34
Outdoor IPM Module Temperature Sensor Malfunction Diagnosis and Solution (P7)
Troubleshooting
Error Code
P7
Malfunction decision conditions
If the sampling voltage is lower than 0.06V or higher than 4.94V, the LED displays a failure.
Supposed Causes
• Faulty wiring
• Faulty sensor
ŚĞĐŬƚŚĞĐŽŶŶĞĐƟŽŶďĞƚǁĞĞŶƚŚĞ
temperature sensor and the PCB.
/ƐŝƚƉƌŽƉĞƌůLJǁŝƌĞĚ͍
Measure the sensor’s resistance value.
/ƐŝƚǁŝƚŚŝŶĂĐĐĞƉƚĂďůĞƉĂƌĂŵĞƚĞƌƐ͍
Yes
Yes
ŶƐƵƌĞĂƉƌŽƉĞƌĐŽŶŶĞĐƟŽŶ͘
No
Replace the sensor.
No
Replace the outdoor main PCB.