38GL_M…G / 38YY(S)_M…G
GB - 16
Electrical connections and electrical data
Remove electric box cover.
Connect the wires to the terminals according to the wiring diagram
and firmly tighten.
IMPORTANT:
Make ground connection prior to any other electrical
connections.
• Make electrical connections between units prior to proceeding to
mains supply unit connection.
• Before proceeding with the unit connection to the mains supply
locate live L and neutral N, then make connections as shown in
the wiring diagram.
• According to the installation instructions, the disconnecting
switches from the mains power supply should have a contact gap
(4 mm) such that total disconnection can be ensured under the
conditions provided for by overvoltage class III.
• The mains supply indoor unit – outdoor unit connecting cable
must be H07 RN-F (60245IEC66), type synthetic rubber insulation
with neoprene coating.
• Make certain the refrigerant pipes and the electrical
connection lines between the indoor unit and the outdoor
unit have the same colours and reference codes (A, A1, A2,
B, B1, B2) using the special adhesive references supplied.
Note:
All field electrical connections are the responsibility of the
installer.
Note:
After connections have been completed, replace electric box cover.
Notes: 1. Unit is suitable for outdoor installation.
2. Data referred to the outdoor unit only.
3. Starting current duration is usually lower than 1 sec.
4. The section of the cables refers to cables with a maximum length of 15 metres.
5. The mains supply indoor unit – outdoor unit connecting cable must be H07 RN-F (60245IEC66), type synthetic rubber insulation with
neoprene coating.
6. If the indoor unit is provided with an electric heater, consult indoor unit installation manual for correct sizing of the wires.
7. Electrical input refer to each one of the two mains supplies.
8. Circuit A1 - A2
9. Circuit B
Cooling only
A
A
W
A
W
A
W
A
W
A
mm
2
mm
2
38GL2M12G
30
6.6
1460
9.5
1850
---
---
---
---
16
2.5
1.0 1.0 1.0 1.0 ---
---
38GL2M18G
30
9.0
2040
11.7
2500
---
---
---
---
20
2.5
1.0 1.0 1.0 1.0 ---
---
38GL2M24G
30
10.9
2560
16.4
3250
---
---
---
---
25
2.5
1.0 1.0 1.0 1.0 ---
---
38GL3M21G
30
10.8
2450
16.3
3180
---
---
---
---
25
2.5
1.0 1.0 1.0 1.0 ---
---
(7)
30
5.8
1310
8.3
1600
---
---
---
---
16
2.5
1.0 1.0 1.0 1.0 ---
38GL3M30G
(8)
50
9.0
2020
12.4
2420
---
---
---
---
20
2.5
1.0 1.0 1.0 1.0 ---
38GL4M24G
30
11.3
2580
16.6
3230
---
---
---
---
25
2.5
1.0 1.0 1.0 1.0 ---
---
38GL2M36G
(7)
50
8.7
2000
12.1
2410
---
---
---
---
20
2.5
1.0 1.0 1.0 1.0 ---
---
38GL2M48G
(7)
60
11.0
2430
15.3
3000
---
---
---
---
25
2.5
1.0 1.0 1.0 1.0 ---
---
Heat pump
A
A
W
A
W
A
W
A
W
A
mm
2
mm
2
38YY2M18G
50
8.5
1920
11.7
2300
7.9
1810
10.5
2060
20
2.5
1.0 1.0 1.0 1.0 1.0 1.0
38YY2M21G
55
9.5
2180
14.2
2760
10.1
2280
15.0
2880
25
2.5
1.0 1.0 1.0 1.0 1.0 1.0
38YY2M24G
60
10.6
2470
15.9
3140
10.5
2410
15.7
3060
25
2.5
1.0 1.0 1.0 1.0 1.0 1.0
38YY(S)2M36G
(6)
50
8.3
1920
11.7
2370
8.0
1830
11.7
2300
20
2.5
1.0 1.0 1.0 1.0 1.0 1.0
38YY(S)2M48G
(6)
60
10.6
2320
12.5
2730
12.5
2780
14.6
2810
25
2.5
1.0 1.0 1.0 1.0 1.0 1.0
Table V: Electrical data
R
C
Y
O
W
2
Nominal conditions
230V ~ 50Hz
PrEN14511-5
indoor 27
°
C d.b. 19
°
C w.b.
outdoor 35
°
C d.b. 24
°
C w.b.
Nominal conditions
230V ~ 50Hz
PrEN14511-5
indoor 27
°
C d.b. 19
°
C w.b.
outdoor 35
°
C d.b. 24
°
C w.b.
Peak conditions
198V ~ 50Hz
PrEN14511-5
indoor 27
°
C
outdoor 24
°
C d.b. 18
°
C w.b.
Peak conditions
198V ~ 50Hz
PrEN14511-5
indoor 32
°
C d.b. 23
°
C w.b.
outdoor 43
°
C d.b. 32
°
C w.b.
Heating
Cooling
Power input
(2)
Main power
connections
(5)
Indoor/Outdoor unit
connections
Wire size
(4-5)
Time-
delay fuse
gL type
Wire
size
(4-5)
Starting
current
(3)