EN-7
EN-7
EnGLisH
En
Controller-side connections (J2)
1
COM IN
2
COM OUT/SUI occupation LED
3
0 V d.c.
4
+12 V d.c.
5
On/off input 1 for chilled beam 1
6
0 V d.c.
7
Room temperature sensor input for
chilled beam 2
8
Setpoint offset input (Setpoint in)
9
0 V d.c.
10
Room temperature sensor for chilled
beam 1
11
On/off input 1 for chilled beam 2
12
0 V d.c.
Connector J2
1 2 3 4 5 6
7 8 9 0
@
!
7
@
1
6
For the connection on the user interface side refer to the
installation manual for this interface.
4.3.5 - room temperature sensor connections
9
0
Cable
Connector J2
Room temperature sensor connection on:
chilled beam 1
chilled beam 2
4.3.6 - Connection of the digital inputs (Di)
This is a volt-free contact for any parameter setting.
Digital inputs 1 are wired to connector J2, and digital
inputs 2 are wired to connector Q11. The maximum length
of the contact loop is 30 m.
@
6
5
!
DI1
Cable
Dry contact
Connector J2
DI1
Chilled beam 1
Chilled beam 2
Q11
Terminal
Function
1
GND
2
DI2 chilled beam 2
3
GND
4
DI2 chilled beam 1
5
GND
6
24 V
Operating principle of connector Q11:
1
Push on the white part to open the connecting hole.
This is not necessary, if the wire is single-strand or
tinned.
2
Insert the stripped cable (max. 7 mm) by pushing it
into the hole.
3
Release the white part and pull lightly on the cable to
ensure that the connection has been made.
Cable insertion hole
Open hole using a pointed tool
7 9
1 2 3 4
2 3
8
0
Connector J2
Cable
J2
J19
ZUI2 or CRC2
SUI
IR2
Location of connector J19 relative to J2
4.3.7 - User interface connection (ZUi2, CrC2, sUi, ir2)
4.3.8 - Controller supply
The controller supply is from the network:
230 V a.c. (± 10 %) 50 Hz or 60 Hz.
The network wiring connection is made to the disconnect
device integrated into chilled beam 1 (with mother board
and daughter board).
The connection cable section must be calculated, based on
the maximum capacity of the chilled beam to which the
controller is connected. The quality and the installation
must comply with the recommendations of standard IEC
60364.
CONNECTION TO THE PROTECTION CIRCuIT
(EARTH): The earth supply cable ensures the continuity of
the protection circuit. It must always be connected at the
earth terminal provided.