38GLP---G / 38GLP---G9 

GB - 10

• Make refrigerant connections before electrical

connections. When disconnecting, disconnect electrical
connections before refrigerant connections.

IMPORTANT:
Make ground connection prior to any other electrical
connections.

Note:
All field electrical connections are the responsibility of the
installer.

Refer to the indoor unit installation manual for sizing the
connection wires between units.

• Remove electric box cover.

• Make electrical connections between units prior to proceeding

to mains supply unit connection.

• Connect the wires to the terminals according to the wiring

diagram and firmly tighten.

Electrical connections

• For 230 V ~ 1 pH 50 Hz single-phase unit

Before proceeding with the unit connection to the mains supply
locate live L and neutral N, then make connections as shown
in the wiring diagram.

• For 400V 3N ~50 Hz three-phase unit

Before proceeding with the unit connection to the mains supply
locate live L1,L2,L3 and neutral N, then make connections as
shown in the wiring diagram.
When the electric supply cables L1 (R)L2 (S), L3 (T) are
connected inversely, a special “PSC” phase inversion protection
device blocks the compressor to prevent the same from rotating
inversely.
In this case, switch off the electrical supply and check the
correctness of the sequence of the cables of the supply line
connected to the main terminal block (they are probably
inverted).
The compressor will only be allowed to work if the phase
sequence is correct.
The phase sequence protection device also continuously
monitors the electrical supply line and if one of the phases is
completely missing it blocks the compressor.
The device only re-starts the compressor after the supply line is
correctly restored.
All the three phase compressors have identical internal wiring.
For this reason when the correct phase connections for a
specific system have been determined, the rotation direction will
always be correct if the same connections are made to the
terminal block (for the other equipment).

• Ensure that mains supply connection is made through a

switch that disconnects all poles, with contact gap of a least
3 mm.

• The mains supply connecting cable must be H07 RN-F type

(or higher), synthetic rubber insulation with neoprene coating,
according to EN 60335-2-40 codes.

Note:
After connections have been completed, replace electric box cover.

Notes:

1. Unit is suitable for outdoor installation.

2. Starting current duration is usually lower than 1 sec.

3. Wire size shown applies to line length up to 15 m.

4. If the indoor unit is provided with an electric heater, consult indoor unit installation manual for correct sizing of the wires.

5. Data referred to the outdoor unit only.

6. The mains supply connecting cable must be H07 RN-F type (or higher), synthetic rubber insulation with Neoprene coating, according to

EN 60335-2-40 codes.

Table IV: Electrical data

 (1)

Cooling only

A

A

W

A

W

A

W

A

W

A

mm

2

38GLP018G

40

9.3

2110

13.1

2560

---

---

---

---

20

2.5

38GLP024G

60

10.1

2300

15.1

3100

---

---

---

---

25

2.5

38GLP018G9

24

3.8

1950

4.4

2600

---

---

---

---

10

2.5

38GLP024G9

32

4.5

2270

5.3

3060

---

---

---

---

10

2.5

38GLP028G9

37

4.8

2900

5.5

3450

---

---

---

---

16

2.5

38GLP036G9

39

4.9

3100

6.4

3800

---

---

---

---

16

2.5

38GLP048G9

54

6.3

3300

7.5

3950

---

---

---

---

16

2.5

38GLP060G9

60

6.8

4580

9.2

5480

---

---

---

---

25

2.5

Starting

current

(2)

Heating

Cooling

Power input 

(5)

Main power

connections 

(6)

Time-delay

fuse

gL type

Wire size

(3-4)

Nominal conditions

230V  ~  50Hz

ISO 5151.2/T1

indoor 27

°

C d.b.  19

°

C w.b.

outdoor 35

°

C d.b.  24

°

C w.b.

Peak conditions

198V  ~  50Hz

ISO 5151.2/T1

indoor 32

°

C d.b.  23

°

C w.b.

outdoor 43

°

C d.b.  32

°

C w.b.

Nominal conditions

230V  ~  50Hz

ISO 5151.2/High+

indoor 20

°

C d.b.  15

°

C w.b.

outdoor 7

°

C d.b.   6

°

C w.b.

Peak conditions

198V  ~  50Hz

ISO 5151.2/High+

indoor 27

°

C

outdoor 24

°

C d.b.  18

°

C w.b.

Summary of Contents for 38GLP---G

Page 1: ...38GLP G 38GLP G9 INSTALLATION MANUAL L L O Y D S R E G I S TER QUALIT Y A S S U R A N C E IS O 900 1...

Page 2: ...igerant Use a commercial type metering device in the manifold hose in order to vaporize the liquid refrigerant before it enters in the unit LR 410A as other HFCs is only compatible with oils selected...

Page 3: ...60 Max height difference 30 m 40 m 40 m 50 m 50 m 50 m Max pipe length 10 m 15 m 25 m 30 m 30 m 30 m Table II Connections 3 1 2 Model Pipe diameter Pipe diameter Gas Liquid Gas Liquid mm inches 18 12...

Page 4: ...42VMC 40SMC 18 1200 8 15 Single phase 24 1525 8 15 150 18 1265 8 15 24 1265 8 15 80 150 Three phase 28 2100 8 25 100 36 2400 8 30 450 48 3300 8 30 60 3800 8 30 Mod 18 24 28 36 48 60 A mm 100 100 100...

Page 5: ...y code requirements have been followed for the mains supply circuit The mains supply must be connected to the outdoor unit Connect indoor and outdoor units with field supplied copper pipes by means of...

Page 6: ...get wet before connection Disconnecting the refrigerant connections after installation this will cause refrigerant leaks Connecting the condensate drain pipe to the outdoor unit Predominant head wind...

Page 7: ...e No dust No leak No mineral oil Neat Dry nitrogen brazing Vacuum Min 100 kPa 755 mmHg Charge liquid no gas Copper tubes during storage Use tools designed for R 410A higher pressure Keep inside clean...

Page 8: ...8 9 52 mm 3 8 42 12 70 mm 1 2 55 15 87 mm 3 8 65 19 05 mm 1 2 100 Flaring the ends of the tubing Remove protective caps from copper tube ends Position tube end downward cut the tube to the requested l...

Page 9: ...erature 21 C d b 15 C w b Mains power supply Nominal single phase voltage 230V 1pH 50Hz 38GLP G Operating voltage limits min 198V max 264V Mains power supply Nominal three phase voltage 400V 3N 50Hz 3...

Page 10: ...uit breaker see table IV Electrical data Terminal box legend all models Earth L Live power supply L1 Live power supply L2 Live power supply L3 Live power supply N Neutral power supply R Live connectio...

Page 11: ...pressors have identical internal wiring For this reason when the correct phase connections for a specific system have been determined the rotation direction will always be correct if the same connecti...

Page 12: ...t be carried out before disconnecting the refrigerant tubing in order to avoid refrigerant loss to the atmosphere if it becomes necessary to disconnect the refrigerant connections for unit repair remo...

Page 13: ...too small for actual air conditioning needs Unit selected at a too low indoor temperature cool only change selection Refrigerant charge low check and add refrigerant Outdoor unit fan faulty replace A...

Page 14: ...oling mode down to 15 C ambient temperature keeping the condensing pressure always close to 26 5 bar HIP With remote manual reset high pressure switch is brased betwen outdoor coil and expansion devic...

Page 15: ...start up or in case of re start after a stop of several hours at 10 C with low voltage supply 198V high pressure switch HIP may trip off the unit In this case reset the system by switching OFF and ON...

Page 16: ...L010126H11 0603 Via R Sanzio 9 20058 Villasanta MI Italy Tel 039 3636 1 The manufacturer reserves the right to change any product specifications without notice June 2003 Printed in Italy...

Reviews: