background image

Remove indoor coil piston if unit is to be installed on system
with a TXV metering device.

Step 8—Remove Indoor AccuRater® Piston and Install
TXV

For proper unit operation and reliability, units must be
installed with a field-supplied hard shut-off TXV. Do not
install with evaporator coils having capillary tube metering
devices or piston.

After removing existing AccuRater from indoor coil, install
field-supplied bi-flow hard shut-off TXV kit. (See Fig. 5 and 6.)

For TXV kit part number and charging instruction, refer to TXV
label on your unit. If indoor unit (fan coil) comes factory equipped
with a bi-flow hard shut off TXV, no TXV change is required.

Install TXV kit to indoor coil as follows:

1. Install suction tube adapter.

2. Install liquid flare-to-sweat adapter.

3. Connect external equalizer tube to fitting on suction tube

adapter.

4. Position sensing bulb on horizontal portion of suction tube

adapter. Secure using supplied hardware.

5. Insulate bulb after installation. (See Fig. 5.)

6. Leak check all connections.

Step 9—Make Tubing Connections

Relieve pressure and recover all refrigerant before system
repair or final unit disposal to avoid personal injury or death.
Use all service ports and open all flow-control devices,
including solenoid valves.

To prevent compressor damage DO NOT bury more than 36
in. of refrigerant tubing. If ANY tubing is buried, provide 6
in. vertical rise at service valve.

To prevent damage to unit or service valves observe the
following:
• Use a brazing shield.
• Wrap service valves with wet cloth or use a heat sink
material.

Connect outdoor unit to indoor sections using accessory tubing
package or field-supplied tubing of refrigerant grade, correct size,
and condition. For tubing requirements beyond 50 ft, consult your
local distributor or the Long-Line Application Guideline. Refer to
Fig. 7 for refrigerant tube dimensions and connections.

If refrigerant tubing or indoor coil is exposed to atmosphere, it
must be evacuated to a minimum of 500 microns to eliminate
contamination and moisture in the system.

SWEAT CONNECTION

1. Consult local code requirements.

2. Remove plastic retainer holding outdoor piston in the liquid

service valve and connect sweat/flare adapter provided to
valve. (See Fig. 8.)

Fig. 5—Typical TXV Installation

A88382

THERMOSTATIC
EXPANSION
VALVE

EQUALIZER
TUBE

SENSING
BULB

COIL

Fig. 6—Positioning of Sensing Bulb

A81032

2  O'CLOCK

10  O'CLOCK

SENSING  BULB

STRAP

SUCTION  TUBE

8  O'CLOCK

4  O'CLOCK

7

8

 IN. OD &  SMALLER

LARGER  THAN 

 

7

8

 IN. OD

 

Fig. 7—Refrigerant Tube Dimensions/Connections

UNIT SIZE

LIQUID TUBE

VAPOR TUBE

Conn Dia

Tube Dia

Conn Dia

Tube Dia

024

3/8

3/8

5/8

5/8

030, 036

3/8

3/8

3/4

3/4

042, 048

3/8

3/8

7/8

7/8

060

3/8

3/8

7/8

1-1/8

NOTE: Tube diameters are for lengths up to 50 ft. For tubing lengths greater
than 50 ft, consult your local distributor.

A97009

LIQUID LINE CONN

FIELD CONTROL 
SUPPLY CONN

7

8

″ 

DIA HOLE

FIELD POWER 
SUPPLY CONN

7

8

″ 

DIA HOLE WITH 

1

8

″ 

DIA KNOCKOUT

AND 1 

3

8

″ 

DIA

KNOCKOUT

AIR DISCHARGE

SUCTION LINE CONN

3

Summary of Contents for 38BYW

Page 1: ...installation of equipment 1 Locate unit away from windows 2 Ensure that vapor and liquid tube diameters are appropriate to capacity of unit 3 Run refrigerant tubes as directly as possible by avoiding...

Page 2: ...per local climate and code requirements to provide clearance above estimated snowfall level and ensure adequate drainage of unit Step 6 Check Defrost Thermostat Check defrost thermostat to ensure it...

Page 3: ...alve To prevent damage to unit or service valves observe the following Use a brazing shield Wrap service valves with wet cloth or use a heat sink material Connect outdoor unit to indoor sections using...

Page 4: ...th CONNECT GROUND AND POWER WIRES Connect ground wire to ground connection in control box for safety Connect power wiring to contactor as shown in Fig 9 CONNECT CONTROL WIRING Route 24 v control wires...

Page 5: ...ling On a call for cooling thermostat makes circuits R O R Y and R G Circuit R O energizes reversing valve switching it to cooling position Circuit R Y energizes contactor starting outdoor fan motor a...

Page 6: ...deline For buried line applications refer to Residential Split System Buried Line Application Guideline Required for Low Ambient Controller full modulation feature and MotorMaster Control only Fig 10...

Page 7: ...NOT USED 24 VAC COM NOT USED TROUBLE OPTIONAL OUTDOOR SENSOR CONNECTION JW1 A97540 24 VAC HOT R G W W1 Y Y2 Y Y2 Y1 W2 R DH RVS COOLING C B L S1 S2 Y W2 CARRIER PROGRAMMABLE THERMOSTAT MODEL 2S FK4C...

Page 8: ...4 VAC COM HEAT STAGE 2 CUT JW1 SHR SHR FA FB FC FH FAN COIL SMART HEAT ODT A97410 24 VAC HOT R C Y G O RVS COOLING W2 OTHER HP THERMOSTAT FA FB FC FH FAN COIL SMART HEAT HEAT PUMP E R C Y G O W2T W3 W...

Page 9: ...NALS MUST BE PRESENT 8 Y1 AND O CONNECTIONS TO 2 STAGE FURNACES MAY NOT EXIST OR MAY ONLY BE A WIRE RATHER THAN A SCREW TERMINAL Fig 13 Typical 24 v Circuit Connections using Carrier Model DF Thermost...

Page 10: ...10...

Page 11: ...oduct theory and skills programs is available using popular video based formats and materials All include video and or slides plus companion book Classroom Service Training plus hands on the products...

Page 12: ...46231 38byw1si Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab 5a 5a PC 101 Catalog No 563...

Reviews: