IMPORTANT:
Never use a pressure water spray without a large diffuser.
Concentrated and/or rotating water jets are strictly forbidden.
Never use a fluid with a temperature above 45 °C to clean the
air-cooled exchangers.
Correct and frequent cleaning (approximately every three
months) will prevent two thirds of corrosion problems. Protect
the electrics box during cleaning operations.
13.7 -
Water type heat exchanger
Check that:
-The insulation has not been detached or torn during
operations,
-The heaters and probes are operating and correctly
positioned in their supports,
-The water-side connections are clean and show no sign of
leakage,
-The periodic inspections required by local regulations have
been carried out
13.8 -
Variable frequency drive
IMPORTANT: Before any work on the variable frequency
drive, ensure that the circuit is isolated and there is no voltage
present (reminder: The capacitors take approximately
5 minutes to discharge once the circuit breaker has been
opened). Only appropriately qualified personnel are
authorised to work on the variable frequency drive.
In case of any alarm or persistent problem related to the variable
frequency drive, contact the manufacturer's service department.
The variable frequency drives fitted on the units do not require a
dielectric test, even if being replaced: they are systematically
checked before delivery. Moreover, the filtering components
installed in the variable frequency drive can falsify the measurement
and may even be damaged. If there is a need to test the insulation
of a component (fan motors and pumps, cables, etc.), the variable
frequency drive must be disconnected from the power circuit.
13.9 - Refrigerant volume
It is essential to run the unit in cooling mode to find out whether
the charge is correct; this is done by checking the actual
subcooling.
Following a slight leak, it will be possible to detect a drop in the
refrigerant charge from the initial charge, and this will affect the
subcooling value obtained at the air-cooled exchanger outlet;
it cannot, however, be detected in heating mode.
IMPORTANT:
it is therefore not possible to optimise the charge in heating
mode following a leak. The unit must be run in cooling mode
if the charge needs topping up.
13.10 - Refrigerant properties
R32 properties
Saturated temperatures (°C) based on the relative pressure (in kPa)
Saturated temp.
Relative
pressure
Saturated temp.
Relative
pressure
Saturated temp.
Relative
pressure
Saturated temp.
Relative
pressure
-20
306
4
822
28
1730
52
3189
-19
321
5
851
29
1778
53
3264
-18
337
6
881
30
1828
54
3341
-17
354
7
912
31
1878
55
3420
-16
371
8
943
32
1929
56
3500
-15
388
9
974
33
1982
57
3581
-14
406
10
1007
34
2035
58
3664
-13
424
11
1040
35
2090
59
3748
-12
443
12
1074
36
2145
60
3833
-11
463
13
1109
37
2202
61
3920
-10
483
14
1144
38
2260
62
4009
-9
503
15
1181
39
2318
63
4099
-8
524
16
1218
40
2378
64
4191
-7
546
17
1256
41
2439
65
4284
-6
568
18
1295
42
2501
66
4379
-5
591
19
1334
43
2565
67
4476
-4
614
20
1375
44
2629
68
4575
-3
638
21
1416
45
2695
69
4675
-2
662
22
1458
46
2762
70
4777
-1
687
23
1501
47
2830
0
713
24
1545
48
2899
1
739
26
1635
49
2969
2
766
25
1590
50
3041
3
794
27
1682
51
3114
13 - STANDARD MAINTENANCE
85
Summary of Contents for 30RB-170R
Page 2: ......
Page 51: ...11 13 Fan arrangement 11 MAIN COMPONENTS OF THE UNIT AND OPERATING CHARACTERISTICS 51...
Page 90: ......
Page 91: ......