background image

23

field-supplied 

1

/

4

-in. (6.4 mm) copper line 

must 

be run

from the 

1

/

4

-in. NPT port on the back-pressure valve cap

to the 

1

/

4

-in. SAE flare fitting on the motor cooling line.

The equalizer line must be installed in order for the unit to

function properly.
NOTE: A ball valve can be installed in the equalizer line

to facilitate servicing.

4. After mounting the back-pressure valve to the unit, prop-

erly supporting it, and running the 

1

/

4

-in. equalizer line,

the discharge piping may be installed.

5. Repeat Steps 1-4 for the other refrigerant circuit.

The 30HXA206-271 machines have 2 back pressure valves

on circuit A. The equalizer line should connect to the 

1

/

4

-in.

NPT ports on each valve then tee together and run to the 

1

/

4

-in.

SAE flare tee provided in the circuit A economizer transducer

connection. The discharge piping from each valve should tee

together as close to the machine as possible. See Fig. 20.
Evacuation and Dehydration — Because the 30HXA systems

use polyolester oil, which can absorb moisture, it is important

to minimize the amount of time that the system interior is left

exposed to the atmosphere. Minimizing the exposure time of

the oil to the atmosphere will minimize the amount of moisture

that needs to be removed during evacuation.

Once all of the piping connections are complete, leak test

the unit and then pull a deep dehydration vacuum. Connect the

vacuum pump to the charging valve at the bottom of the cooler

and 

to the liquid line service valve. For best results, it is recom-

mended that a vacuum of at least 500 microns (0.5 mm Hg) be

obtained. Afterwards, to ensure that no moisture is present in

the system, perform a standing vacuum-rise test.

With the unit in deep vacuum (500 microns or less), isolate

the vacuum pump from the system. Observe the rate-of-rise of

the vacuum in the system. If the vacuum rises by more than

50 microns in a 30-minute time period, then continue the

dehydration process. Maintain a vacuum on the system until

the standing vacuum requirement is met. This will ensure a dry

system.

By following these evacuation and dehydration procedures,

the amount of moisture present in the system will be

minimized. It is required that replaceable core liquid line filter

driers be installed between the condenser(s) and the expansion

devices to capture any foreign debris and provide additional

moisture removal capacity. Be sure to consider the pressure

drop of the filter drier when determining piping requirements.

The factory-supplied strainer may be removed to reduce

pressure drop provided the filter drier is located as close to the

unit as possible.

For further 30HXA piping instructions, proceed to the

section titled Install Pressure Relief Refrigerant Vent Piping.
30HXC PIPING AND VALVE INSTALLATION
30HXC Condenser Connections — The inlet fluid connec-

tion is always the lower of the 2 condenser connections. A

screen strainer with a minimum of 20 mesh must be installed

ahead of the condenser inlet (within 10 ft [3.05 m]) to prevent

debris from damaging the internal condenser tubes.

The outlet water connection is the upper connection of the

2 connections. The condenser has victaulic nozzles to connect

field-supplied piping. Plan the piping arrangement in accor-

dance with good piping practices and so that the piping does

not cross in front of the condenser head. Use flexible

connections on the condenser piping to reduce vibration trans-

mission. Offset the piping to permit condenser head removal

for maintenance purposes. Install pipe hangers where needed.

Make sure no weight or stress is placed on the water nozzle.

Provide openings in water piping for pressure gages and

thermometers (if used). These openings should be 5 to 10 pipe

diameters from the unit water nozzles. For thorough mixing

and temperature stabilization, wells in the leaving water pipe

should extend at least 2 in. (50 mm) into the pipe.

Although condenser has an air vent, it is recommended that

a field-supplied air vent be installed in the system to facilitate

servicing. Field-supplied shut-off and balancing valves should

also be installed to facilitate servicing and flow balancing.

Locate valves in inlet and outlet lines as close to the chiller as

possible. Locate air vents at the highest point of the system

loop. See Fig. 13.

Provide drain connections at all low points in the loop to

permit complete system drainage.

30HXC Condenser Temperature Regulating Valve — For

installations where entering condensing water temperature

could be below 70 F (21.1 C), a field-supplied leaving water

temperature regulating valve is required. Operation below 70 F

(21.1 C) without this valve may cause the unit to shut down on

low oil pressure alarms.
NOTE: This valve should be a temperature-controlled valve

(DO NOT USE a pressure-controlled valve) which controls to

80 F (26.7 C) leaving water temperature. A valve that can be

controlled by a 4 to 20 mA signal is also supported by the

Comfort

Link™ control system. Figure 21 shows the installa-

tion details for the regulating valve.

INSTALL PRESSURE RELIEF REFRIGERANT VENT

PIPING — The low side relief valves on all units are provided

with 

3

/

4

-in. female NPT connections, and are located on top of

the cooler shell. See Fig. 2-9. There are 2 relief valves for

the cooler; one on each circuit. Make the vent connection to

the low side relief valve by installing a male NPT to copper

OD braze adapter. Braze a 90-degree short-radius elbow

to the adapter. This will allow enough space to make vent

connections to the elbow.

The 30HXA high side relief valves are provided with a

5

/

8

-in. SAE (Society of Automotive Engineers, U.S.A.) flare

connection. The 30HXC high side relief valves are provided

with a 

3

/

4

-in. female NPT flare connection, and are located on

the bottom of the condenser shell.

IMPORTANT: Be sure that any Schrader core installed in

the fittings is removed prior to equalizer line installation.

Failure to remove core will result in the unit not function-

ing properly.

CAUTION

Remove any sensors on the condenser nozzles before

welding connecting piping. Reinstall after welding is

complete. Failure to remove these devices may cause unit

damage. Heads are cast iron, welding is 

not

 recommended.

IMPORTANT: Before starting the unit, be sure all of the air

has been purged from the system.

IMPORTANT: A separate, field-supplied power supply

must be used with the 4 to 20 mA valve. Failure to use a

separate power supply may result in damage to the elec-

tronic chiller components.

IMPORTANT: On brine applications where leaving cooler

water is less than 34 F (1.1 C), a minimum water flow of

0.75 gpm/ton (0.14 L/s per kW) should be maintained

through the condenser at all times.

Summary of Contents for 30H

Page 1: ...al Electrical Code NEC U S A and local code requirements Allow sufficient space for wiring piping and service Install unit in an area which will not be exposed to am bient temperatures below 50 F 10 C...

Page 2: ...ERATING WEIGHT lb kg B C E L WGT DISTRIBUTION AT EACH MTG PLATE lb kg 1 2 3 4 5 6 30HXC076 5700 2586 45 87 1165 45 87 1165 32 50 826 65 22 1657 738 335 943 428 595 270 1110 503 1418 643 896 406 30HXC0...

Page 3: ...on all models Flow switch factory installed in cooler outlet victaulic nozzle UNIT OPERATING WEIGHT lb kg WGT DISTRIBUTION AT EACH MTG PLATE lb kg 1 2 3 4 5 6 30HXC116 6415 2911 728 330 1114 505 777...

Page 4: ...d on all models Flow switch factory installed in cooler outlet victaulic nozzle UNIT OPERATING WEIGHT lb kg B C WGT DISTRIBUTION AT EACH MTG PLATE lb kg 1 2 3 4 5 6 30HXC161 7452 3381 72 12 1832 50 63...

Page 5: ...utlet victaulic nozzle UNIT OPERATING WEIGHT lb kg A WGT DISTRIBUTION AT EACH MTG PLATE lb kg 1 2 3 4 5 6 30HXC206 10 581 4799 33 88 860 948 430 2406 1091 1243 564 1201 545 3133 1421 1650 748 30HXC246...

Page 6: ...EACH MTG PLATE lb kg 1 2 3 4 5 6 30HXA076 4717 2140 45 87 1165 45 87 1165 32 50 826 65 22 1657 3 88 99 41 25 1048 46 25 1175 555 252 793 360 418 190 926 420 1326 601 699 317 30HXA086 4744 2152 45 87 1...

Page 7: ...249 926 420 555 252 874 396 1498 679 908 412 30HXA146 5333 2420 551 250 930 422 555 252 883 400 1506 683 908 412 NOTES 1 Operating weight includes weight of water and refrigerant 2 Denotes center of g...

Page 8: ...zle Fig 8 Dimensions 30HXA161 186 UNIT OPERATING WEIGHT lb kg B C R S T WGT DISTRIBUTION AT EACH MTG PLATE lb kg 1 2 3 4 5 6 30HXA161 5752 2610 72 12 1832 50 63 1286 67 50 1715 51 00 1295 48 75 1238 5...

Page 9: ...factory installed in cooler outlet victaulic nozzle UNIT OPERATING WEIGHT lb kg WGT DISTRIBUTION AT EACH MTG PLATE lb kg 1 2 3 4 5 6 30HXA206 7485 3395 671 304 1702 772 879 399 850 385 2216 1005 1167...

Page 10: ...d cover insulate remaining open area for acoustic purposes 6 Recommended control wiring entry area Notch to suit and cover insulate remaining open area for acoustic purposes 7 Recommended cooler relie...

Page 11: ...1 1306 592 1154 523 3276 1486 1733 786 261 985 447 2520 1143 1311 595 1154 523 3283 1489 1739 789 271 985 447 2529 1147 1318 598 1154 523 3294 1494 1749 793 UNIT 30HXA MOUNTING PLATE NO 1 2 3 4 5 6 07...

Page 12: ...elief Valve Connection in NPTF 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 Flow Capacity lb air min 31 7 31 7 31 7 31 7 31 7 31 7 31 7 31 7 Relief Setting psig 220 220 220 220 220 220 220 220 Standard Number of P...

Page 13: ...T Std Pass 3 8 3 8 3 8 3 8 3 8 3 8 3 8 Relief Valve Connection in NPTF 3 4 3 4 3 4 3 4 3 4 3 4 3 4 Flow Capacity lb air min 31 7 31 7 31 7 31 7 31 7 31 7 31 7 Relief Setting psig 220 220 220 220 220 2...

Page 14: ...nection in NPTF 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 Flow Capacity kg air min 14 38 14 38 14 38 14 38 14 38 14 38 14 38 14 38 Relief Setting kPa 1517 1517 1517 1517 1517 1517 1517 1517 Standard Number of P...

Page 15: ...3 8 3 8 3 8 3 8 Relief Valve Connection in NPTF 3 4 3 4 3 4 3 4 3 4 3 4 3 4 Flow Capacity kg air min 14 28 14 38 14 38 14 38 14 38 14 38 14 38 Relief Setting kPa 1517 1517 1517 1517 1517 1517 1517 St...

Page 16: ...ction is recom mended using inhibited ethylene glycol or other suitable corrosion resistant antifreeze solution and electric heater tapes Heater tapes should have a rating for area ambient temperature...

Page 17: ...alled using certified drawings 2 All wiring must comply with applicable codes 3 Refer to the System Design Manual for details regarding piping techniques 4 Piping wiring switches valves vent gages str...

Page 18: ...F 17 8 C a30 4644 NOTES 1 Piping shown is for general point of connection only and is not intended to show details for a specific installation Certified field wiring and dimensional drawings are avai...

Page 19: ...losses should not exceed 4 F 15 6 C at full load A calcula tion of line loss should be performed prior to installation 30HXA UNIT SIZE CKT TOTAL LENGTH OF INTERCONNECTING PIPING FT M 0 50 0 15 50 100...

Page 20: ...086 A 11 8 15 8 15 8 15 8 B 11 8 15 8 15 8 15 8 096 A 11 8 15 8 15 8 21 8 B 11 8 15 8 15 8 15 8 106 A 15 8 15 8 21 8 21 8 B 13 8 13 8 13 8 13 8 116 A 15 8 15 8 21 8 21 8 B 13 8 15 8 15 8 15 8 126 A 15...

Page 21: ...EQUIVALENT LINE LENGTH FT 30 40 50 60 70 80 90 105 141 176 211 246 281 316 100 110 120 130 140 150 352 387 422 457 492 527 TONS COOLING kW COOLING 160 170 180 190 200 562 598 633 668 703 3 1 8 79 4 m...

Page 22: ...ess than the brine freeze point plus 2 F 1 1 C Maintaining flow through the cooler is required for freeze protection Fan Cycling Pressure Switches 09DK Condensers In order to provide proper head press...

Page 23: ...dance with good piping practices and so that the piping does not cross in front of the condenser head Use flexible connections on the condenser piping to reduce vibration trans mission Offset the pip...

Page 24: ...of TB5 are for alarm relay The maximum load allowed for the alarm relay is 75va sealed 360va inrush at 115v or 230v Separate field power supply is not required 8 Terminals 7 and 9 of TB2 are for cond...

Page 25: ...dily accessible from the unit in compliance with NEC Article 440 14 See Tables 6A and 6B for unit electrical data See Tables 7A and 7B for compressor electrical data All units have a single location f...

Page 26: ...factory supplied but is limited to 75 va sealed 360 va inrush See Fig 18 Terminals 10 and 12 of TB5 have been provided for a field supplied chilled water fluid pump relay CWP Power for the field supp...

Page 27: ...0 F 15 C are expected refer to separate 09DK condenser unit installation instructions for low ambient operation using accessory Motormaster V con trol minimum load accessories also required MINIMUM LO...

Page 28: ...158 4 150 150 115 60 104 127 15 380 60 342 418 1 3 173 6 250 589 7 222 7 200 200 230 60 207 254 15 380 415 50 342 440 1 3 178 1 250 660 8 246 8 225 225 230 50 198 254 15 230 50 207 253 1 3 294 2 450 3...

Page 29: ...00 115 60 104 127 15 575 60 518 633 1 3 185 4 250 630 4 255 4 225 225 115 60 104 127 15 380 60 342 418 1 3 280 8 400 881 8 363 8 350 350 230 60 207 254 15 380 415 50 342 440 1 3 289 4 400 984 6 398 6...

Page 30: ...225 115 60 104 127 15 380 60 342 418 1 3 268 6 400 1000 0 380 0 350 350 230 60 207 254 15 380 415 50 342 440 1 3 281 0 400 1059 2 402 2 350 350 230 50 198 254 15 230 50 207 253 1 6 464 2 700 648 9 60...

Page 31: ...700 0 1518 7 653 7 600 600 230 50 198 254 15 230 50 230 50 207 254 15 Ckt A 207 253 1 6 486 0 700 0 771 0 600 Ckt B 207 253 1 6 415 4 700 0 638 0 500 246 230 60 115 60 104 127 15 Ckt A 207 253 1 6 59...

Page 32: ...6 209 98 1 209 230 60 106 7 209 88 3 209 460 60 53 6 104 44 3 104 575 60 42 8 83 35 4 83 380 60 64 9 115 53 7 115 230 50 111 8 213 92 1 174 380 415 50 67 7 134 55 8 109 096 XL 208 230 60 230 60 460 60...

Page 33: ...144 9 256 230 60 157 9 307 130 4 256 460 60 79 2 153 65 5 128 575 60 63 3 123 52 3 102 380 60 95 9 169 79 2 141 230 50 161 7 305 134 9 255 380 415 50 97 8 191 81 7 160 136 XL 208 230 60 230 60 460 60...

Page 34: ...171 XL 208 230 60 230 60 460 60 86 1 580 103 1 685 575 60 68 8 484 82 4 548 380 60 104 2 641 124 8 757 230 50 380 415 50 105 8 715 128 6 856 171 WD 208 230 60 190 6 367 228 8 433 230 60 171 5 367 205...

Page 35: ...1 216 71 2 153 103 1 216 575 60 82 4 173 56 9 123 82 4 173 380 60 124 8 239 86 2 169 124 8 239 230 50 212 5 432 145 7 305 212 5 432 380 415 50 128 6 270 88 2 191 128 6 270 261 XL 208 230 60 230 60 460...

Page 36: ...3 8 307 230 60 154 7 367 129 4 307 460 60 77 6 183 64 9 153 575 60 62 1 147 51 9 123 380 60 94 0 203 78 7 169 230 50 163 9 361 134 8 305 380 415 50 99 2 226 81 5 191 096 XL 208 230 60 230 60 460 60 94...

Page 37: ...433 230 60 230 0 518 188 8 433 460 60 115 4 259 94 8 216 575 60 92 2 207 75 7 173 380 60 139 7 286 114 7 239 230 50 240 2 485 198 2 432 380 415 50 145 4 303 119 9 270 136 XL 208 230 60 230 60 460 60 1...

Page 38: ...L 208 230 60 230 60 460 60 129 6 920 157 9 1175 575 60 103 6 736 126 2 940 380 60 156 9 1017 191 2 1299 230 50 380 415 50 161 7 1226 201 2 1265 171 WD 208 230 60 286 9 581 349 6 743 230 60 258 2 581 3...

Page 39: ...106 6 259 157 9 371 575 60 126 2 297 85 1 207 126 2 297 380 60 191 2 410 129 0 286 191 2 410 230 50 332 3 638 220 3 485 332 3 638 380 415 50 201 2 400 133 4 303 201 2 400 261 XL 208 230 60 230 60 460...

Page 40: ...loaded the sight glass may be flashing This condition is normal for a partially loaded unit If the unit is fully loaded and the sight glass is flashing check EXV posi tion If it is greater than 60 ad...

Page 41: ...13 8 16 7 130 59 B 71 32 24 11 13 8 16 7 112 50 136 09DK 074 2 A 99 45 82 37 13 8 16 7 197 89 B 71 32 82 37 13 8 16 7 169 76 09AZV132FE 1 A 99 45 57 26 13 8 16 7 172 78 B 71 32 42 19 13 8 16 7 130 58...

Page 42: ...42...

Page 43: ......

Page 44: ...discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53300025 01 Printed in U S A Form 30HX 13SI Pg 44 10 08 Replaces 30HX 12SI C...

Reviews: