background image

CAUTION

Refrigerant Piping Connection

1.  Cut the pipe with a pipe cutter.

2. Insert a 

fl

 are nut into the pipe and 

fl

 are the pipe.

 • 

Projection margin in 

fl

 aring : A (Unit : mm)

RIDGID

 (clutch type)

Align the centers of the connecting pipes and tighten the 

fl

 are nut as far as 

possible with your 

fi

 ngers. Then tighten the nut with a spanner and torque 

wrench as shown in the 

fi

 gure.

     

Tightening connection

Do not apply excess torque. Otherwise, the nut may crack depending on 
the conditions.

(Unit : N·m)

Outer dia. of copper pipe 

Tightening torque

Ø6.35 mm

16 to 18 (1.6 to 1.8 kgf·m)

Ø9.52 mm

30 to 42 (3.0 to 4.2 kgf·m)

Evacuating

After the piping has been connected to the indoor unit, you can perform the 
air purge together at once.

AIR PURGE

Evacuate the air in the connecting pipes and in the indoor unit using a 
vacuum pump. Do not use the refrigerant in the outdoor unit. For details, 
see the manual of the vacuum pump.

• 

Tightening torque of 

fl

 are pipe connections

 

The operating pressure of R410A 
is higher than that of R22 (approx. 
1.6 times). It is therefore necessary 
to 

fi

 rmly tighten the 

fl

 are pipe 

connecting sections (which connect 
the indoor and outdoor units) up to the 
speci

fi

 ed tightening torque. Incorrect 

connections may cause not only a 
gas leakage, but also damage to the 
refrigeration cycle.

1.  How to shape the pipes 
  Shape the pipes along the incused line on 

the outdoor unit.

2. How to 

fi

 t position of the pipes

  Put the edges of the pipes to the place with 

a distance of 85 mm from the incused line.

     Shaping pipes

     Flaring

Be sure to use a vacuum pump with counter-

fl

 ow prevention function so that 

inside oil of the pump does not 

fl

 ow backward into pipes of the air conditioner 

when the pump stops.
(If oil inside of the vacuum pump enters the air conditioner, which use R410A, 
refrigeration cycle trouble may result.)
1.  Connect the charge hose from the manifold valve to the service port of the 

packed valve at gas side.

2.  Connect the charge hose to the port of the vacuum pump.
3.  Open fully the low pressure side handle of the gauge manifold valve.
4. Operate the vacuum pump to start evacuating. Perform evacuating for 

about 15 minutes if the piping length is 20 meters. (15 minutes for 20 meters) 
(assuming a pump capacity of 27 liters per minute) Then con

fi

 rm that the 

compound pressure gauge reading is –101 kPa (–76 cmHg).

5.  Close the low pressure side valve handle of the gauge manifold valve.
6.  Open fully the valve stem of the packed valves (both gas and liquid sides).
7.  Remove the charging hose from the service port.
8.  Securely tighten the caps on the packed valves.

     Using a vacuum pump

Packed valve at liquid side

Service port (Valve core (Setting pin))

Packed valve at gas side

Vacuum

pump

Vacuum pump adapter for
counter-

fl

 ow prevention

(For R410A only)

Charge hose
(For R410A only)

Handle Hi
(Keep full closed)

Manifold valve

Pressure gauge

Compound pressure gauge

Handle Lo

Charge hose 
(For R410A only)

Connecting pipe

–101 kPa

(–76 cmHg)

•  Open the valve stem all the way out, but do not try to open it beyond the 

stopper.

•  Securely tighten the valve cap with torque in the following table:

     Packed valve handling precautions

  

A

H

Pipe size of Packed Valve

Size of Hexagon wrench

12.70 mm and smallers

A = 4 mm

15.88 mm

A = 5 mm

Cap

Cap Size (H)

Torque

Valve Rod 

Cap

H17 - H19

14~18 N·m

(1.4 to 1.8 kgf·m)

H22 - H30

33~42 N·m

(3.3 to 4.2 kgf·m)

Service Port 

Cap

H14

8~12 N·m

(0.8 to 1.2 kgf·m)

H17

14~18 N·m

(1.4 to 1.8 kgf·m)

CAUTION

• 

KEEP IMPORTANT 5 POINTS FOR PIPING WORK.

  (1)  Take away dust and moisture (inside of the connecting pipes).
  (2)  Tighten the connections (between pipes and unit).
  (3)  Evacuate the air in the connecting pipes using a VACUUM PUMP.
  (4)  Check gas leak (connected points).
  (5)  Be sure to fully open the packed valves before operation.

IMPERIAL

 (wing nut type)

Outer dia. of copper pipe

R410A

Ø6.35

1.5 to 2.0

Ø9.52

1.5 to 2.0

Outer dia.

of copper pipe

R410A tool used

Conventional tool 

used

Ø6.35

0 to 0.5

1.0 to 1.5

Ø9.52

0 to 0.5

1.0 to 1.5

Hexagon 

Hexagon 
wrench is 

wrench is 
required.

required.

Valve Rod 

Valve Rod 

Cap

Cap

Service Port 

Service Port 

Cap

Cap

90

Roughness

Obliquity

Warp

A

Die

Pipe

Flare nut

Half union

Internally
threaded side

Externally
threaded side

Use a wrench to secure.

Use a torque wrench to tighten.

Flare at
indoor unit side

Flare at
outdoor unit side

Incused line

EN

ES

FR

IT

DE

PT

PL

CZ

RU

CR

HU

TR

NL

GR

SV

FI

NO

DK

RO

BG

EE

LV

SK

SI

7

01_1115551125-EN.indd   7

01_1115551125-EN.indd   7

1/19/2558 BE   1:57 PM

1/19/2558 BE   1:57 PM

Summary of Contents for 38EYV025M

Page 1: ...AIR CONDITIONER SPLIT TYPE INSTALLATION MANUAL Indoor unit 42EQV025M 035M Outdoor unit 38EYV025M 035M 1115551125 ENGLISH...

Page 2: ...n 4 Piping and Drain Hose Installation 5 Indoor Unit Fixing 6 Drainage 6 OUTDOOR UNIT 6 Installation Place 6 Precautions about Installation in Regions with Snowfall and Cold Temperatures 6 Refrigerant...

Page 3: ...NECTING CABLE IS CONNECTED WRONGLY ELECTRIC PARTS MAY BE DAMAGED CHECK THE EARTH WIRE THAT IT IS NOT BROKEN OR DISCONNECTED BEFORE INSTALLATION DO NOT INSTALL NEAR CONCENTRATIONS OF COMBUSTIBLE GAS OR...

Page 4: ...tapes One each Optional Installation Parts Secure the outdoor unit with fixing bolts and nuts if the unit is likely to be exposed to a strong wind Use 8 mm or 10 mm anchor bolts and nuts If it is nece...

Page 5: ...place which allows easy installation of the piping to the outdoor unit A place which allows the front panel to be opened The indoor unit shall be installed as top of the indoor unit comes to at least...

Page 6: ...inal of Display unit board as shown on figure 5 tighten firmly but not over 0 12 N m 0 01 kgf m For indoor unit Air inlet grille Front panel Display board 1 2 3 Display unit Wire size 28 22AWG or 0 08...

Page 7: ...y be set on the wall When bending the connecting pipe make sure to use a spring bender so as not to crush the pipe Bend the connecting pipe within a radius of 30 mm To connect the pipe after installat...

Page 8: ...DOOR UNIT Installation Place A place which provides the spaces around the outdoor unit as shown in the diagram A place which can bear the weight of the outdoor unit and does not allow an increase in n...

Page 9: ...to start evacuating Perform evacuating for about 15 minutes if the piping length is 20 meters 15 minutes for 20 meters assuming a pump capacity of 27 liters per minute Then confirm that the compound p...

Page 10: ...ory shipment The remote control signal is not received when the settings of indoor unit and remote control are different There is no relation between A setting B setting and A room B room when connect...

Page 11: ...A 1 6 R22 R410 X O O O O O X O O O OX O O O O O O O O O O X O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O X O 2 O O O X O O O O O O O O O O Z O O R410A O O O O O O O O...

Page 12: ...8 4 6 mm 1 E 65 mm 170 mm 170 mm C mm F mm E mm D mm O O C mm 5 8 6 o o o o o o o o o o o o o 38EYV025M 38EYV035M C 600 600 D 400 600 E 45 100 F 100 100 108 mm 28 mm 600 mm 320 mm 125 mm 86 mm 102 mm...

Page 13: ...3 7 5 mm 4 x 25R 15 mm O O E 1 m 5 I Q 5 Q 7 1 2 3 1 65 mm 2 m O 5 4 45 5 7 O 1 2 I H07RN F 60245 IEC66 1 5 mm2 o 5 mm 7 I 4 6 O I O O RF Q 1 3 mm 2 80 100 180 65 mm 100 mm O 1 7 O O O 2 m 82 5 62 170...

Page 14: ...5 mm2 o O 100 mm 10 mm 10 mm 90 mm 20 cm o o 1 2 3 1 4 2 3 5 4 6 5 0 12 N m 0 01 kgf m 1 2 3 7 2 3 8 6 9 1 3 o 1 2 3 7 4 8 5 9 0 25 N m 0 03 kgf m 6 7 3 1 16L 8 3 1 25L 9 3 1 25L 0 15 N m 0 02 kgf m 1...

Page 15: ...43 mm o o o o o o 43 mm o o o o o o o o X o o o o o 5 30 mm o o Q E A o o o o o o 4 mm X o o O o o o o o o o o o o o o o o o R 30 mm X o o polisin o o o o o X o o o 1 5 2 9 28 22 AWG 0 08 0 32 mm2 4 7...

Page 16: ...Q I o o o o o o o o o o o o o o o o o O O O o o o o o o o o o o o Q o o o o o o 15 m o o 8 m o o o o o o o O 1 o o o 2 Q o o o o o o o o o o o o o o o 3 o o o o o o o o o o o o 4 o o o o o o o o o o o...

Page 17: ...A 1 2 3 4 15 20 15 20 27 101 kPa 76 cmHg 5 6 7 8 X o o o IMPERIAL 5 o R410A 6 35 1 5 2 0 9 52 1 5 2 0 N m 5 o 6 35 mm 16 18 1 6 1 8 kgf m 9 52 mm 30 42 3 0 4 2 kgf m 5 R410A 6 35 0 0 5 1 0 1 5 9 52 0...

Page 18: ...o o o o o o o o o o 3 mm o TEST RUN COOL o o RESET 10 O o o o o o o o o Auto Restart o o o o o o 2 B 1 RESET 2 3 CHECK 00 1 4 MODE CHECK B 00 2 1 A 2 A 3 Q o o o o o o o o o o o o o o o o o o o o o o...

Page 19: ......

Page 20: ...1115551125...

Reviews: