Electrical data

 

*

Permissible limits of the voltage range at which unit will operate satisfactorily. Operation outside these limits may result in unit failure.

† Time-delay fuse.
‡ Length shown is as measured 1 way along the wire path between the unit and the service panel for voltage drop not to exceed 2%.

**

If wire is applied at ambient greater than 30°C (86°F), consult Table 310-16 of the NEC (ANSI/NFPA 70). The ampacity of nonmetallic-sheathed cable (NM), 
trade name ROMEX, shall be that of 60°C (140°F) conductors, per the NEC (ANSI/NFPA 70) Article 336-26. If other than uncoated (non-plated), 60°or 75°C 
(140°or 167°F) insulation, copper wire (solid wire for 10 AWG and smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the 
NEC (ANSI/NFPA 70).

FLA

— Full Load Amps 

LRA

— Locked Rotor Amps

MCA

— Minimum Circuit Amps 

RLA

— Rated Load Amps

NOTE: 

Control circuit is 24v on all units and requires external power source. Copper wire must be used from service disconnect to unit. All motors/compressors 

contain internal overload protection.

A-weighted sound power (dBA)

 

NOTE: Tested in accordance with ARI Standard 270-95. (Not listed with ARI).

UNIT 

SIZE-SERIES

V/PH

60 Hz

OPER VOLTS*

COMPRESSOR

FAN

FLA

MCA

MIN WIRE

SIZE**

60

°

C/75

°

C

MAX

LENGTH

(Ft)

60

°

C/75

°

C‡

MAX FUSE†

OR CKT

BKR AMPS

Max

Min

LRA

RLA

018-30
024-30
030-30
036-30
042-30
048-30
060-30

208-230/1

253

197

45.0
54.0
72.5
88.0

104.0
137.0
148.0

10.6
12.0
16.7
17.8
23.2
23.9
32.1

0.5
1.1
1.1
1.1
1.1
1.1
1.4

13.8
16.1
22.0
23.4
30.1
31.0
41.5

14/14
14/14
12/12
12/12

8/10
8/10

6/8

71/67
60/57
71/67
66/63

104/63
124/76
156/88

20
25 
30 
35 
50 
45 
60

UNIT

SIZE-SERIES

STANDARD 

RATING

TYPICAL OCTAVE BAND SPECTRUM (without tone adjustment)

125

250

500

1000

2000

4000

8000

018-30

78

69.5

68.0

68.0

69.5

61.0

58.0

57.0

024-30

78

70.5

69.5

69.5

73.0

65.0

63.5

58.0

030-30

78

71.5

71.5

70.5

72.0

65.0

62.0

59.0

036-30

78

68.5

69.0

69.0

71.0

66.0

61.5

61.0

042-30

78

69.0

72.5

71.5

73.0

68.0

66.5

63.0

048-30

78

77.5

68.0

70.0

71.5

68.5

64.5

60.5

060-30

80

74.5

73.5

74.5

74.0

72.0

69.0

65.0

Summary of Contents for 38BYG Series

Page 1: ...ng season All models are listed with UL U S and Canada CEC and ARI FEATURES BENEFITS Electrical Range All units are offered in single phase 208 230v Size Range 38BYG is available in 7 nominal sizes fr...

Page 2: ...ischarge Muffler Incorporated to minimize low frequency sound and pressure pulsation generated by compressor discharge gas Weather Protective Cabinet Steel is protected with a galvanized coating and t...

Page 3: ...2 5 22 40 20 2 6 CONNECTION VALVE In ID Sweat Liquid 5 8 3 4 3 4 3 4 7 8 7 8 7 8 Vapor 3 8 3 8 3 8 3 8 3 8 3 8 3 8 REFRIGERANT TUBES In OD Vapor 5 8 3 4 3 4 3 4 7 8 1 1 8 1 1 8 Liquid 3 8 3 8 3 8 3 8...

Page 4: ...Thermostatic Expansion Valve Hard Shutoff Size 060 Standard Low Pressure Switch All Sizes KHAHI0101HPS High Pressure Switch All Sizes P504 8083S RCD Liquid Line Filter Drier Bi flow Sizes 018 036 P504...

Page 5: ...indoor coil 5 Crankcase Heater An electric resistance heater which mounts to the base of the compressor to keep the lubricant warm during off cycles Improves compressor lubrication on restart and mini...

Page 6: ...during operation in cooling mode only For outdoor temperatures down to 20 F 28 9 C it maintains condensing temperature at 100 F 10 F 37 8 C 12 C Usage Guideline A MotorMaster Low Ambient Controller or...

Page 7: ...ce Copper wire must be used from service disconnect to unit All motors compressors contain internal overload protection A weighted sound power dBA NOTE Tested in accordance with ARI Standard 270 95 No...

Page 8: ...16 3 3 16 5 8 3 11 16 18 1 8 19 3 4 21 5 8 14 3 8 18 7 8 22 1 16 10 3 4 11 14 1 4 22 1 2 x 22 1 2 024 30 30 27 15 16 3 3 16 3 4 6 1 2 23 1 2 27 1 4 29 1 8 20 26 3 8 29 9 16 15 1 2 15 11 3 4 30 x 30 0...

Page 9: ...DOOR TEMPERATURE F 10 0 10 20 30 40 50 60 70 80 70 60 50 40 30 20 10 80 38BYG024 F A B 4ANF030 38BYG036 F A B 4AN F B 042 38BYG048 FK4CNB005 38BYG060 FK4CNB006 BASED ON INDOOR ENT AIR AT 70 F AND AT R...

Page 10: ...80 10 65 23 600 3 24 14 100 2 20 7 3 CE3AA030 23 000 NONE 12 00 10 80 23 600 3 32 14 200 2 24 7 5 CF5AA024 22 600 NONE 11 80 10 60 23 600 3 18 14 100 2 18 7 3 CK3BA024 22 400 NONE 11 70 10 75 23 600...

Page 11: ...AA036 28 400 TDR 13 00 11 15 29 000 3 32 17 900 2 38 7 8 CK3BA036 28 800 TDR 13 00 11 35 29 000 3 46 18 000 2 42 7 8 CK5A CK5BA036 28 800 TDR 13 00 11 35 29 000 3 46 18 000 2 42 7 8 CK5A CK5BT036 28 8...

Page 12: ...5A CK5BA042 33 800 TDR 13 50 11 50 35 200 3 60 22 000 2 56 8 0 CK5A CK5BT042 33 800 TDR 13 50 11 50 35 200 3 60 22 000 2 56 8 0 COILS 58CV A X 155 22 VARIABLE SPEED FURNACE CC5A CD5AA042 33 800 TDR 13...

Page 13: ...00 11 50 42 000 3 52 26 600 2 64 8 0 COILS 58CV A X 110 22 VARIABLE SPEED FURNACE CC5A CD5AC048 39 000 TDR 13 00 11 50 42 000 3 28 26 200 2 56 7 8 CC5A CD5AW048 39 000 TDR 13 00 11 65 42 000 3 44 26...

Page 14: ...0 3 62 32 800 2 60 8 0 FC4CN F B 048 46 000 TDR TXV 11 50 9 90 48 000 3 40 32 600 2 50 7 6 FC4CN F B 060 47 500 TDR TXV 11 70 10 00 48 000 3 48 33 000 2 52 7 8 FC4CNB054 48 000 TDR TXV 12 10 10 45 48...

Page 15: ...000 2 40 7 5 CK5A CK5BA060 54 500 TDR 11 50 9 90 60 000 3 28 39 000 2 40 7 5 CK5A CK5BT060 54 500 TDR 11 50 9 90 60 000 3 28 39 000 2 40 7 5 CK5A CK5BX060 56 500 TDR 12 00 10 20 60 000 3 30 38 500 2 4...

Page 16: ...7 5 1 53 17 2 17 1 1 71 16 5 16 5 1 92 15 8 15 8 2 14 15 0 15 0 2 37 57 17 8 17 8 1 53 17 2 17 2 1 72 16 5 16 5 1 91 15 8 15 8 2 12 15 0 15 0 2 38 72 21 6 11 7 1 58 20 7 11 4 1 78 19 7 11 1 1 98 18 7...

Page 17: ...26 3 24 2 22 5 22 5 22 5 14 0 18 5 17 9 22 4 22 5 2 01 2 01 2 01 2 01 2 01 25 2 23 2 21 6 21 7 21 7 13 6 18 2 17 5 21 7 21 7 2 22 2 21 2 21 2 21 2 21 24 2 22 2 20 6 20 9 20 9 13 3 17 8 17 1 20 9 20 9...

Page 18: ...77 25 6 25 6 3 07 24 5 24 5 3 40 23 2 23 2 3 76 27 7 27 7 2 48 26 7 26 7 2 77 25 6 25 6 3 07 24 5 24 5 3 40 23 3 23 3 3 76 Multipliers for Determining the Performance With Other Indoor Sections Indoo...

Page 19: ...31 8 3 28 30 6 30 6 3 60 29 2 29 2 3 94 27 8 27 8 4 32 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Ca...

Page 20: ...3 87 26 6 22 6 4 24 32 5 31 6 2 92 31 2 30 8 3 21 29 8 29 8 3 53 28 5 28 5 3 87 27 1 27 1 4 25 32 2 32 2 2 92 31 0 31 0 3 21 29 8 29 8 3 53 28 5 28 5 3 87 27 1 27 1 4 25 1350 72 67 63 62 57 39 2 21 5...

Page 21: ...4 35 2 35 2 4 64 4 59 4 54 4 57 4 57 37 4 34 5 32 1 33 6 33 6 22 5 30 8 29 5 33 6 33 6 5 07 5 01 4 96 4 99 4 99 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Si...

Page 22: ...4 17 4 11 4 07 4 08 4 08 39 4 36 2 33 7 34 4 34 4 22 1 29 6 28 6 34 4 34 4 4 56 4 50 4 45 4 47 4 47 37 3 34 2 31 9 32 8 32 8 21 3 28 9 27 8 32 8 32 8 4 98 4 92 4 87 4 89 4 89 1675 72 67 63 62 57 45 8...

Page 23: ...Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA 060 0 96 1 05 COILS 58CV A X 135 22 VARIABLE SPEED FURNACE CC5A CD5AC 048 0 93 1...

Page 24: ...6 32 49 2 49 2 6 98 46 6 46 6 7 70 2000 72 67 8 35 6 5 39 64 7 34 5 5 96 61 5 33 4 6 59 58 1 32 2 7 26 54 4 31 0 7 99 67 62 6 46 3 5 31 59 7 45 2 5 87 56 6 44 0 6 49 53 4 42 7 7 15 50 0 41 4 7 87 63...

Page 25: ...36 13 1 11 6 1 41 15 3 13 9 1 49 17 8 17 8 1 58 20 5 20 5 1 71 23 6 23 6 1 88 550 8 01 7 37 1 29 9 58 8 81 1 33 11 4 10 4 1 37 13 3 11 8 1 42 15 5 14 1 1 49 18 0 18 0 1 59 20 7 20 7 1 71 23 9 23 9 1...

Page 26: ...5 31 8 31 1 31 5 31 8 2 30 2 25 2 23 75 725 825 925 9 25 9 44 9 61 8 51 8 68 8 84 1 86 1 88 1 91 11 9 12 1 12 2 10 9 11 1 11 2 1 93 1 94 1 96 14 4 14 6 14 8 13 2 13 3 13 5 1 99 2 00 2 01 17 1 17 2 17...

Page 27: ...9 3 29 3 2 76 34 1 34 1 2 98 38 6 38 6 3 12 12 0 11 0 2 22 14 9 13 7 2 30 18 0 16 5 2 37 21 5 19 1 2 47 25 4 23 1 2 60 29 5 29 5 2 76 34 3 34 3 2 93 38 2 38 2 3 07 Multipliers for Determining the Perf...

Page 28: ...2 61 22 1 20 2 2 71 26 2 23 3 2 83 30 7 27 9 2 97 35 7 35 7 3 16 40 6 40 6 3 28 43 6 43 6 3 39 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Heating Indoo...

Page 29: ...39 18 4 16 9 2 48 22 1 20 2 2 57 26 2 23 3 2 70 30 7 27 9 2 84 35 8 35 8 3 03 40 9 40 9 3 17 44 8 44 8 3 32 15 2 14 0 2 43 18 7 17 1 2 51 22 4 20 4 2 60 26 5 23 5 2 72 31 0 28 2 2 86 36 1 36 1 3 03 40...

Page 30: ...3 58 3 60 41 9 42 5 43 0 41 9 42 5 43 0 3 79 3 78 3 79 49 0 49 7 50 3 49 0 49 7 50 3 4 08 4 05 4 05 56 5 57 3 57 9 56 5 57 3 57 9 4 42 4 38 4 38 Multipliers for Determining the Performance With Other...

Page 31: ...16 3 20 31 6 32 0 32 4 28 1 28 4 28 8 3 27 3 28 3 32 36 5 37 0 37 4 33 2 33 7 34 0 3 42 3 43 3 45 42 4 43 0 43 5 42 4 43 0 43 5 3 63 3 62 3 64 49 7 50 4 51 0 49 7 50 4 51 0 3 91 3 89 3 89 57 3 58 1 58...

Page 32: ...rs for Determining the Performance With Other Indoor Sections Indoor Section Size Heating Indoor Section Size Heating Capacity Power Capacity Power CC5A CD5AA 060 1 00 1 10 COILS 58CV A X 135 22 VARIA...

Page 33: ...5 57 69 3 69 3 5 97 79 7 79 7 6 41 2000 28 1 25 9 4 41 33 5 30 8 4 59 39 2 35 7 4 77 45 3 40 2 4 96 52 5 47 8 5 20 60 6 60 6 5 49 70 1 70 1 5 87 79 2 79 2 6 18 2250 28 5 26 2 4 45 33 8 31 1 4 61 39 5...

Page 34: ...unit should be level in all horizontal planes 7 Maximum elevation of indoor coil above or below base of outdoor unit is indoor coil above 50 ft indoor coil below 150 ft See items 8 and 9 following 8...

Page 35: ...35...

Page 36: ...d start up Unit Cabinet Unit cabinet will be constructed of galvanized steel bonderized and coated with a powder coat paint Fans Condenser fan will be direct drive propeller type discharging air upwar...