Carrier 38CKE Installation Instructions Manual Download Page 3

3

MAKE REFRIGERANT TUBING CONNECTIONS

Outdoor units may be connected to indoor section using accessory

tubing package or field supplied refrigerant--grade tubing of correct
size and condition. For tubing requirements beyond 80 ft (24.38

m), consult Residential Split System Long--Line Application
Guideline. Connect tubing to fittings on outdoor unit vapor and

liquid service lines. (See Table 1.)
If refrigerant tubes or the indoor coil are exposed to atmospheric
conditions for longer than 5 minutes they must be evacuated to 500

microns to eliminate contamination and moisture in system.

Table 1—Refrigerant Connections and Recommended Liquid

and Vapor Tube Diameters (in.)

UNIT SIZE

Liquid

Rated Vapor*

Connect

Diameter

Tube

Diameter

Connect

Diameter

Tube

Diameter

018, 024, 030

3/8

3/8

3/4

3/4

036, 042, 048

7/8

7/8

060

7/8

1---1/8

* Units are rated with 25 ft. (7.6 m) of lineset. See Product Data sheet for

performance data when using different size and length linesets.

Notes

:

1. Do not apply capillary tube or fixed orifice indoor coils to these units.
2. For Tubing Set lengths between 80 and 200 ft. (24.38 and 60.96 m)

horizontal or 35 ft. (10.7 m) vertical differential 250 ft. (76.2 m) Total

Equivalent Length), refer to the Residential Piping and Longline Guide

line--- Air Conditioners and Heat Pumps using Puron refrigerant.

OUTDOOR UNIT CONNECTED TO FACTORY
APPROVED INDOOR UNIT

Outdoor unit contains correct system refrigerant charge for

operation with indoor unit of same size when connected by 15 ft

(4.57 m) of field supplied or factory accessory tubing. Check
refrigerant charge for maximum efficiency.

SWEAT CONNECTION

UNIT DAMAGE HAZARD

Failure to follow this caution may result in unit component

damage.

Service valves must be wrapped while brazing in a heat

sink material, such as a wet cloth.

CAUTION

!

Use refrigerant grade tubing. Service valves are closed from factory
and ready for brazing. After wrapping service valve with a wet

cloth, tubing set can be brazed to service valve using industry

accepted methods and materials. Consult local code requirements.
Refrigerant tubing and indoor coil are now ready for leak testing.

This check should include all field and factory joints.

MAKE ELECTRICAL CONNECTIONS

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury

or death.
Do not supply power to unit with compressor terminal box

cover removed.

!

WARNING

Be sure field wiring complies with local and national fire, safety,
and electrical codes, and voltage to system is within limits shown

on unit rating plate. Contact local power company for correction of
improper voltage. See unit rating plate for recommended circuit

protection device.

NOTE

: Operation of unit on improper line voltage constitutes

abuse and could affect unit reliability. See unit rating plate. Do not
install unit in system where voltage or phase imbalance (3 phase)
may fluctuate above or below permissible limits.

NOTE

: Use copper wire only between disconnect switch and unit.

NOTE

: Install branch circuit disconnect of adequate size per NEC

to handle unit starting current. Locate disconnect within sight from
and readily accessible from unit, per Section 440--14 of NEC.

ROUTE GROUND AND POWER WIRES

Remove access panel to gain access to unit wiring. Extend wires
from disconnect through power wiring hole provided and into unit

control box.

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury

or death.
The unit cabinet must have an uninterrupted or unbroken

ground. The ground may consist of electrical wire or metal

conduit when installed in accordance with existing electrical

codes.

!

WARNING

CONNECT GROUND AND POWER WIRES

Connect ground wire to ground connection in control box for
safety. Connect power wiring to contactor as shown in Fig. 4

CONTACTOR

L1

L1

L3

L3

L2/N

L2/N

GROUND

LUG

DISCONNECT PER

IEC AND/OR

LOCAL CODES

FIELD POWER

WIRING

GND

N FOR 1-PHASE ONLY

3-PHASE ONLY

A03226

Fig. 4

---

Line Power Connections

CONNECT CONTROL WIRING

Route 24v control wires through control wiring grommet and
connect leads to control wiring. (See Fig. 5.)
Use No. 18 AWG color coded, insulated (35

_

C minimum) wire. If

thermostat is located more than 100 ft from unit, as measured along
the control voltage wires, use No. 16 AWG color coded wire to

avoid excessive voltage drop.
Use furnace transformer, fan coil transformer, or accessory

transformer for control power, 24v/40va minimum.

NOTE

:

Use of available 24v accessories may exceed the

minimum 40va power requirement. Determine total transformer
loading and increase the transformer capacity or split the load with
an accessory transformer as required.

Reviews: