
Fig. 6—Label Wiring 327414-101
A05019
FACTORY POWER WIRING
FIELD POWER WIRING
FACTORY CONTROL WIRING
FIELD CONTROL WIRING
CONDUCTOR ON CIRCUIT
BOARD
COMPONENT CONNECTION
1/4 - INCH QUICK CONNECT
TERMINALS
FIELD SPLICE
JUNCTION
CAPACITOR (DUAL RUN)
CRANKCASE HEATER
COMPRESSOR
CONTACTOR
CIRCUIT BOARD
DEFROST THERMOSTAT
DEFROST RELAY AND
CIRCUITRY
DISCHARGE TEMP. SWITCH
HIGH PRESSURE SWITCH
LOW PRESSURE SWITCH
OUTDOOR FAN MOTOR
PHASE ROTATION MONITOR
REVERSING VALVE
SOLENOID
CAP
*CH
COMP
CONT
CB
DFT
DR
*DTS
*HPS
*LPS
OFM
PRM
RVS
* MAY BE FACTORY OR FIELD INSTALLED.
-LEGEND-
327414-101 REV. B
SCHEMATIC DIAGRAM (LADDER FORM)
CONNECTION DIAGRAM
PRM LED INDICATOR
NOTE
OFF: NO 24VAC
ON: OK
FLASH: PHASE PROBLEM
1. Compressor damage may occur if system is over
charged.
2. This unit is factory charged with R-22 in accordance
with the amount shown on the rating plate. The
charge is adequate for most systems using
matched coils and tubing not over 15 feet long.
The best performance will be achieved when the
unit operates with a suction gas superheat at the
compressor inlet of 5 ºF at normal rating conditions
of the air conditioning and refrigeration, institute
(ARI). This chart may be used to approximate the
charge if ARI rating conditions cannot be obtained.
ARI rating conditions are equivalent to DOE test "A"
conditions. See product data literature for required
indoor air flow rates and for use of line lengths over
15 Ft.
3. Relieve pressure and recover all refrigerant before
system repair or final unit disposal. Use all service
ports and open all flow-control devices, including
solenoid valves.
1. Compressor and fan motor furnished with
inherent thermal protection.
2. To be wired in accordance with National
Electric Code (N.E.C.) and local codes.
3. N.E.C. class 2, 24V circuit, min. 40 VA required.
4. Use copper conductors only, from disconnect
to unit.
5. Must use thermostat and sub-base as stated
in pre-sale literature.
6. If indoor section has a transformer with a
grounded secondary, connect the grounded
side to "C" on the circuit board.
7. If any of the original wire, as supplied, must
be replaced, use the same or equivalent wire.
8. Check all electrical connections inside control
box for tightness.
9. Do not attempt to operate unit until service
valves have been opened.
10. It is imperative to connect 3Ø field power
to unit with correct phasing. The Phase
Rotation Monitor will not allow the contactor
to be energized if thephasing is not correct.
If phasing is reversed, simply interchange any two
of the three power connections on the field side.
11. Use conductors suitable for at least 75ºC (167ºF).
NOTES:
CAUTION
COOLING ONLY
PROCEDURE
EVAPORATOR ENTERING AIR ºF WB.
TEMP °F
OUTDOOR
50
TABLE I - SUPERHEAT CHARGING TABLE
(SUPERHEAT ºF AT LOW-SIDE SERVICE PORT)
52 54 56 58 60 62 64 66 68 70 72 74 76
55
9
37
60
7
65
-- 6
70
-- -- 7
75
-- -- -- 6 9 12 15 18 21 24 28 31 34 37
80
-- -- -- -- 5 8 12 15 18 21 25 28 31 35
85
-- -- -- -- -- -- 8 11 15 19 22 26
90
-- -- -- -- -- --
--
--
--
--
--
--
--
-- -- -- -- -- -- --
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
-- --
--
5 9 13 16 20 24 27 31
95
6
100
8 12 15 20 23 27
5 9 13 17 22 26
6
8
--
--
-- --
-- -- --
105
110
115
91
89
87
85
83
81
79
77
75
40
89
87
85
83
81
79
77
75
73
38
87
85
83
81
79
77
75
73
71
36
85
83
81
79
77
75
73
71
69
34
83
81
79
77
75
73
71
69
67
32
81
79
77
75
73
71
69
67
65
30
79
77
75
73
71
69
67
65
63
28
77
75
73
71
69
67
65
63
61
26
75
73
71
69
67
65
63
61
59
24
73
71
69
67
65
63
61
59
57
22
71
69
67
65
63
61
59
57
55
20
69
67
65
63
61
59
57
55
53
18
67
65
63
61
59
57
55
53
51
16
65
63
61
59
57
55
53
51
49
14
63
61
59
57
55
53
51
49
47
12
61
59
57
55
53
51
49
47
45
10
59
57
55
53
51
49
47
45
43
8
57
55
53
51
49
47
45
43
41
6
55
53
51
49
47
45
43
41
39
4
53
51
49
47
45
43
41
39
37
2
51
49
47
45
43
41
39
37
35
0
85.7
82.4
79.2
76.0
73.0
70.0
67.1
64.2
SUCTION PRESSUR E AT SERVICE PORT PSIG.
TEMP. °F 61.5
SUPERHEAT
45
43
41
39
42
40
35
32
29
40
38
35
33
30
38
36
33
36
33
30
27
30
27
24
33
18
29
30
22 25
14
10
23
25
20
18
14
15
11
27
23
23
18
15
12
10
26
23
20
17
14
12
24
21
19
16
13
10
21
19
16
13
10
TABLE II - REQUIRED SUCTION TUBE TEMPERATURE ºF
(MEASURED AT LOW-SIDE SERVICE PORT)
L3
L2
L1
GND
EQUIP
CONT
11
21
T3
T1
T2
OF2
OF1
DR
CONT
*CH
23
13
OFM
COMP
CAP
C
RVS
O
O
W2
R
R
Y
Y
C
DFT
DFT
DR
*LPS
*DTS
*HPS
T1
C
CONT
LOGIC
L3
L1
L2
PRM
CONT
COM
PRM
24V
OFM
L2
ALERT!
(NOTE #11)
23
13
21
11
L3
L1
EQUIP GND
SUPPLY
POWER
208/230 3Ø
CONT
CAP
COMP
T2
T1
T3
BLK
*DTS
BLK
BLU
YEL
*HPS
*LPS
*CH
RED
BLK
L3
L1
L2
CONT 24V COM
PRM
BLK
YEL
YEL
or
RED or BLK
YEL
YEL
BLK
BRN
YEL
BLK
BLK
BLU
YEL or BLU
BR
N
BR
N
BLU
GRY
YEL or BLU
YEL
ORG
ORG
or
or
RVS
BLK
BLK
DFT
BLK
or
PNK
PNK
or
BLK
WHT
YEL
CB
DR
OF1
OF2
C Y O W2 R
Y
T1
LOGIC
90
30
SP
E
E
D
UP
R
C
C
DFT
O
PNK
PNK
BRN
YEL
ORG
ORG
G
L
E
R
W2
O
Y
C
TERMINAL BLOCK
INDOOR UNIT
RED
ORN
BLK
G
W3
L
E
R
W2
O
Y
C
INDOOR THERMOSTAT (NOTE #5)
BLK
HK32EA001
1. Operate unit a minimum of
10 minutes before checking
charge.
2. Measure suction pressure
by attaching a gage to
suction valve service port.
3. Measure suction temperature
by attaching an accurate
thermistor type or electronic
thermometer to the suction
line at service valve.
4. Measure outdoor air dry-bulb
temperature with a
thermometer.
5. Measure indoor air (entering
indoor coil) wet bulb
temperature with a sling
psychrometer.
6. Refer to table I. Find out-
door temperature and
evaporator entering air wet-
bulb temperature at this
intersection note the super-
heat.
7. Refer to table II. Find super-
heat temperature located in
step 6 and suction pressure,
at this intersection note
suction line temperature.
8. If unit has a higher suction
line temperature than charted
temperature, add refrigerant
until charted temperature
is reached.
9. If unit has a lower suction
line temperature than charted
temperature, remove and
recover refrigerant until
charted temperature is
reached.
10. If outdoor air temperature
or pressure at suction valve
changes, charge to new
suction line temperature
indicated on chart.
11. This procedure is valid when
indoor air flow is within
+/- 21% of its rated cfm.
FIELD SELECTED TIME PERIOD
BETWEEN DEFROST CYCLES (MINUTES)
JUMPERED TEST PINS (USE METAL OBJECT), FIELD SPEED-UP CYCLE
HEAT CYCLE:
90 MIN. ACCELERATED TO 21 SEC.
60 MIN. ACCELERATED TO 14 SEC.
50 MIN. ACCELERATED TO 12 SEC.
30 MIN. ACCELERATED TO 7 SEC.
10 MIN. ACCELERATED TO 2 SEC.
DEFROST CYCLE:
90
30
SPEED
UP
50
**
**
50
**
**
BOARD MAY HAVE 60
AS MIDDLE SELECTION
7