background image

Step 13—Start-Up and Check Charge

To prevent compressor damage or personal injury, observe
the following:
• Do not overcharge system with refrigerant.
• Do not operate unit in a vacuum or at negative pressure.
• Do not disable low-pressure switch
In scroll compressor applications:
• Dome temperatures may be hot.
• In 3 phase application, incorrect phasing will cause reverse
rotation, resulting in elevated noise levels, equalized pres-
sures, and reduced current draw. Correct by reversing power
connection L1 and L2 on contactor.

To prevent personal injury wear safety glasses, protective
clothing, and gloves when handling refrigerant and observe
the following:
• Back seating service valves are not equipped with Schrader
valves. Fully back seat (counter clockwise) valve stem before
removing gage port cap.
• Front seating service valves are equipped with Schrader
valves.

Do not vent refrigerant to atmosphere. Recover during system
repair or final unit disposal.

Follow these steps to properly charge a system.

1. Fully back seat (open) liquid and vapor tube service valves.

2. Unit is shipped with valve stem(s) front seated (closed) and

caps installed. Replace stem caps after system is opened to
refrigerant flow. Replace caps finger-tight and tighten with
wrench an additional 1/6 turn for front seating valves (female
hex stem) or 1/12 turn for back seating valves (male square
stem).

3. Close electrical disconnects to energize system.

4. Set room thermostat at desired temperature.

5. Set room thermostat to HEAT or COOL and fan to ON or

AUTO mode, as desired. Operate unit for 15 minutes. Check
system refrigerant charge.

6. Factory charge is shown on outdoor unit rating plate. Adjust

charge in cooling mode by following procedure shown on the
charging table. Check charge in heating mode by following
procedure shown on heating check chart. Both are located on
outdoor unit.

SEQUENCE OF OPERATION

NOTE:

Defrost control board may be equipped with 5-minute

lockout timer which may be initiated upon any interruption of
power.

With power supplied to indoor and outdoor units, transformer is
energized.

Cooling

On a call for cooling, thermostat makes circuits R-O, R-Y, and
R-G. Circuit R-O energizes reversing valve, switching it to cooling
position. Circuit R-Y energizes contactor, starting outdoor fan
motor and compressor circuit. R-G energizes indoor unit blower
relay, starting the indoor blower motor on high speed.

When the thermostat is satisfied, its contacts open, de-energizing
the contactor and blower relay. Compressor and motors should
stop.

NOTE:

If indoor unit is equipped with a time-delay relay circuit,

the blower will run an additional 90 sec to increase system
efficiency.

Heating

On a call for heating, thermostat makes circuits R-Y and R-G.
Circuit R-Y energizes contactor, starting outdoor fan motor and
compressor. Circuit R-G energizes indoor blower relay, starting
blower motor on high speed.

Should temperature continue to fall, R-W2 is made through
second-stage room thermostat bulb. Circuit R-W2 energizes a
sequencer, bringing on first bank of supplemental electric heat and
providing electrical potential to second heater sequencer (if used).
If outdoor temperature falls below setting of outdoor thermostat
(field-installed option), contacts close to complete circuit and bring
on second bank of supplemental electric heat.

When thermostat is satisfied, its contacts open, de-energizing the
contactor and sequencer. All heaters and motors should stop.

Defrost

The defrost control is a time/temperature control which includes a
field-selectable (quick-connects located at board edge) time period
between defrost cycles (30, 50, and 90 minutes), factory set at 90
minutes.

The electronic timer and defrost cycle start only when contactor is
energized and defrost thermostat is closed.

The defrost mode is identical to cooling mode except that outdoor
fan motor stops and second-stage heat is turned on to continue
warming conditioned space.

CARE AND MAINTENANCE

For continuing high performance and to minimize possible equip-
ment failure, it is essential that periodic maintenance must be
performed on this equipment.

Leave User’s Manual with homeowner. Explain system operation
and periodic maintenance requirements outlined in manual. Fre-
quency of maintenance may vary depending upon geographic
areas, such as coastal applications which require more frequent
maintenance.

5

Summary of Contents for 38BYW

Page 1: ...installation of equipment 1 Locate unit away from windows 2 Ensure that vapor and liquid tube diameters are appropriate to capacity of unit 3 Run refrigerant tubes as directly as possible by avoiding...

Page 2: ...per local climate and code requirements to provide clearance above estimated snowfall level and ensure adequate drainage of unit Step 6 Check Defrost Thermostat Check defrost thermostat to ensure it...

Page 3: ...alve To prevent damage to unit or service valves observe the following Use a brazing shield Wrap service valves with wet cloth or use a heat sink material Connect outdoor unit to indoor sections using...

Page 4: ...th CONNECT GROUND AND POWER WIRES Connect ground wire to ground connection in control box for safety Connect power wiring to contactor as shown in Fig 9 CONNECT CONTROL WIRING Route 24 v control wires...

Page 5: ...ling On a call for cooling thermostat makes circuits R O R Y and R G Circuit R O energizes reversing valve switching it to cooling position Circuit R Y energizes contactor starting outdoor fan motor a...

Page 6: ...deline For buried line applications refer to Residential Split System Buried Line Application Guideline Required for Low Ambient Controller full modulation feature and MotorMaster Control only Fig 10...

Page 7: ...NOT USED 24 VAC COM NOT USED TROUBLE OPTIONAL OUTDOOR SENSOR CONNECTION JW1 A97540 24 VAC HOT R G W W1 Y Y2 Y Y2 Y1 W2 R DH RVS COOLING C B L S1 S2 Y W2 CARRIER PROGRAMMABLE THERMOSTAT MODEL 2S FK4C...

Page 8: ...4 VAC COM HEAT STAGE 2 CUT JW1 SHR SHR FA FB FC FH FAN COIL SMART HEAT ODT A97410 24 VAC HOT R C Y G O RVS COOLING W2 OTHER HP THERMOSTAT FA FB FC FH FAN COIL SMART HEAT HEAT PUMP E R C Y G O W2T W3 W...

Page 9: ...NALS MUST BE PRESENT 8 Y1 AND O CONNECTIONS TO 2 STAGE FURNACES MAY NOT EXIST OR MAY ONLY BE A WIRE RATHER THAN A SCREW TERMINAL Fig 13 Typical 24 v Circuit Connections using Carrier Model DF Thermost...

Page 10: ...10...

Page 11: ...oduct theory and skills programs is available using popular video based formats and materials All include video and or slides plus companion book Classroom Service Training plus hands on the products...

Page 12: ...46231 38byw1si Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab 5a 5a PC 101 Catalog No 563...

Reviews: