Installation Instructions

CONTENTS

Page

INTRODUCTION

. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

INSTALLATION

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

General

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

• VARIABLE AIR VOLUME CONTROLS

— 37HS1 UNIT WITH 23-IN. DIFFUSER

• VARIABLE AIR VOLUME CONTROLS

— 37HS1 UNIT WITH 47-IN. DIFFUSER

AND 37HS2 UNIT

• VARIABLE AIR VOLUME CONTROLS

— 37HS4 UNIT

• INTERCONNECTING TUBING, ALL MODELS

AIRFLOW ADJUSTMENT

. . . . . . . . . . . . . . . . . . . . 9

Maximum Airflow (Cfm) Adjustment

. . . . . . . . . . 9

Minimum Airflow (Cfm) Adjustment

. . . . . . . . . . 9

INTRODUCTION

These instructions describe the installation and adjust-

ment of the universal variable air volume (VAV) control pack-
age. This package contains all necessary control devices and
hardware for mounting the system-powered controls on 37HS1,
37HS2 and 37HS4 Moduline® units.

Note that for certain applications, additional control pack-

ages are required and must be ordered separately. These

include wall thermostats, warm-up valves, changeover valves
and electric warm-up valves. Separate installation instruc-
tions are provided in these packages.

This package supplements the individual VAV control pack-

ages offered for specific Moduline models. Table 1 shows
the control packages available for specific models and the
universal VAV package. Note that the constant volume con-
trol package applies to all 37HS models. Figure 1 shows the
contents of the universal VAV control package.

Table 1 — Volume Control Package Numbers

UNIT

VARIABLE

AIR

VOLUME*

CONSTANT

AIR VOLUME or

WALL THERMOSTAT

APPLICATIONS

Package Number

37HS1

37HS900001

37HS900003

37HS2

37HS900002

37HS900003

37HS4

37HS900004

37HS900003

*The same volume controller is used for all 37HS models; however,

other components in the VAV control packages differ.

UNIT

UNIVERSAL VARIABLE AIR VOLUME

CONTROL PACKAGE—DIFFUSER THERMOSTAT

Package Number

37HS1
37HS2
37HS4

37HS900005

Fig. 1 — Contents of the Universal VAV Control Package

120

100

80

40

CFM

%

37HS

Universal Variable Air Volume Control Package

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book 3
Tab

6a

PC 201

Catalog No. 533-716

Printed in U.S.A.

Form 37HS-6SI

Pg 1

7-91

Replaces: New

Summary of Contents for 37HS Series

Page 1: ...age supplements the individual VAV control pack ages offered for specific Moduline models Table 1 shows the control packages available for specific models and the universal VAV package Note that the c...

Page 2: ...th of fitting See Fig 3 3 Push the diffuser baffle into the space between side dif fusers and down onto the center diffuser at the end away from the unit Then push down the end close to the unit The b...

Page 3: ...and onto the side diffusers to hold thermostat in place Make sure that thermostat le ver will rotate 11 Connect the thermostat to the volume controller with the rubber tube with spring 12 Remove cap f...

Page 4: ...he end close to the unit The baffle will form around the legs of the diffuser spacer and lock onto the center diffuser See Fig 14 Baffle should fill space between side diffusers between unit end and t...

Page 5: ...thermostat and onto the side diffusers to hold thermostat in place See Fig 20 Make sure that thermostat lever will rotate 10 Remove cap from the aspirator supply port on the unit control block Connect...

Page 6: ...Then push down the end close to the unit The baffle will form around the legs of the diffuser spacer and lock onto the center diffuser See Fig 23 Baffle should fill space between side diffusers betwe...

Page 7: ...ever 37AG501302 and replace it with lever 37AH501182 Snap lever over die cast stud taking care to lock lever slot on the thermostat case hook 9 Remove the 51 2 in long clear plastic tube from ther mos...

Page 8: ...es See Interconnect ing Tubing All Models on this page INTERCONNECTING TUBING ALLMODELS See Fig 31 For 2 units controlled by a single volume controller 1 Use 1 4 in OD FR tubing Connect tubing to the...

Page 9: ...l MODEL PLENUM SIZE in FIRST UNIT IN AIR SERIES NUMBER OF UNITS ON ONE CONTROLLER Single Unit Units in Air Series 2 3 4 5 37HS1 5 x 7 X 7 x 7 X X X X 9 x 9 X X X X X 11 x 11 X X X X X 37HS2 7 x 7 X 9...

Page 10: ...CFM 100 120 80 40 H K 0 8 Z Z 0 3 0 MAXIMUM CFM LEVER VOLUME CONTROLLER S O OPEN MINIMUM CFM STAR WHEEL S O CFM 120 100 80 40 Fig 32 Minimum and Maximum Airflow Adjustments 37HS Controller 10...

Page 11: ......

Page 12: ...nufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 3 Tab 6a PC 201 Catalog No 533 716 Printed in U S A F...

Reviews: