Compressor Checking
Measure the resistance value of each winding by using the tester.
IPM Continuity Check
Turn off the power, let the large capacity electrolytic capacitors discharge completely, and dismount the IPM. Use a digital tester to measure the
resistance between P and UVWN; UVW and N.
POSITION
NOMINAL RESISTANCE VALUE
ATF310D43UMT
ATQ420D1UMU
Blue - Red
0.65
Ω
0.38
Ω
Blue - Black
Red - Blue
DIGITAL TESTER
NORMAL
RESISTANCE VALUE
DIGITAL TESTER
NORMAL RESISTANCE VALUE
(+)Red
(-)Black
∞
(Several M
Ω
)
(+)Red
(-)Black
∞
(Several M
Ω
)
P
N
U
N
U
V
V
W
W
(+)Red