background image

10

English

4.2 - Water coil

4.2.1 - Removal procedure for the water coil

CAUTION: Before any work, it is essential that the 
power supply to the device is disconnected.

•   Close the isolation valves on the manifolds.

•   Drain the isolated unit using the purge device 

provided.

•   Disconnect the hydraulic hoses by unscrewing the 

union nuts.

•   Remove the actuators, taking care to mark the cold 

valve and hot valve.

•   Disconnect the condensate drain hose held in place by 

a collar (not supplied by Carrier).

 •   Remove the water flow control valve bodies. 

Depending on the configuration of the 36XB, the 

valve coupling may be fitted with a hot/cold 

changeover switch which must not be removed.

•   Open the grille: Fig. 10-11.

•   Remove the safety device: Fig 6.

•   Remove the bracket for the condensate pan, then the 

pan itself:  
Fig. 14.

• 

Remove the four retaining screws for the water coil: 

Fig. 15.

•   After work on the pan/coil assembly is complete, refit 

the assembly in the reverse order to removal, ensuring 

that all the gaskets are replaced (new gaskets fitted) 

and that the coil inlet/outlet connections have been 

made water-tight using a suitable sealing compound.

• 

Purge all air from the coil during refilling.

ATTENTION: It is recommended that the valve bodies 
are tightened on the coils with great care (25 N

·

m is 

sufficient) to ensure no damage is caused.

4.2.2 - Water inlet/outlet positions

Water inlets/outlets, all sizes: Fig. 17

Left-hand connections: Fig 17a

Right-hand connections: Fig 17b.

ATTENTION: Ensure the flow direction indicated by an 

arrow on the valves is observed, based on the connection 
and type of valve.

4.3 - Condensate pan

4.3.1 - Removal procedure for the condensate pan:

CAUTION: Before any work, it is essential that the 
power supply to the device is disconnected.

•   Open the grille: Fig. 10-11

•   Remove the safety device: Fig 6

•   Remove the condensate drain piping

•   Remove the bracket for the condensate pan, then the 

pan itself:  
Fig. 14.

•   Once work on the assembly is complete, refit the 

assembly in the reverse order to removal.

Note: To clean the condensate pan, refer to the relevant 
local legislation.

4.4 - Fresh air connection spigot

This is fitted in place from inside the unit. The duct must 

be attached to the spigot using a clamp or adhesive; it must 
not be screwed in or riveted.

ATTENTION: When the fresh air duct is fitted, make sure 

the spigot is fully inserted to ensure the best possible seal.

Ensure that the maximum supply air temperature does not 

exceed 60°C.

Ensure that the device is not lifted using the spigot. Do not 

place any loads on this component, and take care not to 
damage it using tools or during installation.

4.5 - Air filter option and access

4.5.1 - Description

The Carrier Hybrid Air Terminal can be equipped with a 

disposable filter as per standard EN 779.

Fire classification for the medium is M1, metal wire frame.

The filter must be released when the grille is opened:

•   Open the grille: Fig. 10-11

•   Remove the safety device: Fig 6

•   Remove the filters and replace them: Fig. 16

•   Once work is complete, refit the assembly in the 

reverse order to removal.

4.5.2 - Air filter replacement

The filter must be replaced regularly. The service life of a 

filter depends on the level of clogging, which varies 

according to its conditions of use.

If a clogged filter is not replaced, the pressure drop 

increases and it may start to release its stored dust, 
adversely affecting the performance of the unit (reduction 

of the air flow rate). 

4.6 - Fresh air flow controller option

The 36XB Hybrid Air terminal can be equipped (as an 

option) with a fresh air flow controller with a variable flow 

rate from 0 to 41.6 l/s (0 to 150 m

3

/h). 

This is connected to the Carrier digital controller and can 

adjust the fresh air intake flow rate in two ways 

•   Either to a fixed flow rate set by the installer, which 

can be reconfigured as required

•   Or based on the CO

2

 rate; in this case, it is connected 

to a CO

2

 sensor via the Carrier digital controller (the 

CO

2

 sensor is located on the air return).

NOTE: For a fresh air flow controller with a variable 

flow rate, the upstream pressure in the fresh air duct must 

be at least 180 Pa.

Summary of Contents for 36XB

Page 1: ...36XB Translation of original document Hybrid Air Terminal INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS...

Page 2: ...2 5 Conformity 8 3 InstALLAtIon oF the UnIt 8 3 1 Coordination between the unit and suspended ceiling 8 3 2 Installation procedure 9 3 3 Removal procedure 9 4 CoMPonents 9 4 1 Fan motor assemblies 9...

Page 3: ...3 1 60 cm 60 cm 3 2 4 5 6 7 9 10 8 1 3 11...

Page 4: ...4 13 14 12 15...

Page 5: ...5 16a 18 17b 17a 16b...

Page 6: ...ting multiple units to the same drainage manifold 9 Condensate drain pipe 9a Siphon height greater than 50mm 10 Procedure for opening the grille 11 Procedure for opening the grille 12 Removal of the e...

Page 7: ...ure for opening the grille The grille is held in place at two points at each end of the diffuser in the supply air zone Fig 2 Insert the special Carrier tool ref 36XB500085M in the third slot on the s...

Page 8: ...evices connected to it The wiring of the components which make up the different control systems and the communication buses must be carried out in accordance with the latest rules and regulations by p...

Page 9: ...on prepared connect the piping Carrier recommends using the flexible hoses which can be provided as accessories Each hose is fitted with a 1 2 gas union nut depending on the model Remember to fit a ga...

Page 10: ...e refit the assembly in the reverse order to removal Note To clean the condensate pan refer to the relevant local legislation 4 4 Fresh air connection spigot This is fitted in place from inside the un...

Page 11: ...e valve coupling may be fitted with a hot cold changeover switch which must not be removed Fit the new valve body to the coil fit new gaskets Refit the condensate pan coil assembly Refit the actuators...

Page 12: ...No 10005 09 2014 Replace No New Printed in the European Union The manufacturer reserves the right to change the product specifications without notice...

Reviews: