from the outdoor unit to the indoor unit.
Please use a separate shielded 16GA stranded control wire.

CAUTION

!

EQUIPMENT DAMAGE HAZARD

Failure to follow this caution may result in equipment
damage or improper operation.

S

Wires should be sized based on NEC and local codes.

S

Use copper conductors only with a minimum 600 volt 
rating and double insulated copper wire.

Summary of Contents for 38MHR series

Page 1: ...ual before starting the installation TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS 2 PARTS LIST 3 SYSTEM REQUIREMENTS 4 DIMENSIONS OUTDOOR 5 CLEARANCES OUTDOOR 8 INSTALLATION TIPS 9 OUTDOOR UNIT INSTAL...

Page 2: ...hazards which will result in severe personal injury or death WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in...

Page 3: ...rips from the connection pipe before it enters the wall Piping and the interconnecting wiring are field supplied The illustration above is only a sketch Different models may be slightly different The...

Page 4: ...il connected Wiring All wires must be sized per NEC National Electrical Code or CEC Canadian Electrical Code and local codes Use the Electrical Data table MCA minimum circuit amps and MOCP maximum ove...

Page 5: ...88 6 40 2 Heat Pump System Size Height H in mm Width W in mm Depth D in mm Weight Net lbs kg 9K 115 21 85 555 30 31 770 11 81 300 61 5 27 9 12K 115V 21 85 555 30 31 770 11 81 300 65 0 29 5 9K 208 230V...

Page 6: ...800 20 24 514 21 81 554 2 36 6 0 3 37 8 5 5 13 39 340 0 47 1 2 12 24 311 12 80 325 13 11 333 2 76 7 0 H H1 H2 D1 D2 D3 2 43 6 1 8 4 17 1 06 0 87 2 2 R 0 79 R 20 R 0 24 R 6 2 43 6 1 6 D W W1 W2 B1 B2 A...

Page 7: ...7 DIMENSIONS OUTDOOR CONT Unit inch mm Fig 4 Size 24K...

Page 8: ...C E A07894 Fig 5 Outdoor Unit Clearance Table 5 Outdoor Unit Clearance Dimensions UNIT MINIMUM VALUE in mm A 24 610 B 24 610 C 24 610 D 4 101 E 4 101 NOTE The outdoor unit must be mounted at least 2i...

Page 9: ...ntaminants to avoid damaging the refrigerant system Avoid sags in the suction line to prevent the formation of oil traps Insulate each tube with a minimum 3 8 in 10 mm wall thermal pipe insulation Ins...

Page 10: ...malfunction A fire hazard may also exist Therefore ensure all wiring is tightly connected S No wire should be allowed to touch the refrigerant tubing compressor or any moving parts S Disconnecting mea...

Page 11: ...ble limits of the voltage range at which the unit will operate satisfactorily LEGEND FLA Full Load Amps MCA Minimum Circuit Amps MOCP Maximum Over Current Protection RLA Rated Load Amps CONNECTION DIA...

Page 12: ...acuum Method The deep vacuum method requires a vacuum pump capable of pulling a vacuum of 500 microns and a vacuum gage capable of accurately measuring this vacuum depth The deep vacuum method is the...

Page 13: ...r unit s problems If possible always check the diagnostic codes displayed on the indoor unit first The diagnostic codes displayed on the outdoor units are listed on Table 10 Table 10 Unit Diagnostic G...

Page 14: ...BDP S 7310 W Morris St S Indianapolis IN 46231 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No IM 38MHR 01 Replaces N...

Reviews: