7. Refer to Table 4. Find superheat temperature located in item

6 and suction pressure. At this intersection, note suction line

temperature.

8. If a unit has a higher suction line temperature than charted

temperature, add refrigerant until charted temperature is

reached.

9. If unit has a lower suction line temperature than charted

temperature, reclaim refrigerant until charted temperature is
reached.

10. When adding refrigerant, charge in liquid form into suction

service port using a flow--restricting device.

11. If outdoor air temperature or pressure at suction valve

changes, charge to new suction line temperature indicated
on chart.

NOTE

: If line length is beyond 80 ft (24.38 m) or greater than 20

ft (6.10 m) vertical separation, See Long Line Guideline for
special charging requirements.

UNIT DAMAGE HAZARD

Failure to follow this caution may result in unit damage.

Compressor damage may occur if system is overcharged.

CAUTION

!

Table 3—Superheat Charging Table (SI)

OUTDOOR

TEMP (

_

C)

EVAPORATOR ENTERING AIR TEMPERATURE (

_

C WB)

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

13

5.0

6.7

7.8

9.4

11.1

11.9

12.8

14.4

16.1

17.8

19.4

20.6

22.2

23.3

25.0

16

3.9

5.6

6.7

8.3

10.0

10.8

11.7

13.3

15.0

16.7

18.3

20.0

21.1

22.2

23.9

18

3.3

5.6

7.2

8.9

9.7

10.6

11.7

13.3

15.0

16.7

18.3

20.0

21.1

22.8

21

3.9

5.6

7.2

8.1

8.9

10.6

11.7

13.3

15.0

16.7

18.3

20.0

21.7

24

3.3

5.0

5.8

6.7

8.3

10.0

11.7

7.8

15.6

17.2

18.9

20.6

27

2.8

3.6

4.4

6.7

8.3

10.0

11.7

13.9

15.6

17.2

19.4

29

4.4

6.1

8.3

10.6

12.2

14.4

16.7

18.3

32

2.8

5.0

7.2

8.9

11.1

13.3

15.0

17.2

35

3.3

5.6

7.8

10.0

12.2

13.9

16.1

38

4.4

6.7

8.3

11.1

12.8

15.0

41

2.8

5.0

7.2

9.4

12.2

14.4

43

3.3

6.1

8.3

11.1

13.9

46

4.4

7.8

10.0

12.8

Where a dash (–) appears, do not attempt to charge system under these conditions, or refrigerant slugging may occur. Charge must be weighed in.

NOTE

: Superheat ° C is at low---side service port.

Table 4—Required Suction--Line Temperature (

_

C)

SUPERHEAT TEMP

(° C)

SUCTION PRESSURE AT SERVICE PORT (KPA)

743

774

805

836

869

902

957

971

1005

0

1.7

2.8

3.9

5.0

6.1

7.2

8.3

9.4

10.6

1

2.8

3.9

5.0

6.1

7.2

8.3

9.4

10.6

11.7

2

3.9

5.0

6.1

7.2

8.3

9.4

10.6

11.7

12.8

3

5.0

6.1

7.2

8.3

9.4

10.6

11.7

12.8

13.9

4

6.1

7.2

8.3

9.4

10.6

11.7

12.8

13.9

15.0

6

7.2

8.3

9.4

10.6

11.7

12.8

13.9

15.0

16.1

7

8.3

9.4

10.6

11.7

12.8

13.9

15.0

16.1

17.2

8

9.4

10.6

11.7

12.8

13.9

15.0

16.1

17.2

18.3

9

10.6

11.7

12.8

13.9

15.0

16.1

17.2

18.3

19.4

10

11.7

12.8

13.9

15.0

16.1

17.2

18.3

19.4

20.6

11

12.8

13.9

15.0

16.1

17.2

18.3

19.4

20.6

21.7

12

13.9

15.0

16.1

17.2

18.3

19.4

20.6

21.7

22.8

13

15.0

16.1

17.2

18.3

19.4

20.6

21.7

22.8

23.9

14

16.1

17.2

18.3

19.4

20.6

21.7

22.8

23.9

25.0

15

16.7

17.8

18.9

20.0

21.1

22.2

23.3

24.4

25.6

16

17.2

18.3

19.4

20.6

21.7

22.8

23.9

25.0

26.1

17

18.3

19.4

20.6

21.7

22.8

23.9

25.0

26.1

27.2

18

19.4

20.6

21.7

22.8

23.9

25.0

26.1

27.2

28.3

19

20.6

21.7

22.8

23.9

25.0

26.1

27.2

28.3

29.4

20

21.7

22.8

23.9

25.0

26.1

27.2

28.3

29.4

30.6

21

22.8

23.9

25.0

26.1

27.2

28.3

29.4

30.6

31.7

22

23.9

25.0

26.1

27.2

28.3

29.4

30.6

31.7

32.8