VARIABLE AIR VOLUME CONTROLS — 37HS4 UNIT
From the universal control package, select the following com-
ponents (see Fig. 21):

• filter assembly
• pneumatic tubing,

11

16

in. long

• volume controller
• diffuser baffle, wide, 3

5

8

in. long

• thermostat/aspirator assembly
• thermostat lever, no. 37AH501182
• clear plastic tube, 5

3

4

in. long

• white foam thermostat gasket
• 2-in. offset rubber tube
• brass tee
• thermostat mount spring clip

Control Installation, 37HS4 Unit

1. Remove the plugs from the high-pressure and low-

pressure ports located at the control block of the unit.

2. Remove cap from bellows fitting and install

11

16

-in. long

piece of

1

4

-in. OD pneumatic adapter tubing onto the

bellows fitting (push on full length of fitting). See Fig. 22.

3. Push the diffuser baffle into the space between side dif-

fusers and down onto the center diffuser at the end away
from the unit. Then push down the end close to the unit.
The baffle will form around the legs of the diffuser spacer
and lock onto the center diffuser. See Fig. 23. Baffle should
fill space between side diffusers between unit end and
thermostat.

4. To prepare the control filter for installation, be sure that

the bellows chamber filter plug is pushed tightly into
the correct connection. Figure 24 shows the connection
ports on both sides of the filter. The lower bellows port
on the unit side and the small bellows pressure connec-
tion on the control side should be capped or plugged
before installation.

5. Moisten the 2 O-rings with water, then push the filter

into the unit control block and onto bellows connection
until the standoffs rest on the unit end plate.

120

100

80

40

CFM

%

Fig. 21 — Components Selected From

Universal Control Package for

Installation on 37HS4

BELLOWS
FITTING

FOR
DIFFUSER
THERMOSTAT
ASPIRATOR

HIGH

LOW

Fig. 22 — Typical 37HS Air Terminal

Before Installation of Controls

Fig. 23 — Diffuser Baffle Assembly

Fig. 24 — Filter/Manifold Connections

6

Summary of Contents for 37HS Series

Page 1: ...age supplements the individual VAV control pack ages offered for specific Moduline models Table 1 shows the control packages available for specific models and the universal VAV package Note that the c...

Page 2: ...th of fitting See Fig 3 3 Push the diffuser baffle into the space between side dif fusers and down onto the center diffuser at the end away from the unit Then push down the end close to the unit The b...

Page 3: ...and onto the side diffusers to hold thermostat in place Make sure that thermostat le ver will rotate 11 Connect the thermostat to the volume controller with the rubber tube with spring 12 Remove cap f...

Page 4: ...he end close to the unit The baffle will form around the legs of the diffuser spacer and lock onto the center diffuser See Fig 14 Baffle should fill space between side diffusers between unit end and t...

Page 5: ...thermostat and onto the side diffusers to hold thermostat in place See Fig 20 Make sure that thermostat lever will rotate 10 Remove cap from the aspirator supply port on the unit control block Connect...

Page 6: ...Then push down the end close to the unit The baffle will form around the legs of the diffuser spacer and lock onto the center diffuser See Fig 23 Baffle should fill space between side diffusers betwe...

Page 7: ...ever 37AG501302 and replace it with lever 37AH501182 Snap lever over die cast stud taking care to lock lever slot on the thermostat case hook 9 Remove the 51 2 in long clear plastic tube from ther mos...

Page 8: ...es See Interconnect ing Tubing All Models on this page INTERCONNECTING TUBING ALLMODELS See Fig 31 For 2 units controlled by a single volume controller 1 Use 1 4 in OD FR tubing Connect tubing to the...

Page 9: ...l MODEL PLENUM SIZE in FIRST UNIT IN AIR SERIES NUMBER OF UNITS ON ONE CONTROLLER Single Unit Units in Air Series 2 3 4 5 37HS1 5 x 7 X 7 x 7 X X X X 9 x 9 X X X X X 11 x 11 X X X X X 37HS2 7 x 7 X 9...

Page 10: ...CFM 100 120 80 40 H K 0 8 Z Z 0 3 0 MAXIMUM CFM LEVER VOLUME CONTROLLER S O OPEN MINIMUM CFM STAR WHEEL S O CFM 120 100 80 40 Fig 32 Minimum and Maximum Airflow Adjustments 37HS Controller 10...

Page 11: ......

Page 12: ...nufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 3 Tab 6a PC 201 Catalog No 533 716 Printed in U S A F...

Reviews: