background image

22

30HXA PIPING, VALVE, AND FAN CYCLING PRES-

SURE SWITCH INSTALLATION
Relieve Pressure and Recover Refrigerant — The 30HXA

units are shipped from the factory with a holding charge of

nitrogen or R-134a. Before opening the refrigerant system, re-

lieve system pressure and recover system refrigerant through

the access fitting on the cooler.
30HXA Refrigerant Piping (See Fig. 14A and 14B) — When

running the refrigerant piping from the 30HXA unit to the

remote condenser(s), avoid excessive pressure drops. 

Minimiz-

ing line pressure drop is critical to the proper operation of the

unit expansion device

. Refer to Tables 2 and 3 for refrigerant

line sizing guidance. The pressure drop using R-134a refriger-

ant is different than when using R-22 refrigerant. See Tables 4

and 5 for an example of a 2 F (1.1 C) pressure drop in saturated

temperature in the discharge (hot gas) line and liquid line, re-

spectively. Refer to Fig. 15 and 16 for line sizing information

for the discharge and liquid lines for 30HXA (R-134a) units.

See Fig. 17 for double discharge riser details.

Table 4 — Discharge Line 2 F (1.1 C) Drop in

Saturated Temperature Example

Table 5 — Liquid Line 2 F (1.1 C) Drop in

Saturated Temperature Example

An inverted trap should be installed in the discharge line at

the condenser to prevent refrigerant from flowing back to the

oil separator and compressor during unit shutdown. The invert-

ed trap must extend to the height of the condenser. The

discharge line must be brazed to the back-pressure valve locat-

ed on the top of the oil separator. Be sure to wrap back-pressure

valve when brazing discharge line to avoid damaging the

valve. Liquid line solenoid valves with manual lift stems

should be installed between the field-supplied liquid line filter

driers and the unit. For proper electrical connections see

Fig. 18.

If valves are installed in the liquid lines, it is recommended

that field-supplied pressure relief valves be installed in each

liquid line and the pressure setting should be 320 psig

(2205 kPa). Most local codes require that the relief valves be

vented directly outdoors. The vent must not be smaller than the

relief valve outlet.
30HXA Low-Ambient Considerations — In installations

where outdoor ambient temperatures may be below 34 F

(1.1 C), it is recommended that inhibited ethylene glycol or

other suitable corrosion-resistant antifreeze solution be used in

the cooler loop to prevent cooler freeze-up.

If a suitable antifreeze solution is not used in the cooler

loop, chilled water pump control is required. The chiller will

automatically start the chilled water pump if the saturated suc-

tion temperature is less than the brine freeze point minus 6° F

(3.3° C) or if the entering or leaving water temperature is less

than the brine freeze point plus 2° F (1.1° C). Maintaining flow

through the cooler is required for freeze protection.
Fan-Cycling Pressure Switches (09DK Condensers) — In

order to provide proper head-pressure control in 30HXA units,

install fan-cycling pressure switches in each circuit in the liquid

line between the separate condenser unit and expansion device.

Two switches are shipped from the factory with the 30HXA

units. Refer to the 09DK condenser installation literature for

details on the location and installation of the switches. Since

the 30HXA is an HFC-134a unit, switch selection is based on

R-134a refrigerant pressures.
NOTES: The switches that are standard with the 09DK con-

densers are designed for R-22 operation and must 

not 

be used.

Instead use the switches shipped with the chiller (Part No.

HK02YB097). Switches open at 97 psig (± 10 psi), and close

at 185 psig (± 10 psi).
Back-Pressure Valve, 30HXA Units (See Fig. 19 and 20)  —

The 30HXA back-pressure valves are supplied with an integral

mounting flange. The valves mount on the 30HXA oil separa-

tor. This reduces brazing when installing the discharge piping,

and allows the installer to orient the valve in any desired

position.

Complete the steps below to install the flanged back-

pressure valves on the 30HXA chiller before running discharge

piping. Follow these steps for both refrigerant circuits.

1. Be sure to remove nitrogen charge or properly recover re-

frigerant charge before removing the blank-off plate. Re-

move the blank-off plate from the mating flange on top of

the oil separator by removing the screws from the flange.

See Fig. 19 for location.

2. Using the screws that were removed in Step 1, bolt the

flanged back-pressure valve to the mating flange on top

of the oil separator. An O-ring is included in the box with

the back-pressure valve for sealing the flange.
The valve may be oriented in any desired position in or-

der to make discharge piping easier. Install pipe hangers

where needed. Make sure no weight or stress is placed on

the back-pressure valve.

3. Once the back-pressure valve has been mounted to the

mating flange, and the piping is properly supported, a

SATURATED
DISCHARGE

TEMP

PRESSURE

R-134a

R-22

F

C

Psig

kPa

Psig

kPa

126

52.2

187.5

1293

281.6

1942

124

51.1

182.0

1255

274.3

1891

Δ

 PRESSURE

5.5

38

7.3

51

SATURATED

LIQUID

TEMP

PRESSURE

R-134a

R-22

F

C

Psig

kPa

Psig

kPa

100

37.8

124.3

857

195.9

1351

98

36.7

120.1

828

190.2

1311

Δ 

PRESSURE

4.2

29

5.7

40

IMPORTANT: The back-pressure valves are 

not

 mounted

to the 30HXA chiller at the factory. They are packaged and

supplied attached to the unit shipping skid. These valves

must

 be installed at the time of chiller installation. Failure

to install the back-pressure valves will result in improper

unit operation.

TO
CONDENSER

B

RED.
TEE

90 DEGREE
STR ELLS

FROM
CHILLER

45 DEGREE
STR ELLS

A

LEGEND

RED. TEE

Reducing Tee

STR ELLS —

Street Elbows

Fig. 17 — Double Discharge Riser

Construction Detail

Summary of Contents for 30H

Page 1: ...al Electrical Code NEC U S A and local code requirements Allow sufficient space for wiring piping and service Install unit in an area which will not be exposed to am bient temperatures below 50 F 10 C...

Page 2: ...ERATING WEIGHT lb kg B C E L WGT DISTRIBUTION AT EACH MTG PLATE lb kg 1 2 3 4 5 6 30HXC076 5700 2586 45 87 1165 45 87 1165 32 50 826 65 22 1657 738 335 943 428 595 270 1110 503 1418 643 896 406 30HXC0...

Page 3: ...on all models Flow switch factory installed in cooler outlet victaulic nozzle UNIT OPERATING WEIGHT lb kg WGT DISTRIBUTION AT EACH MTG PLATE lb kg 1 2 3 4 5 6 30HXC116 6415 2911 728 330 1114 505 777...

Page 4: ...d on all models Flow switch factory installed in cooler outlet victaulic nozzle UNIT OPERATING WEIGHT lb kg B C WGT DISTRIBUTION AT EACH MTG PLATE lb kg 1 2 3 4 5 6 30HXC161 7452 3381 72 12 1832 50 63...

Page 5: ...utlet victaulic nozzle UNIT OPERATING WEIGHT lb kg A WGT DISTRIBUTION AT EACH MTG PLATE lb kg 1 2 3 4 5 6 30HXC206 10 581 4799 33 88 860 948 430 2406 1091 1243 564 1201 545 3133 1421 1650 748 30HXC246...

Page 6: ...EACH MTG PLATE lb kg 1 2 3 4 5 6 30HXA076 4717 2140 45 87 1165 45 87 1165 32 50 826 65 22 1657 3 88 99 41 25 1048 46 25 1175 555 252 793 360 418 190 926 420 1326 601 699 317 30HXA086 4744 2152 45 87 1...

Page 7: ...249 926 420 555 252 874 396 1498 679 908 412 30HXA146 5333 2420 551 250 930 422 555 252 883 400 1506 683 908 412 NOTES 1 Operating weight includes weight of water and refrigerant 2 Denotes center of g...

Page 8: ...zle Fig 8 Dimensions 30HXA161 186 UNIT OPERATING WEIGHT lb kg B C R S T WGT DISTRIBUTION AT EACH MTG PLATE lb kg 1 2 3 4 5 6 30HXA161 5752 2610 72 12 1832 50 63 1286 67 50 1715 51 00 1295 48 75 1238 5...

Page 9: ...factory installed in cooler outlet victaulic nozzle UNIT OPERATING WEIGHT lb kg WGT DISTRIBUTION AT EACH MTG PLATE lb kg 1 2 3 4 5 6 30HXA206 7485 3395 671 304 1702 772 879 399 850 385 2216 1005 1167...

Page 10: ...d cover insulate remaining open area for acoustic purposes 6 Recommended control wiring entry area Notch to suit and cover insulate remaining open area for acoustic purposes 7 Recommended cooler relie...

Page 11: ...1 1306 592 1154 523 3276 1486 1733 786 261 985 447 2520 1143 1311 595 1154 523 3283 1489 1739 789 271 985 447 2529 1147 1318 598 1154 523 3294 1494 1749 793 UNIT 30HXA MOUNTING PLATE NO 1 2 3 4 5 6 07...

Page 12: ...elief Valve Connection in NPTF 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 Flow Capacity lb air min 31 7 31 7 31 7 31 7 31 7 31 7 31 7 31 7 Relief Setting psig 220 220 220 220 220 220 220 220 Standard Number of P...

Page 13: ...T Std Pass 3 8 3 8 3 8 3 8 3 8 3 8 3 8 Relief Valve Connection in NPTF 3 4 3 4 3 4 3 4 3 4 3 4 3 4 Flow Capacity lb air min 31 7 31 7 31 7 31 7 31 7 31 7 31 7 Relief Setting psig 220 220 220 220 220 2...

Page 14: ...nection in NPTF 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 Flow Capacity kg air min 14 38 14 38 14 38 14 38 14 38 14 38 14 38 14 38 Relief Setting kPa 1517 1517 1517 1517 1517 1517 1517 1517 Standard Number of P...

Page 15: ...3 8 3 8 3 8 3 8 Relief Valve Connection in NPTF 3 4 3 4 3 4 3 4 3 4 3 4 3 4 Flow Capacity kg air min 14 28 14 38 14 38 14 38 14 38 14 38 14 38 Relief Setting kPa 1517 1517 1517 1517 1517 1517 1517 St...

Page 16: ...ction is recom mended using inhibited ethylene glycol or other suitable corrosion resistant antifreeze solution and electric heater tapes Heater tapes should have a rating for area ambient temperature...

Page 17: ...alled using certified drawings 2 All wiring must comply with applicable codes 3 Refer to the System Design Manual for details regarding piping techniques 4 Piping wiring switches valves vent gages str...

Page 18: ...F 17 8 C a30 4644 NOTES 1 Piping shown is for general point of connection only and is not intended to show details for a specific installation Certified field wiring and dimensional drawings are avai...

Page 19: ...losses should not exceed 4 F 15 6 C at full load A calcula tion of line loss should be performed prior to installation 30HXA UNIT SIZE CKT TOTAL LENGTH OF INTERCONNECTING PIPING FT M 0 50 0 15 50 100...

Page 20: ...086 A 11 8 15 8 15 8 15 8 B 11 8 15 8 15 8 15 8 096 A 11 8 15 8 15 8 21 8 B 11 8 15 8 15 8 15 8 106 A 15 8 15 8 21 8 21 8 B 13 8 13 8 13 8 13 8 116 A 15 8 15 8 21 8 21 8 B 13 8 15 8 15 8 15 8 126 A 15...

Page 21: ...EQUIVALENT LINE LENGTH FT 30 40 50 60 70 80 90 105 141 176 211 246 281 316 100 110 120 130 140 150 352 387 422 457 492 527 TONS COOLING kW COOLING 160 170 180 190 200 562 598 633 668 703 3 1 8 79 4 m...

Page 22: ...ess than the brine freeze point plus 2 F 1 1 C Maintaining flow through the cooler is required for freeze protection Fan Cycling Pressure Switches 09DK Condensers In order to provide proper head press...

Page 23: ...dance with good piping practices and so that the piping does not cross in front of the condenser head Use flexible connections on the condenser piping to reduce vibration trans mission Offset the pip...

Page 24: ...of TB5 are for alarm relay The maximum load allowed for the alarm relay is 75va sealed 360va inrush at 115v or 230v Separate field power supply is not required 8 Terminals 7 and 9 of TB2 are for cond...

Page 25: ...dily accessible from the unit in compliance with NEC Article 440 14 See Tables 6A and 6B for unit electrical data See Tables 7A and 7B for compressor electrical data All units have a single location f...

Page 26: ...factory supplied but is limited to 75 va sealed 360 va inrush See Fig 18 Terminals 10 and 12 of TB5 have been provided for a field supplied chilled water fluid pump relay CWP Power for the field supp...

Page 27: ...0 F 15 C are expected refer to separate 09DK condenser unit installation instructions for low ambient operation using accessory Motormaster V con trol minimum load accessories also required MINIMUM LO...

Page 28: ...158 4 150 150 115 60 104 127 15 380 60 342 418 1 3 173 6 250 589 7 222 7 200 200 230 60 207 254 15 380 415 50 342 440 1 3 178 1 250 660 8 246 8 225 225 230 50 198 254 15 230 50 207 253 1 3 294 2 450 3...

Page 29: ...00 115 60 104 127 15 575 60 518 633 1 3 185 4 250 630 4 255 4 225 225 115 60 104 127 15 380 60 342 418 1 3 280 8 400 881 8 363 8 350 350 230 60 207 254 15 380 415 50 342 440 1 3 289 4 400 984 6 398 6...

Page 30: ...225 115 60 104 127 15 380 60 342 418 1 3 268 6 400 1000 0 380 0 350 350 230 60 207 254 15 380 415 50 342 440 1 3 281 0 400 1059 2 402 2 350 350 230 50 198 254 15 230 50 207 253 1 6 464 2 700 648 9 60...

Page 31: ...700 0 1518 7 653 7 600 600 230 50 198 254 15 230 50 230 50 207 254 15 Ckt A 207 253 1 6 486 0 700 0 771 0 600 Ckt B 207 253 1 6 415 4 700 0 638 0 500 246 230 60 115 60 104 127 15 Ckt A 207 253 1 6 59...

Page 32: ...6 209 98 1 209 230 60 106 7 209 88 3 209 460 60 53 6 104 44 3 104 575 60 42 8 83 35 4 83 380 60 64 9 115 53 7 115 230 50 111 8 213 92 1 174 380 415 50 67 7 134 55 8 109 096 XL 208 230 60 230 60 460 60...

Page 33: ...144 9 256 230 60 157 9 307 130 4 256 460 60 79 2 153 65 5 128 575 60 63 3 123 52 3 102 380 60 95 9 169 79 2 141 230 50 161 7 305 134 9 255 380 415 50 97 8 191 81 7 160 136 XL 208 230 60 230 60 460 60...

Page 34: ...171 XL 208 230 60 230 60 460 60 86 1 580 103 1 685 575 60 68 8 484 82 4 548 380 60 104 2 641 124 8 757 230 50 380 415 50 105 8 715 128 6 856 171 WD 208 230 60 190 6 367 228 8 433 230 60 171 5 367 205...

Page 35: ...1 216 71 2 153 103 1 216 575 60 82 4 173 56 9 123 82 4 173 380 60 124 8 239 86 2 169 124 8 239 230 50 212 5 432 145 7 305 212 5 432 380 415 50 128 6 270 88 2 191 128 6 270 261 XL 208 230 60 230 60 460...

Page 36: ...3 8 307 230 60 154 7 367 129 4 307 460 60 77 6 183 64 9 153 575 60 62 1 147 51 9 123 380 60 94 0 203 78 7 169 230 50 163 9 361 134 8 305 380 415 50 99 2 226 81 5 191 096 XL 208 230 60 230 60 460 60 94...

Page 37: ...433 230 60 230 0 518 188 8 433 460 60 115 4 259 94 8 216 575 60 92 2 207 75 7 173 380 60 139 7 286 114 7 239 230 50 240 2 485 198 2 432 380 415 50 145 4 303 119 9 270 136 XL 208 230 60 230 60 460 60 1...

Page 38: ...L 208 230 60 230 60 460 60 129 6 920 157 9 1175 575 60 103 6 736 126 2 940 380 60 156 9 1017 191 2 1299 230 50 380 415 50 161 7 1226 201 2 1265 171 WD 208 230 60 286 9 581 349 6 743 230 60 258 2 581 3...

Page 39: ...106 6 259 157 9 371 575 60 126 2 297 85 1 207 126 2 297 380 60 191 2 410 129 0 286 191 2 410 230 50 332 3 638 220 3 485 332 3 638 380 415 50 201 2 400 133 4 303 201 2 400 261 XL 208 230 60 230 60 460...

Page 40: ...loaded the sight glass may be flashing This condition is normal for a partially loaded unit If the unit is fully loaded and the sight glass is flashing check EXV posi tion If it is greater than 60 ad...

Page 41: ...13 8 16 7 130 59 B 71 32 24 11 13 8 16 7 112 50 136 09DK 074 2 A 99 45 82 37 13 8 16 7 197 89 B 71 32 82 37 13 8 16 7 169 76 09AZV132FE 1 A 99 45 57 26 13 8 16 7 172 78 B 71 32 42 19 13 8 16 7 130 58...

Page 42: ...42...

Page 43: ......

Page 44: ...discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53300025 01 Printed in U S A Form 30HX 13SI Pg 44 10 08 Replaces 30HX 12SI C...

Reviews: