background image

28

Table 6A — Unit Electrical Data, 30HXC Units

UNIT

30HXC

UNIT VOLTAGE

POWER

SUPPLY

QTY. REQD.

NO. POWER

SUPPLY

CONDUCTORS

UNIT VOLTAGE

CONTROL CIRCUIT

V-Hz

(3 Ph)

Supplied

MCA

MOCP

ICF

Rec Fuse Size

V-Hz

(Single

Ph)

Supplied

MCA 

and

MOCP

Min

Max

XL

WD

XL

WD

Min

Max

076

230-60

207

253

1

3

198.7

250

297.3

225

115-60

104

127

15

208/230-60

187

253

1

3

220.7

300

307.1

250

115-60

104

127

15

460-60

414

506

1

3

99.7

125

374.3

148.3

125

125

115-60

104

127

15

575-60

518

633

1

3

79.7

110

299.4

118.4

90

90

115-60

104

127

15

380-60

342

418

1

3

120.8

150

418.7

168.7

150

150

230-60

207

254

15

380/415-50

342

440

1

3

125.6

175

399.8

164.8

150

150

230-50

198

254

15

230-50

207

253

1

3

207.2

250

266.1

250

230-50

207

254

15

086

230-60

207

253

1

3

221.7

300

297.3

250

115-60

104

127

15

208/230-60

187

253

1

3

246.4

350

307.1

300

115-60

104

127

15

460-60

414

506

1

3

111.3

150

374.3

148.3

125

125

115-60

104

127

15

575-60

518

633

1

3

88.9

125

299.4

118.4

100

100

115-60

104

127

15

380-60

342

418

1

3

134.8

175

418.7

168.7

175

175

230-60

207

254

15

380/415-50

342

440

1

3

140.4

200

478.8

189.8

175

175

230-50

198

254

15

230-50

207

253

1

3

231.9

300

305.1

300

230-50

207

254

15

096

230-60

207

253

1

3

251.3

350

344.3

300

115-60

104

127

15

208/230-60

187

253

1

3

279.2

400

354.1

350

115-60

104

127

15

460-60

414

506

1

3

126.2

175

449.3

172.3

150

150

115-60

104

127

15

575-60

518

633

1

3

100.8

150

359.4

137.4

125

125

115-60

104

127

15

380-60

342

418

1

3

152.7

225

501.7

194.7

175

175

230-60

207

254

15

380/415-50

342

440

1

3

157.9

225

561.8

215.8

200

200

230-50

198

254

15

230-50

207

253

1

3

260.7

350

347.1

300

230-50

207

254

15

106

230-60

207

253

1

3

285.6

400

395.3

350

115-60

104

127

15

208/230-60

187

253

1

3

317.4

450

405.1

400

115-60

104

127

15

460-60

414

506

1

3

143.3

200

529.3

197.3

175

175

115-60

104

127

15

575-60

518

633

1

3

114.5

175

423.4

158.4

150

150

115-60

104

127

15

380-60

342

418

1

3

173.6

250

589.7

222.7

200

200

230-60

207

254

15

380/415-50

342

440

1

3

178.1

250

660.8

246.8

225

225

230-50

198

254

15

230-50

207

253

1

3

294.2

450

397.1

350

230-50

207

254

15

116

230-60

207

253

1

3

304.1

450

413.7

350

115-60

104

127

15

208/230-60

187

253

1

3

337.9

500

425.6

400

115-60

104

127

15

460-60

414

506

1

3

152.6

225

538.6

206.6

175

175

115-60

104

127

15

575-60

518

633

1

3

121.9

175

430.8

165.8

150

150

115-60

104

127

15

380-60

342

418

1

3

184.8

250

600.9

233.9

225

225

230-60

207

254

15

380/415-50

342

440

1

3

190.0

250

672.7

258.7

225

225

230-50

198

254

15

230-50

207

253

1

3

313.9

450

416.8

400

230-50

207

254

15

126

230-60

207

253

1

3

327.7

450

437.4

400

115-60

104

127

15

208/230-60

187

253

1

3

364.2

500

451.9

450

115-60

104

127

15

460-60

414

506

1

3

164.5

225

550.5

218.5

200

200

115-60

104

127

15

575-60

518

633

1

3

131.4

175

440.3

175.3

150

150

115-60

104

127

15

380-60

342

418

1

3

199.1

250

615.2

248.2

225

225

230-60

207

254

15

380/415-50

342

440

1

3

204.0

300

686.7

272.7

250

250

230-50

198

254

15

230-50

207

253

1

3

337.0

450

439.9

400

230-50

207

254

15

136

230-60

207

253

1

3

366.7

500

497.4

450

115-60

104

127

15

208/230-60

187

253

1

6

407.4

600

511.9

500

115-60

104

127

15

460-60

414

506

1

3

183.8

250

645.5

248.5

225

225

115-60

104

127

15

575-60

518

633

1

3

147.1

200

536.3

199.3

175

175

115-60

104

127

15

380-60

342

418

1

3

222.8

300

720.2

282.2

300

300

230-60

207

254

15

380/415-50

342

440

1

3

230.2

300

796.7

307.7

300

300

230-50

198

254

15

230-50

207

253

1

6

380.3

500

495.9

450

230-50

207

254

15

146

230-60

207

253

1

6

394.1

500

524.9

450

115-60

104

127

15

208/230-60

187

253

1

6

437.9

600

542.4

500

115-60

104

127

15

460-60

414

506

1

3

197.5

250

659.2

262.2

225

225

115-60

104

127

15

575-60

518

633

1

3

158.1

225

547.3

210.3

200

200

115-60

104

127

15

380-60

342

418

1

3

239.5

350

736.9

298.9

300

300

230-60

207

254

15

380/415-50

342

440

1

3

246.3

350

812.8

323.8

300

300

230-50

198

254

15

230-50

207

253

1

6

407.1

600

522.7

500

230-50

207

254

15

Summary of Contents for 30H

Page 1: ...al Electrical Code NEC U S A and local code requirements Allow sufficient space for wiring piping and service Install unit in an area which will not be exposed to am bient temperatures below 50 F 10 C...

Page 2: ...ERATING WEIGHT lb kg B C E L WGT DISTRIBUTION AT EACH MTG PLATE lb kg 1 2 3 4 5 6 30HXC076 5700 2586 45 87 1165 45 87 1165 32 50 826 65 22 1657 738 335 943 428 595 270 1110 503 1418 643 896 406 30HXC0...

Page 3: ...on all models Flow switch factory installed in cooler outlet victaulic nozzle UNIT OPERATING WEIGHT lb kg WGT DISTRIBUTION AT EACH MTG PLATE lb kg 1 2 3 4 5 6 30HXC116 6415 2911 728 330 1114 505 777...

Page 4: ...d on all models Flow switch factory installed in cooler outlet victaulic nozzle UNIT OPERATING WEIGHT lb kg B C WGT DISTRIBUTION AT EACH MTG PLATE lb kg 1 2 3 4 5 6 30HXC161 7452 3381 72 12 1832 50 63...

Page 5: ...utlet victaulic nozzle UNIT OPERATING WEIGHT lb kg A WGT DISTRIBUTION AT EACH MTG PLATE lb kg 1 2 3 4 5 6 30HXC206 10 581 4799 33 88 860 948 430 2406 1091 1243 564 1201 545 3133 1421 1650 748 30HXC246...

Page 6: ...EACH MTG PLATE lb kg 1 2 3 4 5 6 30HXA076 4717 2140 45 87 1165 45 87 1165 32 50 826 65 22 1657 3 88 99 41 25 1048 46 25 1175 555 252 793 360 418 190 926 420 1326 601 699 317 30HXA086 4744 2152 45 87 1...

Page 7: ...249 926 420 555 252 874 396 1498 679 908 412 30HXA146 5333 2420 551 250 930 422 555 252 883 400 1506 683 908 412 NOTES 1 Operating weight includes weight of water and refrigerant 2 Denotes center of g...

Page 8: ...zle Fig 8 Dimensions 30HXA161 186 UNIT OPERATING WEIGHT lb kg B C R S T WGT DISTRIBUTION AT EACH MTG PLATE lb kg 1 2 3 4 5 6 30HXA161 5752 2610 72 12 1832 50 63 1286 67 50 1715 51 00 1295 48 75 1238 5...

Page 9: ...factory installed in cooler outlet victaulic nozzle UNIT OPERATING WEIGHT lb kg WGT DISTRIBUTION AT EACH MTG PLATE lb kg 1 2 3 4 5 6 30HXA206 7485 3395 671 304 1702 772 879 399 850 385 2216 1005 1167...

Page 10: ...d cover insulate remaining open area for acoustic purposes 6 Recommended control wiring entry area Notch to suit and cover insulate remaining open area for acoustic purposes 7 Recommended cooler relie...

Page 11: ...1 1306 592 1154 523 3276 1486 1733 786 261 985 447 2520 1143 1311 595 1154 523 3283 1489 1739 789 271 985 447 2529 1147 1318 598 1154 523 3294 1494 1749 793 UNIT 30HXA MOUNTING PLATE NO 1 2 3 4 5 6 07...

Page 12: ...elief Valve Connection in NPTF 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 Flow Capacity lb air min 31 7 31 7 31 7 31 7 31 7 31 7 31 7 31 7 Relief Setting psig 220 220 220 220 220 220 220 220 Standard Number of P...

Page 13: ...T Std Pass 3 8 3 8 3 8 3 8 3 8 3 8 3 8 Relief Valve Connection in NPTF 3 4 3 4 3 4 3 4 3 4 3 4 3 4 Flow Capacity lb air min 31 7 31 7 31 7 31 7 31 7 31 7 31 7 Relief Setting psig 220 220 220 220 220 2...

Page 14: ...nection in NPTF 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 Flow Capacity kg air min 14 38 14 38 14 38 14 38 14 38 14 38 14 38 14 38 Relief Setting kPa 1517 1517 1517 1517 1517 1517 1517 1517 Standard Number of P...

Page 15: ...3 8 3 8 3 8 3 8 Relief Valve Connection in NPTF 3 4 3 4 3 4 3 4 3 4 3 4 3 4 Flow Capacity kg air min 14 28 14 38 14 38 14 38 14 38 14 38 14 38 Relief Setting kPa 1517 1517 1517 1517 1517 1517 1517 St...

Page 16: ...ction is recom mended using inhibited ethylene glycol or other suitable corrosion resistant antifreeze solution and electric heater tapes Heater tapes should have a rating for area ambient temperature...

Page 17: ...alled using certified drawings 2 All wiring must comply with applicable codes 3 Refer to the System Design Manual for details regarding piping techniques 4 Piping wiring switches valves vent gages str...

Page 18: ...F 17 8 C a30 4644 NOTES 1 Piping shown is for general point of connection only and is not intended to show details for a specific installation Certified field wiring and dimensional drawings are avai...

Page 19: ...losses should not exceed 4 F 15 6 C at full load A calcula tion of line loss should be performed prior to installation 30HXA UNIT SIZE CKT TOTAL LENGTH OF INTERCONNECTING PIPING FT M 0 50 0 15 50 100...

Page 20: ...086 A 11 8 15 8 15 8 15 8 B 11 8 15 8 15 8 15 8 096 A 11 8 15 8 15 8 21 8 B 11 8 15 8 15 8 15 8 106 A 15 8 15 8 21 8 21 8 B 13 8 13 8 13 8 13 8 116 A 15 8 15 8 21 8 21 8 B 13 8 15 8 15 8 15 8 126 A 15...

Page 21: ...EQUIVALENT LINE LENGTH FT 30 40 50 60 70 80 90 105 141 176 211 246 281 316 100 110 120 130 140 150 352 387 422 457 492 527 TONS COOLING kW COOLING 160 170 180 190 200 562 598 633 668 703 3 1 8 79 4 m...

Page 22: ...ess than the brine freeze point plus 2 F 1 1 C Maintaining flow through the cooler is required for freeze protection Fan Cycling Pressure Switches 09DK Condensers In order to provide proper head press...

Page 23: ...dance with good piping practices and so that the piping does not cross in front of the condenser head Use flexible connections on the condenser piping to reduce vibration trans mission Offset the pip...

Page 24: ...of TB5 are for alarm relay The maximum load allowed for the alarm relay is 75va sealed 360va inrush at 115v or 230v Separate field power supply is not required 8 Terminals 7 and 9 of TB2 are for cond...

Page 25: ...dily accessible from the unit in compliance with NEC Article 440 14 See Tables 6A and 6B for unit electrical data See Tables 7A and 7B for compressor electrical data All units have a single location f...

Page 26: ...factory supplied but is limited to 75 va sealed 360 va inrush See Fig 18 Terminals 10 and 12 of TB5 have been provided for a field supplied chilled water fluid pump relay CWP Power for the field supp...

Page 27: ...0 F 15 C are expected refer to separate 09DK condenser unit installation instructions for low ambient operation using accessory Motormaster V con trol minimum load accessories also required MINIMUM LO...

Page 28: ...158 4 150 150 115 60 104 127 15 380 60 342 418 1 3 173 6 250 589 7 222 7 200 200 230 60 207 254 15 380 415 50 342 440 1 3 178 1 250 660 8 246 8 225 225 230 50 198 254 15 230 50 207 253 1 3 294 2 450 3...

Page 29: ...00 115 60 104 127 15 575 60 518 633 1 3 185 4 250 630 4 255 4 225 225 115 60 104 127 15 380 60 342 418 1 3 280 8 400 881 8 363 8 350 350 230 60 207 254 15 380 415 50 342 440 1 3 289 4 400 984 6 398 6...

Page 30: ...225 115 60 104 127 15 380 60 342 418 1 3 268 6 400 1000 0 380 0 350 350 230 60 207 254 15 380 415 50 342 440 1 3 281 0 400 1059 2 402 2 350 350 230 50 198 254 15 230 50 207 253 1 6 464 2 700 648 9 60...

Page 31: ...700 0 1518 7 653 7 600 600 230 50 198 254 15 230 50 230 50 207 254 15 Ckt A 207 253 1 6 486 0 700 0 771 0 600 Ckt B 207 253 1 6 415 4 700 0 638 0 500 246 230 60 115 60 104 127 15 Ckt A 207 253 1 6 59...

Page 32: ...6 209 98 1 209 230 60 106 7 209 88 3 209 460 60 53 6 104 44 3 104 575 60 42 8 83 35 4 83 380 60 64 9 115 53 7 115 230 50 111 8 213 92 1 174 380 415 50 67 7 134 55 8 109 096 XL 208 230 60 230 60 460 60...

Page 33: ...144 9 256 230 60 157 9 307 130 4 256 460 60 79 2 153 65 5 128 575 60 63 3 123 52 3 102 380 60 95 9 169 79 2 141 230 50 161 7 305 134 9 255 380 415 50 97 8 191 81 7 160 136 XL 208 230 60 230 60 460 60...

Page 34: ...171 XL 208 230 60 230 60 460 60 86 1 580 103 1 685 575 60 68 8 484 82 4 548 380 60 104 2 641 124 8 757 230 50 380 415 50 105 8 715 128 6 856 171 WD 208 230 60 190 6 367 228 8 433 230 60 171 5 367 205...

Page 35: ...1 216 71 2 153 103 1 216 575 60 82 4 173 56 9 123 82 4 173 380 60 124 8 239 86 2 169 124 8 239 230 50 212 5 432 145 7 305 212 5 432 380 415 50 128 6 270 88 2 191 128 6 270 261 XL 208 230 60 230 60 460...

Page 36: ...3 8 307 230 60 154 7 367 129 4 307 460 60 77 6 183 64 9 153 575 60 62 1 147 51 9 123 380 60 94 0 203 78 7 169 230 50 163 9 361 134 8 305 380 415 50 99 2 226 81 5 191 096 XL 208 230 60 230 60 460 60 94...

Page 37: ...433 230 60 230 0 518 188 8 433 460 60 115 4 259 94 8 216 575 60 92 2 207 75 7 173 380 60 139 7 286 114 7 239 230 50 240 2 485 198 2 432 380 415 50 145 4 303 119 9 270 136 XL 208 230 60 230 60 460 60 1...

Page 38: ...L 208 230 60 230 60 460 60 129 6 920 157 9 1175 575 60 103 6 736 126 2 940 380 60 156 9 1017 191 2 1299 230 50 380 415 50 161 7 1226 201 2 1265 171 WD 208 230 60 286 9 581 349 6 743 230 60 258 2 581 3...

Page 39: ...106 6 259 157 9 371 575 60 126 2 297 85 1 207 126 2 297 380 60 191 2 410 129 0 286 191 2 410 230 50 332 3 638 220 3 485 332 3 638 380 415 50 201 2 400 133 4 303 201 2 400 261 XL 208 230 60 230 60 460...

Page 40: ...loaded the sight glass may be flashing This condition is normal for a partially loaded unit If the unit is fully loaded and the sight glass is flashing check EXV posi tion If it is greater than 60 ad...

Page 41: ...13 8 16 7 130 59 B 71 32 24 11 13 8 16 7 112 50 136 09DK 074 2 A 99 45 82 37 13 8 16 7 197 89 B 71 32 82 37 13 8 16 7 169 76 09AZV132FE 1 A 99 45 57 26 13 8 16 7 172 78 B 71 32 42 19 13 8 16 7 130 58...

Page 42: ...42...

Page 43: ......

Page 44: ...discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53300025 01 Printed in U S A Form 30HX 13SI Pg 44 10 08 Replaces 30HX 12SI C...

Reviews: